 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 IF YOU HAVE ANY QUESTIONS OR IF I CAN BE OF FURTHER
 ASSISTANCE FEEL FREE TO CONTACT ME.
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 MARRIOTT HOTEL 17110874
  
 2ND REVIEW
  
 DATE: APRIL 6, 2018
  
  
 1. ADDRESSED.
  
 2. PROVIDE A SQUARE FOOTAGE BREAKDOWN BY USE AND
 OCCUPANCY CLASSIFICATION ON PAGE A-000.
  
 THIS IS USED TO ESTIMATE THE PROJECT COST USING ICC
 BUILDING VALUATION DATA.
 FBC 107.3
  
 PLAN REVIEW RESPONSE:
  
 A) PLEASE NOTE SINCE THE OCCUPANT LOAD FOR THE ROOFTOP
 FLOOR IS OVER 1,000 OCCUPANTS. THERE ARE ONLY 3
 VERTICAL STAIRWAYS IN THE CURRENT CONFIGURATION.
 STAIRWAY # 2 WOULD NEED TO BE RE-CONFIGURED WITH A 2
 HOUR WALL SEPARATING THE TWO SETS OF STAIRS INTO TWO
 SEPARATE STAIR ENCLOSURES TO BE ABLE TO COMPLY WITH
 FBC-B 1021.2.4.
  
 B) SHEET 049-LS-102. IN THE EVENT ROOM 803 CAN BE MADE
 INTO 4 SMALLER ROOMS PLEASE BREAK DOWN THE SQUARE
 FOOTAGE OF EACH ROOM AND THE OCCUPANT LOAD IN EACH.
 WITH THE OCCUPANT LOAD BEING TAKEN @ 7 NET IT WOULD
 APPEAR THAT EACH OF THE FOLDING WALLS WILL NEED A 2ND
 MEANS OF EGRESS IN EACH ROOM. SEE FBC-B TABLE 1015.1.
  
 C) PLEASE NOTE ON THE ROOFTOP DECK THERE MAYBE 3
 VERTICAL EXIT STAIRS BUT STAIRS 1 & 2 ARE LOCATED WHERE
 YOU HAVE TO GO THROUGH SERVICE AREAS. STAIR # 1, JUST
 TO THE EAST OF THIS STAIR IT LOOKS LIKE THIS IS A
 SERVICE AREA FOR DRINKS, AND FOR STAIR # 2 THE SERVICE
 AREA # 800 IS JUST THAT SERVICE AND STORAGE AREAS.
  
 D) INCLUDE THE PREFUNCTION AREAS AND TERRACE AS 7 NET
 AS PART OF THE OCCUPANT LOAD CALCULATIONS.
 SEE TABLE 1004.1.2
  
 2014 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
  
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. 4. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 SHEET 049-LS-102 SHOWS WHAT APPEARS TO BE A SLIDING
 DOOR 802B A FOLDING GLASS PARTITION WALL. PLEASE
 PROVIDE HOW COMPLIANCE WITH 2014 FBC-B 1008.1.2 DOOR
 SWING. EGRESS DOORS SHALL BE OF THE PIVOTED OR
 SIDE-HINGED SWINGING TYPE.
  
 EXCEPTIONS: 9. IN OTHER THAN GROUP H OCCUPANCIES,
 MANUALLY OPERATED HORIZONTAL SLIDING DOORS ARE
 PERMITTED IN A MEANS OF EGRESS FROM SPACES WITH AN
 OCCUPANT LOAD OF 10 OR LESS.
  
 D) SEE ALSO SLIDING GLASS DOOR 802B. THIS CANNOT BE
 USED TO ACCESS THE CORRIDOR LABELED SERVICE 610.
  
 E) SHEET 049-LS-102. THE KEY PLAN INDICATES AREAS OF
 THE FLOOR PLAN WHERE THERE WILL BE NON-SIMULTANEOUS
 OCCUPANT LOADS. THE PRE-FUNCTION AREA LOBBY AND SERVICE
 AREA 610. PLEASE NOTE FOR ASSEMBLY OCCUPANCIES THE ONLY
 AREAS NOT TO BE FIGURED ARE NET AREAS. 2014 FBC-B 201:
 FLOOR AREA, NET. THE ACTUAL OCCUPIED AREA NOT INCLUDING
 UNOCCUPIED ACCESSORY AREAS SUCH AS CORRIDORS,
 STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS AND CLOSETS.
 BUILDINGS ARE LOOKED AT IN THE WORST CASE SCENARIO.
 PROVIDE A CHART NAMING EACH ROOM, AND ROOM NUMBER, THE
 SQUARE FOOT PER OCCUPANT, AND OCCUPANT LOAD PER ROOM,
 PLUS THE TOTAL OCCUPANT LOAD FOR THIS FLOOR PER TABLE
 1004.1.2.
  
 F) IN ORDER TO MAINTAIN A CLEAR FLOW TO THE STAIRS WE
 CAME UP WITH A FEW OPTIONS.
  
 A. ADD A STAY OPEN DOOR TO PREVENT FLOW OF TRAVEL BACK
 INTO THE CORRIDOR NEAR THE WALK IN COOLER ADJACENT TO
 DOOR 807A.
  
 B. AREAS 610 AND 800 SHOULD BE LABELED AS CORRIDOR NOT
 SERVICE AREA.
  
 C. ADDING A DOOR FROM THE POOL DECK TO STAIRS #3 NEAR
 DOOR 814A AND MOVING DOOR 814A OVER TO ALLOW CLEARANCE
 FOR THE NEW DOOR.
  
 D. ADDING A SERIES OF EXIT SIGNS STARTING AT THE
 PREFUNCTION AREA 802 THROUGH LOBBY 801 DIRECTING THE
 FLOW TO THE #1 STAIRS. IF YOU WOULD LIKE TO DISCUSS
 THESE OPTIONS FEEL FREE TO CONTACT ME.
  
 3. OK. ADDRESSED.
  
 4. ELEVATION CERTIFICATE ADDRESSED, WILL ISSUE WITH
 PROVISIO
  
 5. OK. ADDRESSED. WITH FOUNDATION PERMIT.
  
 6. THRESHOLD AGREEMENTS WITH FOUNDATION PERMIT.
  
 7. OK. ADDRESSED.
  
 8. OK. ADDRESSED.
  
 9. OK. ADDRESSED.
  
 10. OK. ADDRESSED.
  
 11. OK. ADDRESSED.
  
 12. OK. ADDRESSED.
  
 13. OK. ADDRESSED.
  
 14. OK. ADDRESSED.
  
 15. AN IMPACT FEE STOP HAS BEEN ADDED SO THAT THIS
 COMMENT CAN BE REMOVED FROM THE STRUCTURAL REVIEW
 COMMENTS.
  
 16. OK. ADDRESSED.
  
 17. OK. ADDRESSED.
  
 18. OK. ADDRESSED.
  
 19. ACCESSIBILITY NOT ADDRESSED. PLEASE SHOW HOW
 COMPLIANCE WILL BE MET FOR THE FOLLOWING AREAS.
  
 226.2 DISPERSION. DINING SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES.
 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS AS WELL
 AS BARS.
  
 A. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR GUEST
 RECEPTION COUNTER.
  
 B. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR BAR AND
 ROOF TOP BARS.
  
 C. PROVIDE ACCESSIBLE SEATING IN DINING ROOM 1ST FLOOR
 CAF? ON TERRACE, RESTAURANT.
  
 D. PROVIDE ACCESSIBLE COUNTER AT ROOF TOP MAIN POOL BAR
 AND SATELLITE BAR.
  
 E. PROVIDE A FURNITURE PLAN FOR THE RESTAURANT AND BAR
 AREAS.
  
 INCLUDE ELEVATIONS OF THESE AREAS TO SHOW COMPLIANCE
 WITH THE FLORIDA ACCESSIBILITY CODE FOLLOWING SECTIONS.
  
 902.1 DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
  
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 902.4.1 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED, EXCEPT
 THAT KNEE CLEARANCE 24 INCHES (610 MM) MINIMUM ABOVE
 THE FINISH FLOOR OR GROUND SHALL BE PERMITTED.
  
 902.4.2 HEIGHT.
 THE TOPS OF TABLES AND COUNTERS SHALL BE 26 INCHES (660
 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 F. 19-2 PROVIDE THE FOLLOWING DETAILS FOR THE HOTEL
 DROP OFF ZONE.
 SHEET 047-AS-101 SHOWS A DROP OFF ZONE IN FRONT OF THE
 HOTEL. THE DETAIL INDICATES SEE SHEET AS102 CURB RAMP
 DETAILS. THE DETAIL SHEET DOES NOT PROVIDE DETAILS FOR
 THE:
 2014 FBC-ACCESSIBILITY CODE:
  
 503.2 VEHICLE PULL-UP SPACE.
 503.3 ACCESS AISLE.
 503.3.1 WIDTH.
 503.3.2 LENGTH.
 503.3.3 MARKING.
 503.4 FLOOR AND GROUND SURFACES.
 503.5 VERTICAL CLEARANCE.
  
 20. OK. ADDRESSED.
  
 21. OK. ADDRESSED.
  
 22. TO BE A PROVISO. PRODUCT APPROVALS AND SHOP
 DRAWINGS WILL BE DEFFERED SUBMITTALS.
  
 23. NOT ADDRESSED.
  
 CONFIRM THAT THE NANA WALL ASSEMBLY USED WILL EXCEED
 THE PRESSURES FOR THE AREAS THAT THEY ARE LOCATED.
 OFTEN THESE DOORS DO NOT MEET THE PRESSURE REQUIREMENTS
 FOR THIS TYPE OF BUILDING. FBC CHAPTER 16 FOR
 COMPONENTS AND CLADDING.
 24. PARTIALLY ADDRESSED. THANK YOU FOR PROVIDING THE
 WEST FACADE AREA CALCULATIONS.
  
 WE VARIFIED THAT THE CALCULATED OPENINGS ARE ACCURATE.
 WE WERE NOT ABLE TO LOCATE THE DISTANCE OF 16FT. 3 IN.
 FOR AREA B. PLEASE CONFIRM THIS DISTANCE. IT APPEARS TO
 BE APPROXIMATLEY 12FT. 7IN. THE CALCULATIONS WILL BE OK
 AT THIS DISTANCE.
  
 PROVIDE THE CALCULATIONS TO SHOW MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION ON THE WEST
 SIDE OF THE HOTEL AND THE PROPOSED BUILDING ALONG THAT
 WEST WALL.
  
 FBC 705.8.1 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
  
 25. OK. ADDRESSED.
  
 26. GENERATOR
  
 AS MENTIONED IN A RESPONSE FOR THE MECHANICAL REVIEW.
 PLEASE PROVIDE INFORMATION ON THE GENERATOR ENCLOSURE
 THAT WILL BE PROVIDED ALONG WITH THE FOLLOWING. ALSO
 SHOW HOW THIS ENCLOSURE WILL COMPLY WITH FBC 1609 BASIC
 WIND SPEED.
  
 A) DISCREPANCY IN PLANS, THE LS SHEET 048-LS-101 DOES
 NOT SHOW A GENERATOR WHEREAS SHEET 050-A101 DOES SHOW A
 GENERATOR. PLEASE NOTE THIS BUILDING DOES REQUIRE A
 GENERATOR BEING A HIGHRISE BUILDING.
  
 2014 FBC-B 403.4.8 STANDBY POWER.
 2014 FBC-B 403.4.8.1 SPECIAL REQUIREMENTS FOR STANDBY
 POWER.
  
 B) DISCREPANCY IN PLANS, THE LS SHEET 048-LS-101 DOES
 NOT SHOW A GENERATOR WHEREAS SHEET 050-A101 DOES SHOW A
 GENERATOR. IN NEITHER SHEET DOES THE PLANS SHOW THE
 GENERATOR FULLY ENCASED IN A 2 HOUR WALL. THE PROPERTY
 LINE WALL IS MISSING. PLEASE SEE FBC-B 403.8.1
 REQUIRING A 2 HOUR FIRE BARRIERS ENCLOSURE WITHIN A
 BUILDING. JUST THE OTHER SIDE OF THE PROPERTY LINE
 THERE IS A 3 HOUR WALL AT THE ASSUMED PROPERTY LINE.
  
 C) SHEETS LS SHEET 048-LS-101 ONLY INDICATE THIS ROOM
 IS TO BE A GENERATOR, PLEASE NOTE THAT NO INFORMATION
 IS GIVEN ON THE LIFE SAFETY SHEET IF THE GENERATOR HAS
 A DAY TANK AND OTHER STORAGE TANKS, NOR DOES EITHER OF
 THESE SHEETS NOTE INTAKE AND EXHAUST FOR THE GENERATOR,
 104-M-101 IS ALSO SILENT ON THIS MATTER. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 D) SHEET 104-M-101 SHOWS WHAT APPEARS TO BE AN EXTERIOR
 WALL ON THE PROPERTY LINE BUT A 18 X 18 INCH EXTERIOR
 LOUVER WHICH WOULD NEED TO BE EXTENDED OUT OF THE
 GENERATOR ROOM. 701.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. THERE SHOULD BE AN EXTERIOR WALL FOR THE
 GENERATOR, NOT SHOWN ON THE CURRENT SET OF PLANS.
  
 27. PENETRATIONS THROUGH 2 HOUR RATED STAIRWAYS
  
 A) PAGE 098-A-701 SHOWS WHAT APPEARS TO BE A 2 HOUR
 DROPPED CEILING.
  
 B) PAGE 048-LS101 AND 050-A101 BOTH SHOW STAIRWAY 3 AS
 A 2HR VERTICAL EXIT STAIRWAY. PENETRATIONS WERE FOUND
 ON PAGE 124-P-101.
  
 SEE FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 28. LAUNDRY ROOM AND LAUNDRY CHUTE
  
 COMMON STATEMENT FOR FLOORS 2-7. SHEET 049LS102 AND
 SHEET 055-A-103 BOTH SHOW THE LAUNDRY CHUTE ACCESS ROOM
 WITHIN THE HOUSE KEEPING ROOM. THE HOUSE KEEPING ROOM
 IS SHOWN AS 1 HOUR RATED BUT NOT THE LAUNDRY CHUTE
 ACCESS ROOM.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 713.13.3 REFUSE,
 RECYCLING AND LAUNDRY CHUTE ACCESS ROOMS.
  
 ACCESS OPENINGS FOR REFUSE, RECYCLING AND LAUNDRY
 CHUTES SHALL BE LOCATED IN ROOMS OR COMPARTMENTS
 ENCLOSED BY NOT LESS THAN 1-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS
 SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION
 OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3.
  
 COMMON STATEMENT FOR FLOORS 2-7. SHEET 049LS102 AND
 SHEET 055-A-103 BOTH SHOW THE LAUNDRY CHUTE ACCESS ROOM
 WITHIN THE HOUSE KEEPING ROOM. THE LAUNDRY CHUTE ACCESS
 ROOM DOES NOT SHOW UP ON THE DOOR SCHEDULE, AND NEEDS
 TO BE 1 HOUR FIRE RATED PER 2014 FBC-B 713.13.3.
  
 29. BOOSTER PUMP
  
 A) BOOSTER PUMP ROOM MAYBE WILL NEED FIRE RATED WALLS
 AND OPENING PROTECTIVES? WHAT IS THIS BOOSTER PUMP TO
 BE USED IN CONJUNCTION WITH? SHEET 124-P-101 THE
 PLUMBING 1ST FLOOR DOES NOT SHOW THE BOOSTER PUMP TYING
 INTO THE PRESSURE POTABLE WATER SYSTEM. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 B) ON PAGE LS 101 THERE IS NOT A DOOR SHOWN TO GET OUT
 OF THE BOOSTER ROOM / STORAGE AREA. PLEASE UPDATE.
  
 30. SWIMMING POOL AREA
  
 NOTE: SEVERAL OF THESE COMMENTS COULD BE A PROVISO OR
 ADDED TO THE SWIMMING POOL PERMIT.
  
 POOL DECK ONLY POOL UNDER A SEPARATE PERMIT.
  
 A) SHEET 049-LS-102, 058-A-104 BOTH SHOW A LINEAR POOL
 DECK DRAIN. NONE OF THE ARCHITECTURAL SHEETS SHOW THE
 ELEVATION OR CROSS SLOPES OF THE POOL DECK. THE
 STRUCTURAL SHEET 012-S-1.04 SHOWS (2) ELEVATIONS ONE AT
 T. O. SLAB AT EL= 83 FEET AND A 2ND ELEVATION AT
 ELEVATION T. O. SLAB 82 FEET. THE STRUCTURAL SHEET
 036-S-4.20 DETAIL # 4 SHOWS 2 HEIGHTS IN THE CONCRETE
 DECK. A FINISHED CONCRETE DECK AND A DROPPED STRUCTURAL
 DECK AROUND THE POOL DECK ASSUMED AT T. O. SLAB AT EL=
 82 FEET.
  
 B) SHEET 037-S-4.21 DETAIL 10 SHOWS THE SUPPORT LIFT BY
 THE EDGE OF THE POOL, BUT THIS SAME DETAIL SHOWS THE
 SIDE WALL OF THE POOL, SECONDARY POOL STRUCTURE BY POOL
 DESIGNER. THERE ARE ONLY THE 2 ELEVATIONS AROUND THE
 POOL. THE STRUCTURAL SHEET 036-S-4.20 DETAIL # 4 HAS A
 NOTE SEE ARCHITECTURAL SHEETS FOR SLOPE.
  
 C) 2014 FBC-B SECTION 454.1.3.1.2. POOL WET DECKS SHALL
 BE UNIFORMLY SLOPED AT A MINIMUM OF 2 PERCENT TO A
 MAXIMUM OF 4 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER. THE PLANS ONLY SHOW A
 LINEAR POOL DRAIN ON THE WEST SIDE OF THE POOL. PLEASE
 SHOW COMPLIANCE FOR THE OTHER 3 SIDES.
  
 D) THE ACCESSIBILITY CODE SECTION 403.3 CROSS SLOPES
 FOR WALKING SURFACES SHALL BE NOT STEEPER THAN 1:48.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED FOR BOTH
 SECTIONS OF THE CODE.
  
 E) SHEET 036-S-4.20 DETAIL # 1 AND 037-S-4.21 DETAIL #
 10 SHOWS THE POOL STRUCTURAL WALL LEVEL WITH THE
 STRUCTURAL DECK HOW WILL WATER FROM THE POOL DECK BE
 SLOPED BACK TO THE LINEAR DECK DRAIN. WATER ON THE POOL
 DECK SHALL BE SLOPED AWAY FROM THE POOL EDGE. 2014
 FBC-B SECTION 454.1.3.1.2.
  
 F) SHEET 036-S-4.20 DETAIL 4 INDICATES THE USE OF WOOD
 DECK BY OTHERS, PLEASE PROVIDE EXACTLY WHERE THIS WOOD
 DECKING IS TO BE INSTALLED, SEE SECTION 454.1.3.1.1 OF
 THE 2014 FBC-B. POOL WET DECKS SHALL BE CONSTRUCTED OF
 CONCRETE OR OTHER NONABSORBENT MATERIAL HAVING A SMOOTH
 SLIP-RESISTANT FINISH. WET DECK AREA FINISHES SHALL BE
 DESIGNED FOR SUCH USE AND SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.
 WOODEN DECKS AND WALKWAYS ARE PROHIBITED.
  
 G) SHEET 037-S-4.21 DETAIL # 10 SHOWS A STRUCTURAL BASE
 FOR AN ADA CHAIR LIFT. THE ARCHITECTURAL SHEET
 058-A-104 SHOWS THE POSITION OF THE CHAIR LIFT AND THE
 CLEAR 48X30 INCHES PLEASE PROVIDE THE MANUFACTURES SPEC
 ON THE LIFT THE DISTANCE FROM EDGE OF THE WATER TO THE
 CENTERLINE OF THE SEAT IS 4.75 FEET. WILL THE LIFT BE
 ABLE TO LIFT A PERSON INTO THE WATER WITH A SPAN OF 6
 FEET OR MORE? 2014 FBC-ACCESSIBILITY CODE 1009.2. THE
 LOCATION OF THE STRUCTURAL STAND APPEARS CLOSER THAN
 THE ARCHITECTURAL SHEET?
  
 31. WALL IDENTIFICATION
  
 SHEET 048-LS101 AND 050-A101 THIS STATEMENT IS COMMON
 FOR ALL FLOOR PLANS. I COULD NOT FIND ANY WALL
 IDENTIFICATION TAGS IDENTIFYING WALL TYPES LISTED ON
 SHEET 093-A6.11. SHEET 093-A6-11 ALSO DOES NOT IDENTIFY
 WALL TYPES WITH WALL IDENTIFICATION TAGS.
 707.3.4 EXIT PASSAGEWAY.
 707.3.1 SHAFT ENCLOSURES.
 707.3.5 HORIZONTAL EXIT
 707.3.7 INCIDENTAL USES.
 420.2 SEPARATION WALLS.
  
 NOTE THIS LIST IS ONLY AN EXAMPLE OF MISSING WALL
 IDENTIFICATION TAGS. SHEET 092-A-601 DOES SHOW WALL
 TYPES BUT THE REFERENCE IS NOT FOUND ON THE
 ARCHITECTURAL FLOOR PLANS, A-101, A-102, A-103, &
 A-104.
  
 32. DOOR AND WALL RATINGS
  
 A) THE LIFE SAFETY PLAN SHOWS 2 HOUR FIRE RATED WALLS
 IN THE LIFE SAFETY ROOM 107 AND MAIN ELECTRICAL ROOM
 BUT THE DOORS 107A AND 108A ONLY SHOW 45 MINUTES. SEE
 FBC-B TABLE 716.5. 2 HOUR WALLS REQUIRE 1 ? HR. OPENING
 PROTECTIVES.
 B) DOOR INTO GENERATOR ROOM 137B. SEE FBC-B TABLE
 716.5. 2 HOUR WALLS REQUIRE 1 ? HR. OPENING
 PROTECTIVES.
 C) DOOR 128A VESTIBULE IN A ONE DOOR FIRE RATED WALL,
 TABLE 716.5 FOR A ONE HOUR FIRE BARRIER A ONE HOUR FIRE
 RATED DOOR.
 D) DOOR 128A VESTIBULE IN A ONE DOOR FIRE RATED WALL,
 TABLE 716.5 FOR A ONE HOUR FIRE BARRIER A ONE HOUR FIRE
 RATED DOOR.
 E) DOOR 124A FUTURE LAUNDRY IN A ONE HOUR RATED WALL
 REQUIRES 1 HR. FIRE RATING PER TABLE 716.5.
 F) PAGES 049 LS102, 055 A-103 AND M-102 AT STAIRWELL #3
 SHOULD SHOW A 2 HOUR RATING BETWEEN THE SMOKE PURGE
 MAKE- UP AIR AND THE STAIRWELL AND THE STAIRWELL
 PRESSURIZATION RISER.
 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK
 NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
 G) DOOR 124A FUTURE LAUNDRY IN A ONE HOUR RATED WALL
 REQUIRES 1 HR. FIRE RATING PER TABLE 716.5.
 H) DOOR 118A LOOKS LIKE AN EXIT DOOR FROM THE
 STAIRWELL, THERE NEEDS TO BE SIGNAGE ON THIS DOOR NOT
 AN EXIT TO THE EXTERIOR. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. SIGNAGE REQUIRED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  
 PROVISOS:
  
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 C) PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  