| 2018-01-31 09:44:49 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. COULD YOU CLARIFY THE DIFFERENCE BETWEEN A MOBILITY |
| | ROLL IN TYPE SHOWER AND A MOBILITY NON ROLL IN WHAT |
| | TYPE OF SHOWER OR TUB WILL IT HAVE? PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 2. SHT. A-102 RM 216 APPEARS TO BE AN ACCESSIBLE |
| | BATHROOM IT?S NOT LABELED AS ACCESSIBLE ALSO THE MATRIX |
| | ON SHT. A002 DOES NOT LIST 216 AS AN ACCESSIBLE PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. A-102 RM 243 IS LABELED AS M, R IT HAS A TUB IN |
| | IT ACCESSIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. SHT. A-103 SHOWS 2 ACCESSIBLE UNITS 316 AND 336 THE |
| | MATRIX ON SHT. A002 RMS. 336 AND 736 ARE NOT LISTED AS |
| | ACCESSIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2 |
| | AND 606.3 PLEASE SHOW ON PLAN. |
| | |
| | 6. SHT. A230 EMPLOYEE BATHROOM S 2.3 AND 2.4 PLEASE |
| | SHOW DIMENSIONS ON THE REQUIRED CLEAR FLOOR FOR THE |
| | TOILET AND LAVATORY AND THE TOILET COMPARTMENT DOORS |
| | SHALL NOT SWING INTO THE MINIMUM REQUIRED COMPARTMENT |
| | AREA. PER FBC ACC 606.2 AND 604.8.1.2 |
| | |
| | 7. SHT. A230 IN THE MEN?S AND WOMEN?S BATHROOMS 809 |
| | +810 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE FOR THE |
| | TOILETS AND LAVATORY?S , THE CLEAR FLOOR SPACE FOR THE |
| | TOILET SHALL START AT THE REAR WALL AND SIDE WALL OF |
| | THE TOILET. ALSO IN THE MEN?S THE URINAL SHALL NOT BE |
| | LOCATED WITHIN THE CLEAR FLOOR SPACE OF THE TOILET. PER |
| | FBC PL 604.3.1 AND 604.3.2 AND 606.2 |
| | |
| | 8. SHT. A230 DETAIL #4 SHOW DIMENSIONS ON THE CLEAR |
| | FLOOR SPACE FOR THE TOILETS AND LAVATORY?S THE DOOR |
| | SHALL NOT SWING INTO THE REQUIRED CLEAR FLOOR SPACE, |
| | THE TOILET IN 817 IS SHOWN AT 19? THE CENTERLINE OF ALL |
| | ACCESSIBLE TOILETS SHALL BE 16? MIN 18? MAX OFF THE |
| | SIDE WALL. PER FBC ACC 604.3.1, 606.2, 604.8.1.2 AND |
| | 604.2 |
| | |
| | 9. SHT. 230 DETAIL #1 SHOW DIMENSIONS ON THE CLEAR |
| | FLOOR SPACE FOR THE TOILETS AND LAVATORY?S, SHOW |
| | LOCATION OF THE LAVATORY LOCATED OUTSIDE OF THE |
| | ACCESSIBLE STALL. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 10. SHT. A230 DETAIL #2 SHOW DIMENSIONS ON THE CLEAR |
| | FLOOR SPACE FOR THE TOILETS AND LAVATORY?S , THE CLEAR |
| | FLOOR SPACE FOR THE TOILET SHALL START AT THE REAR WALL |
| | AND SIDE WALL OF THE TOILET. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 11. SHT. 230 DETAIL #3 SHOW DIMENSIONS ON THE CLEAR |
| | FLOOR SPACE FOR THE TOILETS AND LAVATORY?S, ? THE |
| | CENTERLINE OF ALL ACCESSIBLE TOILETS SHALL BE 16? MIN |
| | 18? MAX OFF THE SIDE WALL. PER FBC ACC 604.3.1, 606.2, |
| | AND 604.2 |
| | |
| | 12. SHT. 231 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE |
| | FOR THE TOILETS AND LAVATORY?S , THE CLEAR FLOOR SPACE |
| | FOR THE TOILET SHALL START AT THE REAR WALL AND SIDE |
| | WALL OF THE TOILET, THE CENTERLINE OF ALL ACCESSIBLE |
| | TOILETS SHALL BE 16? MIN 18? MAX OFF THE SIDE WALL AND |
| | SHOW THE GRAB BARS IN THE AMBULATORY STALL. PER FBC ACC |
| | 604.3.1, 606.2, AND 604.2 |
| | |
| | 13. SHT. A250 DETAIL #3 FOR K6 DOES NOT MATCH THE |
| | LAYOUT OF ROOM 216 ON THE FLOOR PLAN SHT A102 PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 14. SHT. A243 DETAIL #7 IF THE BATHROOM IS ACCESSIBLE |
| | PLEASE SHOW CLEAR FLOOR SPACE FOR FIXTURES AND GRAB |
| | BARS. PER FBC ACC 604.3.1, 606.2, AND 604.2 |
| | |
| | 15. PLEASE PROVIDE DETAILS FOR THE MOUNTING HEIGHTS OF |
| | THE ACCESSIBLE FIXTURES, GRAB BARS, MIRRORS, TOILET |
| | PAPER DISPENSERS. PER FBC ACC CHAPTER 6 |
| | |
| | 16. PLEASE PROVIDE A SHOWER PAN DETAIL SHALL COMPLY |
| | WITH FBC PL 417 |
| | |
| | 17. PLEASE EXPAND THE ISOMETRICS FOR THE GANG BATH ON |
| | 8TH FLOOR, POOL BATHE AND COMMON BATHROOMS ON GROUND |
| | FLOOR THEY ARE EXTREMELY HARD TO READ AS THEY ARE AND |
| | WHEN SAVED FOR OUR RECORD WILL NOT TRANSFER WELL. PER |
| | WPB AMEND TO FBC 107.2.1.4 |
| | |
| | 18. PLEASE PROVIDE A SANITARY COLLECTION ISOMETRIC |
| | SHOWING ALL THE RISERS LABELED TO MATCH THE FLOOR |
| | PLANS. WPB AMEND TO FBC 107.2.1 |
| | |
| | 19. PLEASE PROVIDE A COMPLETE WATER ISOMETRIC SHOWING |
| | THE MAIN, RISERS LABELED TO MATCH FLOOR PLAN. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 20. PLEASE SHOW THE RISER NUMBERS FOR THE SANITARY, |
| | WATER AND STORM ON FLOOR PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 21. PLEASE PROVIDE A STORM ISOMETRIC WITH THE SQFT AND |
| | SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |