| Date |
Text |
| 2018-04-13 09:33:51 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | PERMIT #17110874 |
| | OLD CITY HALL/MARRIOTT HOTEL |
| | 4/12/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED |
| | PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE |
| | ENGINEER OF RECORD. |
| | ALL 1ST REVIEW COMMENTS NOT COMPLETELY RESOLVED ARE |
| | LISTED BELOW IN THEIR ORIGINAL NUMERICAL ORDER. |
| | |
| | 1) THE RESUBMITTED AC SUMMARY CALCULATIONS ARE NOT |
| | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER. |
| | PLEASE NOTE THAT THE OUTDOOR DRYBULB TEMPERATURE SHOWN |
| | ON M-600 DOES NOT MATCH THE TEMPERATURE SHOWN IN THE |
| | CALCS. |
| | |
| | 2) THE REVISED ENERGYGAUGE SUBMITTAL IS MISSING |
| | COMPLIANCE DATA FOR THE ODU-L5 SYSTEM. |
| | |
| | 3) IF NOT PROVIDING A COMMISSIONING PLAN AT THIS TIME, |
| | PLEASE PROVIDE A NOTE ON THE PLANS TO INDICATE A PLAN |
| | WILL BE PROVIDED AS A DEFERRED SUBMITTAL. |
| | |
| | 4) THE REQUESTED AIR BALANCE CALCULATIONS WERE NOT |
| | PROVIDED. |
| | |
| | 5) THE ENGINEER'S RESPONSE TO THE COMMENT #5 REQUESTING |
| | THE SMOKE CONTROL RATIONAL ANALYSIS STATES "THE |
| | BUILDING DOES NOT INCLUDE A SMOKE CONTROL SYSTEM AS IT |
| | IS NOT REQUIRED BY FLORIDA BUILDING CODE". THAT IS |
| | ACKNOWLEDGED, HOWEVER THE PLANS ARE INDICATING A SMOKE |
| | CONTROL SYSTEM IS BEING INSTALLED. REFER TO SHEET M-704 |
| | SMOKE CONTROL SEQUENCE AND REQUIREMENTS, M-705 SMOKE |
| | CONTROL RISERS, & M-706 SMOKE CONTROL PANEL GRAPHIC. |
| | EVIDENTLY THIS BUILDING CONTAINS A SMOKE CONTROL |
| | SYSTEM. PLEASE REFER TO SECTION 909.4 AND PROVIDE THE |
| | ANALYSIS. ADDITIONALLY PLEASE SHOW COMPLIANCE WITH THE |
| | FOLLOWING MECHANICAL CODE SECTIONS: |
| | 513.10 EQUIPMENT. |
| | EQUIPMENT SUCH AS, BUT NOT LIMITED TO, FANS, DUCTS, |
| | AUTOMATIC DAMPERS AND BALANCE DAMPERS SHALL BE SUITABLE |
| | FOR THEIR INTENDED USE, SUITABLE FOR THE PROBABLE |
| | EXPOSURE TEMPERATURES THAT THE RATIONAL ANALYSIS |
| | INDICATES, AND AS APPROVED BY THE CODE OFFICIAL. |
| | 513.10.1EXHAUSTFANS. |
| | COMPONENTS OF EXHAUST FANS SHALL BE RATED AND CERTIFIED |
| | BY THE MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE |
| | TO WHICH THE COMPONENTS WILL BE EXPOSED. THIS |
| | TEMPERATURE RISE SHALL BE COMPUTED BY: |
| | TS = (QC/MC)+ (TA) (EQUATION 5-4) |
| | WHERE: |
| | C = SPECIFIC HEAT OF SMOKE AT SMOKE-LAYER TEMPERATURE, |
| | BTU/LB F (KJ/KG ? K). |
| | M = EXHAUST RATE, POUNDS PER SECOND (KG/S). |
| | QC = CONVECTIVE HEAT OUTPUT OF FIRE, BTU/S (KW). |
| | TA = AMBIENT TEMPERATURE, F (K). |
| | TS = SMOKE TEMPERATURE, F (K). |
| | EXCEPTION: REDUCED TS AS CALCULATED BASED ON THE |
| | ASSURANCE OF ADEQUATE DILUTION |
| | 513.10.2 DUCTS. |
| | DUCT MATERIALS AND JOINTS SHALL BE CAPABLE OF |
| | WITHSTANDING THE PROBABLE TEMPERATURES AND PRESSURES TO |
| | WHICH THEY ARE EXPOSED AS DETERMINED IN ACCORDANCE WITH |
| | SECTION 513.10.1. DUCTS SHALL BE CONSTRUCTED AND |
| | SUPPORTED IN ACCORDANCE WITH CHAPTER 6. |
| | DUCTS SHALL BE LEAK TESTED TO 1.5 TIMES THE MAXIMUM |
| | DESIGN PRESSURE IN ACCORDANCE WITH NATIONALLY ACCEPTED |
| | PRACTICES. MEASURED LEAKAGE SHALL NOT EXCEED 5 PERCENT |
| | OF DESIGN FLOW. RESULTS OF SUCH TESTING SHALL BE A PART |
| | OF THE DOCUMENTATION PROCEDURE. DUCTS SHALL BE |
| | SUPPORTED DIRECTLY FROM FIRE-RESISTANCE-RATED |
| | STRUCTURAL ELEMENTS OF THE BUILDING BY SUBSTANTIAL, |
| | NONCOMBUSTIBLE SUPPORTS. |
| | EXCEPTION: FLEXIBLE CONNECTIONS, FOR THE PURPOSE OF |
| | VIBRATION ISOLATION, THAT ARE CONSTRUCTED OF APPROVED |
| | FIRE-RESISTANCE-RATED MATERIALS. |
| | 513.10.3 EQUIPMENT,INLETS AND OUTLETS. |
| | EQUIPMENT SHALL BE LOCATED SO AS TO NOT EXPOSE |
| | UNINVOLVED PORTIONS OF THE BUILDING TO AN ADDITIONAL |
| | FIRE HAZARD. OUTDOOR AIR INLETS SHALL BE LOCATED SO AS |
| | TO MINIMIZE THE POTENTIAL FOR INTRODUCING SMOKE OR |
| | FLAME INTO THE BUILDING. EXHAUST OUTLETS SHALL BE SO |
| | LOCATED AS TO MINIMIZE REINTRODUCTION OF SMOKE INTO THE |
| | BUILDING AND TO LIMIT EXPOSURE OF THE BUILDING OR |
| | ADJACENT BUILDINGS TO AN ADDITIONAL FIRE HAZARD. |
| | 513.10.4 AUTOMATIC DAMPERS. |
| | AUTOMATIC DAMPERS, REGARDLESS OF THE PURPOSE FOR WHICH |
| | THEY ARE INSTALLED WITHIN THE SMOKE CONTROL SYSTEM, |
| | SHALL BE LISTED AND CONFORM TO THE REQUIREMENTS OF |
| | APPROVED RECOGNIZED STANDARDS. |
| | 513.10.5 FANS. |
| | IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN FANS |
| | SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED FOR |
| | THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS BEING |
| | TWO. FANS SHALL BE SELECTED FOR STABLE PERFORMANCE |
| | BASED ON NORMAL TEMPERATURE AND, WHERE APPLICABLE, |
| | ELEVATED TEMPERATURE. CALCULATIONS AND MANUFACTURER'S |
| | FAN CURVES SHALL BE PART OF THE DOCUMENTATION |
| | PROCEDURES. FANS SHALL BE SUPPORTED AND RESTRAINED BY |
| | NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH THE |
| | STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT BE |
| | OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER (KILOWATTS) |
| | AS DETERMINED FROM MEASUREMENT OF ACTUAL CURRENT DRAW. |
| | MOTORS DRIVING FANS SHALL HAVE A MINIMUM SERVICE FACTOR |
| | OF 1.15. |
| | 513.11 POWER SYSTEMS. |
| | THE SMOKE CONTROL SYSTEM SHALL BE SUPPLIED WITH TWO |
| | SOURCES OF POWER. PRIMARY POWER SHALL BE THE NORMAL |
| | BUILDING POWER SYSTEMS. SECONDARY POWER SHALL BE FROM |
| | AN APPROVED STANDBY SOURCE COMPLYING WITH CHAPTER 27 OF |
| | THE FLORIDA BUILDING CODE, BUILDING. THE STANDBY POWER |
| | SOURCE AND ITS TRANSFER SWITCHES SHALL BE IN A ROOM |
| | SEPARATE FROM THE NORMAL POWER TRANSFORMERS AND SWITCH |
| | GEAR AND VENTILATED DIRECTLY TO AND FROM THE EXTERIOR. |
| | THE ROOM SHALL BE ENCLOSED WITH NOT LESS THAN 1-HOUR |
| | FIRE-RESISTANCE-RATED FIRE BARRIERS CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 707 OF THE FLORIDA BUILDING |
| | CODE, BUILDING OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711 OF THE FLORIDA BUILDING |
| | CODE, BUILDING, OR BOTH. POWER DISTRIBUTION FROM THE |
| | TWO SOURCES SHALL BE BY INDEPENDENT ROUTES. TRANSFER TO |
| | FULL STANDBY POWER SHALL BE AUTOMATIC AND WITHIN 60 |
| | SECONDS OF FAILURE OF THE PRIMARY POWER. THE SYSTEMS |
| | SHALL COMPLY WITH NFPA 70. |
| | 513.11.1 POWER SOURCES AND POWERSURGES. |
| | ELEMENTS OF THE SMOKE MANAGEMENT SYSTEM RELYING ON |
| | VOLATILE MEMORIES OR THE LIKE SHALL BE SUPPLIED WITH |
| | UNINTERRUPTIBLE POWER SOURCES OF SUFFICIENT DURATION TO |
| | SPAN 15-MINUTE PRIMARY POWER INTERRUPTION. ELEMENTS OF |
| | THE SMOKE MANAGEMENT SYSTEM SUSCEPTIBLE TO POWER SURGES |
| | SHALL BE SUITABLY PROTECTED BY CONDITIONERS, |
| | SUPPRESSORS OR OTHER APPROVED MEANS. |
| | 513.12 DETECTION AND CONTROL SYSTEMS. |
| | FIRE DETECTION SYSTEMS PROVIDING CONTROL INPUT OR |
| | OUTPUT SIGNALS TO MECHANICAL SMOKE CONTROL SYSTEMS OR |
| | ELEMENTS THEREOF SHALL COMPLY WITH NFPA 72 AND THE |
| | REQUIREMENTS OF CHAPTER 9 OF THE FLORIDA BUILDING CODE, |
| | BUILDING OR THE FLORIDA FIRE PREVENTION CODE. SUCH |
| | SYSTEMS SHALL BE EQUIPPED WITH A CONTROL UNIT COMPLYING |
| | WITH UL 864 AND LISTED AS SMOKE CONTROL EQUIPMENT. |
| | CONTROL SYSTEMS FOR MECHANICAL SMOKE CONTROL SYSTEMS |
| | SHALL INCLUDE PROVISIONS FOR VERIFICATION. VERIFICATION |
| | SHALL INCLUDE POSITIVE CONFIRMATION OF ACTUATION, |
| | TESTING, MANUAL OVERRIDE, THE PRESENCE OF POWER |
| | DOWNSTREAM OF ALL DISCONNECTS AND, THROUGH A |
| | PREPROGRAMMED WEEKLY TEST SEQUENCE REPORT, ABNORMAL |
| | CONDITIONS AUDIBLY, VISUALLY AND BY PRINTED REPORT. |
| | [513.12.1 WIRING. |
| | IN ADDITION TO MEETING THE REQUIREMENTS OF NFPA 70, ALL |
| | WIRING, REGARDLESS OF VOLTAGE, SHALL BE FULLY ENCLOSED |
| | WITHIN CONTINUOUS RACEWAYS. |
| | 513.12.2 ACTIVATION. |
| | SMOKE CONTROL SYSTEMS SHALL BE ACTIVATED IN ACCORDANCE |
| | WITH THE FLORIDA BUILDING CODE, BUILDING OR THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | 513.12.3 AUTOMATIC CONTROL. |
| | WHERE COMPLETELY AUTOMATIC CONTROL IS REQUIRED OR USED, |
| | THE AUTOMATIC CONTROL SEQUENCES SHALL BE INITIATED FROM |
| | AN APPROPRIATELY ZONED AUTOMATIC SPRINKLER SYSTEM |
| | COMPLYING WITH THE FLORIDA FIRE PREVENTION CODE, FROM |
| | MANUAL CONTROLS THAT ARE READILY ACCESSIBLE TO THE FIRE |
| | DEPARTMENT, AND ANY SMOKE DETECTORS REQUIRED BY |
| | ENGINEERING ANALYSIS. |
| | [513.13 CONTROL-AIR TUBING. |
| | CONTROL-AIR TUBING SHALL BE OF SUFFICIENT SIZE TO MEET |
| | THE REQUIRED RESPONSE TIMES. TUBING SHALL BE FLUSHED |
| | CLEAN AND DRY PRIOR TO FINAL CONNECTIONS. TUBING SHALL |
| | BE ADEQUATELY SUPPORTED AND PROTECTED FROM DAMAGE. |
| | TUBING PASSING THROUGH CONCRETE OR MASONRY SHALL BE |
| | SLEEVED AND PROTECTED FROM ABRASION AND ELECTROLYTIC |
| | ACTION. |
| | 513.13.1 MATERIALS. |
| | CONTROL-AIR TUBING SHALL BE HARD-DRAWN COPPER, TYPE L, |
| | ACR IN ACCORDANCE WITH ASTM B 42, ASTM B 43, ASTM B 68, |
| | ASTM B 88, ASTM B 251 AND ASTM B 280. FITTINGS SHALL BE |
| | WROUGHT COPPER OR BRASS, SOLDER TYPE IN ACCORDANCE WITH |
| | ASME B 16.18 OR ASME B 16.22. CHANGES IN DIRECTION |
| | SHALL BE MADE WITH APPROPRIATE TOOL BENDS. BRASS |
| | COMPRESSION-TYPE FITTINGS SHALL BE USED AT FINAL |
| | CONNECTION TO DEVICES; OTHER JOINTS SHALL BE BRAZED |
| | USING A BCUP5 BRAZING ALLOY WITH SOLIDUS ABOVE 1,100?F |
| | (593?C) AND LIQUIDS BELOW 1,500?F (816?C). BRAZING FLUX |
| | SHALL BE USED ON COPPER-TO-BRASS JOINTS ONLY. |
| | EXCEPTION: NONMETALLIC TUBING USED WITHIN CONTROL |
| | PANELS AND AT THE FINAL CONNECTION TO DEVICES PROVIDED |
| | ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | 1. TUBING SHALL COMPLY WITH THE REQUIREMENTS OF SECTION |
| | 602.2.1.3. |
| | 2. TUBING AND CONNECTED DEVICE SHALL BE COMPLETELY |
| | ENCLOSED WITHIN A GALVANIZED OR PAINT-GRADE STEEL |
| | ENCLOSURE HAVING A MINIMUM THICKNESS OF 0.0296 INCH |
| | (0.7534 MM) (NO. 22 GAGE). ENTRY TO THE ENCLOSURE SHALL |
| | BE BY COPPER TUBING WITH A PROTECTIVE GROMMET OF |
| | NEOPRENE OR TEFLON OR BY SUITABLE BRASS COMPRESSION TO |
| | MALE BARBED ADAPTER. |
| | 3. TUBING SHALL BE IDENTIFIED BY APPROPRIATELY |
| | DOCUMENTED CODING. |
| | 4. TUBING SHALL BE NEATLY TIED AND SUPPORTED WITHIN THE |
| | ENCLOSURE. TUBING BRIDGING CABINETS AND DOORS OR |
| | MOVEABLE DEVICES SHALL BE OF SUFFICIENT LENGTH TO AVOID |
| | TENSION AND EXCESSIVE STRESS. TUBING SHALL BE PROTECTED |
| | AGAINST ABRASION. TUBING SERVING DEVICES ON DOORS SHALL |
| | BE FASTENED ALONG HINGES. |
| | 513.13.2 ISOLATION FROM OTHER FUNCTIONS. |
| | CONTROL TUBING SERVING OTHER THAN SMOKE CONTROL |
| | FUNCTIONS SHALL BE ISOLATED BY AUTOMATIC ISOLATION |
| | VALVES OR SHALL BE AN INDEPENDENT SYSTEM. |
| | 513.13.3 TESTING. |
| | TEST CONTROL-AIR TUBING AT THREE TIMES THE OPERATING |
| | PRESSURE FOR NOT LESS THAN 30 MINUTES WITHOUT ANY |
| | NOTICEABLE LOSS IN GAUGE PRESSURE PRIOR TO FINAL |
| | CONNECTION TO DEVICES. |
| | 513.14 MARKING AND IDENTIFICATION. |
| | THE DETECTION AND CONTROL SYSTEMS SHALL BE CLEARLY |
| | MARKED AT ALL JUNCTIONS, ACCESSES AND TERMINATIONS. |
| | 513.15 CONTROL DIAGRAMS. |
| | IDENTICAL CONTROL DIAGRAMS SHALL BE PROVIDED AND |
| | MAINTAINED AS REQUIRED BY THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | 513.16 FIRE FIGHTER'S SMOKE CONTROL PANEL. |
| | A FIRE FIGHTER'S SMOKE CONTROL PANEL FOR FIRE |
| | DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE |
| | PROVIDED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | 513.17 SYSTEM RESPONSE TIME. |
| | SMOKE CONTROL SYSTEM ACTIVATION SHALL COMPLY WITH THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | 513.18 ACCEPTANCE TESTING. |
| | DEVICES, EQUIPMENT, COMPONENTS AND SEQUENCES SHALL BE |
| | TESTED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | 513.19 SYSTEM ACCEPTANCE. |
| | ACCEPTANCE OF THE SMOKE CONTROL SYSTEM SHALL BE IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 5) CONTINUED. IN REFERENCE TO SECTION 513.10.5 LISTED |
| | ABOVE, INDICATE THE MAKES OF THE PRESSURIZATION AND |
| | SMOKE EXHAUST FANS, AND VERIFY THAT THEY ARE UL LISTED |
| | AS POWER VENTILATORS FOR SMOKE CONTROL SYSTEMS. |
| | |
| | 6) ACKNOWLEDGED: SMOKE CONTROL FANS, DUCTS, MOTORIZED |
| | DAMPERS, FIRE/SMOKE DAMPERS ARE TO BE DEFERRED |
| | SUBMITTALS. |
| | |
| | 7, 8, 9) ACKNOWLEDGED THAT THE GENERATOR IS LOCATED |
| | OUTSIDE OF THE BUILDING. PLEASE PROVIDE AN ENLARGED |
| | DRAWING SHOWING THE EXHAUST PIPING RUN AND DISCHARGE |
| | LOCATION, REQUIRED EXHAUST OUTLET CLEARANCES TO |
| | BUILDING OPENINGS, AND WIND LOAD ENGINEERING FOR TIE |
| | DOWN OF THE UIOT AND ALL ASSOCIATED EXTERIOR |
| | COMPONENTS. SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | APPROVED BY THE EOR. |
| | |
| | ADVISORY: IT IS IMPORTANT TO NOT THAT SOUND MAY BE AN |
| | ISSUE WITH THE GENERATOR LOCATED IN CLOSE PROXIMITY OF |
| | THE GARAGE. PLEASE PROVIDE THE DBA OF THE GENERATOR |
| | |
| | 12) ACKNOWLEDGED. DUCT SMOKE DETECTOR NOTE ADDED TO AC |
| | EQUIPMENT SCHEDULE. PLEASE PROVIDE SYMBOLS ON THE |
| | MECHANICAL LAYOUT PLANS TO SHOW THE LOCATIONS. |
| | |
| | 16) ACKNOWLEDGED THAT THE FABRIC DUCT WILL BE A |
| | DEFERRED SUBMITTAL, AND THE PRODUCT SHALL MEET THE |
| | REQUIREMENTS OF UL 181. |
| | |
| | 17) AS PREVIOUSLY REQUESTED PLEASE SHOW THE LOCATIONS |
| | OF ACCESS PANELS FOR ABOVE CEILING AC UNITS. |
| | |
| | 19) 2ND REQUEST FOR DUCT SIZES OR DUCT SCHEDULE TO BE |
| | PLACED ON SHEET M-101. |
| | |
| | 20) PLEASE REMOVE THE 6070 CFMS OF EA FOR OAU-3 SHOWN |
| | IN THE SCHEDULE ON M-600. |
| | |
| | 21) THE MAKEUP AIR FOR THE KITCHEN EXHAUST HOOD IS INTO |
| | COMBUSTION AIR FOR THE APPLIANCES. MAKEUP AIR IS |
| | INTRODUCED DIRECTLY INTO THE HOOD CANOPY FOR THE |
| | EXHAUST SYSTEM. PLEASE PROVIDE ANOTHER MEANS OF |
| | PROVIDING COMBUSTION AIR EITHER FROM THE SPACE OR |
| | PROVIDED MECHANICALLY- SECTION 304 FBC-14 FUEL GAS. |
| | |
| | 22) THE REQUESTED AIR BALANCE CALCULATION WAS NOT |
| | PROVIDED. |
| | |
| | 23, 29, 39) 2ND REQUEST FOR LOCATIONS OF REFRIGERANT |
| | CHASES FOR THE VRF SYSTEMS. PLEASE NOTE THAT CONTRACTOR |
| | SHOP DRAWINGS SHALL BE APPROVED BY THE EOR AND |
| | SUBMITTED PRIOR TO 1ST INSPECTION. |
| | |
| | 24) 2ND REQUEST FOR CLEARANCE DISTANCE MEASUREMENTS FOR |
| | THE EXHAUST FANS TO THE BUILDING WALLS- SECTION |
| | 506.3.13. |
| | |
| | 25) COMMENT NOT COMPLETELY ADDRESS. O/A FOR ELEVATOR |
| | LOBBY NOT PROVIDED. |
| | |
| | 31) THE REVISED LIFE SAFETY SHEETS LS101 & LS102 HAVE |
| | NOT BEEN CORRECTED TO SHOW THE REQUIRED FIRE RATED |
| | SEPARATION BETWEEN THE SMOKE PURGE DUCT AND THE |
| | STAIRWELL ENCLOSURE- SECTION 1022.5 FBC-14 BUILDING. |
| | |
| | 32) ACKNOWLEDGED THAT THE EA IS SUB-DUCTED INTO THE |
| | FIRE-RATED SHAFTS BUT FIRE DAMPERS STILL MISSING AT THE |
| | O/A DUCT PENETRATIONS INTO THE SHAFTS. |
| | |
| | 33) PROVIDE THE SEQUENCE OF OPERATION FOR POOL |
| | EQUIPMENT EF-8, AND PROVIDE MAKEUP AIR FOR THE STORAGE |
| | ROOM EXHAUST SYSTEMS. |
| | |
| | 35) ACKNOWLEDGED THAT THE POOL HEATER WILL BE A |
| | DEFERRED SUBMITTAL. |
| | |
| | 36) THE REVISED LIFE SAFETY SHEETS LS101 & LS102 HAVE |
| | NOT BEEN CORRECTED TO SHOW THE REQUIRED FIRE RATED |
| | SEPARATION BETWEEN THE SMOKE PURGE DUCT AND THE |
| | STAIRWELL ENCLOSURE- SECTION 1022.5 FBC-14 BUILDING. |
| | |
| | 38) 2ND REQUEST FOR DUCT SIZES OR DUCT SCHEDULE TO BE |
| | PLACED ON SHEET M-105. |
| | |
| | 40) ACKNOWLEDGED. DUCT SMOKE DETECTOR NOTE ADDED TO AC |
| | EQUIPMENT SCHEDULE. PLEASE PROVIDE SYMBOLS ON THE |
| | MECHANICAL LAYOUT PLANS TO SHOW THE LOCATIONS. |
| | |
| | 42) AS PREVIOUSLY REQUESTED PLEASE SHOW THE LOCATIONS |
| | OF ACCESS PANELS FOR ABOVE CEILING AC UNITS. |
| | |
| | 43) REQUESTED AIR BALANCE CALCULATION NOT PROVIDED. |
| | |
| | 44) ACKNOWLEDGED THAT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE OAU SYSTEMS WILL BE DEFERRED SUBMITTAL. |
| | |
| | 45) ACKNOWLEDGED THAT WIND LOAD ENGINEERING FOR ALL |
| | EXTERIOR MOUNTED MECHANICAL EQUIPMENT AND APPLIANCES |
| | WILL BE DEFERRED SUBMITTALS. |
| | |
| | 46) ACKNOWLEDGED THAT REFRIGERANT PIPING RISER DRAWINGS |
| | WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 48) ACKNOWLEDGED THAT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GAS WATER HEATERS AND COMBUSTION AIR INTAKE DUCT |
| | AND EXHAUST VENTS WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 49) PLEASE PROVIDE ON THE PLAN, OR AS A SUBMITTAL |
| | DOCUMENT, A MASTER LIST OF ALL DEFERRED SUBMITTALS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |