2018-04-12 16:39:051ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-903 #3 UNDER THE KEYED NOTES LIST THE LONGEST
 RUN AT 150' WHEN I ADDED UP THE LENGTHS ON THE RISER TO
 THE MAIN KIT IT WAS OVER 200' AND THE ARE SOME LENGTHS
 MISSING AT THE END OF THE RUN PLEASE CLARIFY. PER FBC
 FG 402.4.1 AND WPB AMEND TO FBC 107.2.1
  
 2. THE 11/2" BRANCH FEEDING THE UPPER KITCHEN AND POOL
 EQUIPMENT AT 4142 CFH IS UNDERSIZED RESIZE AFTER
 LONGEST LENGTH IS CLARIFIED. PER FBC FG TABLE 402.4(5)
  
 3. PLEASE LABEL THE GAS APPLIANCE BEING FED BY THE 11/4
 BRANCH AT 2782 CFH. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE LABEL THE FOUR GAS APPLIANCE BEINGWIT A CFH
 LOAD OF 1060 I THINK THEY ARE THE BOILERS . PER WPB
 AMEND TO FBC 107.2.1
  
 5. THE 1" BRANCH AT .5 LBS TO POOL HEATER IS
 UNDERSIZED. FBC FG TABLE 402.4(1)
  
 6. PLEASE LABEL THE DUCT WORK ON SHT P-401 DETAILS
 #1+3. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  