Plan Review Notes
Plan Review Notes For Permit 17110874
Permit Number 17110874
Review Stop Z
Sequence Number 1
Notes
Date Text
2018-02-09 15:29:321. ENTRANCE CANOPY GOES OVER THE PROPERTY LINE. AN
 AGREEMENT WILL BE NECESSARY.
 2. CANOPY COLUMNS ARE CREATING A NARROW PATH FOR
 PEDESTRIAN IN FRONT OF HOTEL ENTRANCE, 3.5' ONLY OF
 CLEAR SPACE. CAN THE COLUMNS BE REMOVED?
 3. A NEW TRANSFORMER ROOM IS INDICATED ALONG THE BANYAN
 BOULEAVARD FRONTAGE. PLEASE SUBMIT A REVISED
 CALCULATION OF ACTIVE USES ALONG BANYAN TO CONFIRM
 COMPLIANCE WITH REQUIRED 80%. THE CALCULATION SHALL
 INCLUDE THE RESIDENTIAL BUILDING. WHAT IS THE ENCLOSUDE
 OF THAT TRANSFORMER ROOM?
 4. PLEASE INDICATE THE LOCATION OF THE PROPERTY LINE
 AND SETBACK LINE ON ALL FLOOR PLANS AND ELEVATIONS TO
 DETERMINE ANY ENCROACHMENTS.
 5. PLEASE PROVIDE A COMPLETE GROSS SQUARE FOOTAGE TABLE
 INCLUDING ALL THE BUILDINGS IN THE PROJECT.
 6.PLEASE SUBMIT LANDSCAPE AND HARDSCAPE DRAWINGS,
 INCLUDING PHOTOMETRICS FOR STREETSCAPE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.