| 2018-04-12 16:39:05 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P-903 #3 UNDER THE KEYED NOTES LIST THE LONGEST |
| | RUN AT 150' WHEN I ADDED UP THE LENGTHS ON THE RISER TO |
| | THE MAIN KIT IT WAS OVER 200' AND THE ARE SOME LENGTHS |
| | MISSING AT THE END OF THE RUN PLEASE CLARIFY. PER FBC |
| | FG 402.4.1 AND WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE 11/2" BRANCH FEEDING THE UPPER KITCHEN AND POOL |
| | EQUIPMENT AT 4142 CFH IS UNDERSIZED RESIZE AFTER |
| | LONGEST LENGTH IS CLARIFIED. PER FBC FG TABLE 402.4(5) |
| | |
| | 3. PLEASE LABEL THE GAS APPLIANCE BEING FED BY THE 11/4 |
| | BRANCH AT 2782 CFH. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. PLEASE LABEL THE FOUR GAS APPLIANCE BEINGWIT A CFH |
| | LOAD OF 1060 I THINK THEY ARE THE BOILERS . PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. THE 1" BRANCH AT .5 LBS TO POOL HEATER IS |
| | UNDERSIZED. FBC FG TABLE 402.4(1) |
| | |
| | 6. PLEASE LABEL THE DUCT WORK ON SHT P-401 DETAILS |
| | #1+3. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |