| 2018-04-12 14:10:51 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. PROVIDE SPECS OF FIRE PUMP CONTROLLER/ATS, FIRE |
| | PUMP MOTOR, AND JOCKEY PUMP. INCLUDE MOTOR SIZES AND |
| | AMPERAGE DRAW TO CONFIRM CONDUCTOR SIZING. NEC 110.3, |
| | 695.4, 695.6 (INSUFFICIENT INFORMATION PROVIDED. MOTOR |
| | HP, LOCKED ROTOR CURRENT, AND NORMAL CURRENT NEED TO BE |
| | SHOWN ON PLAN FOR SIZING OF CONDUCTORS. FIRE PROTECTION |
| | SHEET DOES NOT PROVIDE THIS INFORMATION.) |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. PROVIDE ACCURATE SIZE OF MAIN BONDING JUMPER. NEC |
| | 250.28(D) (THE MAIN BONDING JUMPER IS DEFINED AS "THE |
| | CONNECTION BETWEEN THE GROUNDED CIRCUIT CONDUCTOR AND |
| | THE EQUIPMENT GROUNDING CONDUCTOR AT THE SERVICE". THE |
| | PLAN SHOWS A 750 KCMIL CONDUCTOR IN THE LOCATION THAT |
| | THE GROUNDING ELECTRODE CONDUCTOR IS INSTALLED, WHICH |
| | IS LABELED WRONG AS THE MAIN BONDING JUMPER. PER NEC |
| | 250.66, THE GROUNDING ELECTRODE CONDUCTOR WOULD BE 3/0 |
| | CU OR 250 KCMIL AL. THE MAIN BONDING JUMPER FOR SERVICE |
| | # 1 WOULD HAVE TO EQUAL OR EXCEED 12.5% OF THE TOTAL |
| | CONDUCTOR AREA. NINE SETS OF 750 KCMIL WOULD THEREFORE |
| | REQUIRE A CONDUCTOR SIZED AT 843.75 KCMIL CU, WHICH THE |
| | NEXT SIZE AVAILABLE IS 900 KCMIL, OR THE EQUIVALENT |
| | PARALLEL CONDUCTORS. THE MAIN BONDING JUMPERS FOR |
| | ADDITIONAL SERVICES WOULD ALSO NEED TO BE CALCULATED |
| | PER NEC 250.28(D)(1). PROVIDE CORRECTION.) |
| | 14. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE. |
| | LOAD CALCULATION PROVIDED SHOWS DEMAND FACTORS APPLIED |
| | TWICE, ONCE FOR EACH PANEL, AND THEN AGAIN FOR NUMBER |
| | OF UNITS. DEMAND FACTORS CAN ONLY BE APPLIED ONCE FOR |
| | SERVICE. ADDITIONALLY, THE DEMAND FACTORS PERMITTED IN |
| | NEC 220.84 APPLY TO DWELLING UNITS, WHICH IS DEFINED AS |
| | A UNIT THAT HAS PERMANENT PROVISIONS FOR LIVING, |
| | SLEEPING, COOKING, AND SANITATION. MANY OF THE GUEST |
| | ROOMS DO NOT FIT THIS DEFINITION, THEREFORE, THE DEMAND |
| | FACTORS COULD NOT BE APPLIED. NO LOAD CALCULATION |
| | PROVIDED FOR SERVICE 2 OF 2, OR FOR GENERATOR. NEC 100, |
| | 220; FBC 107.2.1 (THERE ARE STILL LOADS MISSING IN SOME |
| | PANEL SCHEDULES, THEREFORE, HOW CAN THE LOAD |
| | CALCULATION PROVIDED BE ACCURATE? AS AN EXAMPLE, THERE |
| | IS NO LOAD INCLUDED FOR THE POOL PANEL. THIS IS NOT THE |
| | ONLY EXAMPLE. PROVIDE ACCURATE LOAD CALCULATION AS |
| | PREVIOUSLY REQUESTED.) |
| | 15. PROVIDE VOLTAGE DROP CALCULATIONS, SHOWING |
| | COMPLIANCE WITH FBC EC C405.7.3, PROVIDE BLOCK NOTE |
| | STATING COMPLIANCE WITH FBC EC C405.7.4 AT COMPLETION |
| | OF PROJECT. (THESE ARE 2 SEPARATE ITEMS. THE VOLTAGE |
| | DROP CALCULATIONS NEED TO BE SHOWN ON PLAN AS PART OF |
| | DESIGN PER C405.7.3. VOLTAGE DROP CALCULATION IS ALSO |
| | REQUIRED AT FIRE PUMP PER 695.7. THE BLOCK NOTE |
| | PROVIDED INCORRECTLY REQUIRES THE ELECTRICAL CONTRACTOR |
| | TO PROVIDE THIS INFORMATION. THE BLOCK NOTE SHOULD BE |
| | FOR SUBMITTAL DOCUMENTS REQUIRED PER C405.7.4. READ |
| | CODE SECTION AND PROVIDE ACCURATE BLOCK NOTE IN |
| | ADDITION TO THE VOLTAGE DROP CALCULATIONS THAT ARE |
| | REQUIRED TO BE ON PLAN.) |
| | 16. CORRECTED. |
| | 17. MANY PANEL SCHEDULES PROVIDED ARE MISSING |
| | INFORMATION INCLUDING LOAD INFORMATION, GFCI |
| | PROTECTION, AND WIRE SIZES. PROVIDE PANEL SCHEDULES FOR |
| | ALL PANELS WITH COMPLETE INFORMATION. NEC 215.2, 215.5, |
| | 408.4, 408.30; FBC 107.2.1 (NOT CORRECTED COMPLETELY) |
| | 18. CORRECTED. |
| | 19. CORRECTED. |
| | 20. CORRECTED. |
| | 21. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87 (NOTE |
| | PROVIDED STATES THAT DOCUMENTATION WILL BE PROVIDED. |
| | HOWEVER, THERE IS NO EXPLANATION ON PLAN HOW THE ARC |
| | REDUCTION WILL BE ACCOMPLISHED. DETAIL WHICH METHOD |
| | WILL BE USED.) |
| | 22. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 |
| | (RESPONSE LETTER STATES THIS WILL BE PROVIDED IN AN |
| | ADDENDUM, BUT THIS COULD NOT BE LOCATED ON PLAN. |
| | PROVIDE AS PREVIOUSLY REQUESTED.) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |