Plan Review Notes
Plan Review Notes For Permit 17110874
Permit Number 17110874
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-31 09:44:491ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. COULD YOU CLARIFY THE DIFFERENCE BETWEEN A MOBILITY
 ROLL IN TYPE SHOWER AND A MOBILITY NON ROLL IN WHAT
 TYPE OF SHOWER OR TUB WILL IT HAVE? PER WPB AMEND TO
 FBC 107.2.1
  
 2. SHT. A-102 RM 216 APPEARS TO BE AN ACCESSIBLE
 BATHROOM IT?S NOT LABELED AS ACCESSIBLE ALSO THE MATRIX
 ON SHT. A002 DOES NOT LIST 216 AS AN ACCESSIBLE PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. A-102 RM 243 IS LABELED AS M, R IT HAS A TUB IN
 IT ACCESSIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. A-103 SHOWS 2 ACCESSIBLE UNITS 316 AND 336 THE
 MATRIX ON SHT. A002 RMS. 336 AND 736 ARE NOT LISTED AS
 ACCESSIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2
 AND 606.3 PLEASE SHOW ON PLAN.
  
 6. SHT. A230 EMPLOYEE BATHROOM S 2.3 AND 2.4 PLEASE
 SHOW DIMENSIONS ON THE REQUIRED CLEAR FLOOR FOR THE
 TOILET AND LAVATORY AND THE TOILET COMPARTMENT DOORS
 SHALL NOT SWING INTO THE MINIMUM REQUIRED COMPARTMENT
 AREA. PER FBC ACC 606.2 AND 604.8.1.2
  
 7. SHT. A230 IN THE MEN?S AND WOMEN?S BATHROOMS 809
 +810 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE FOR THE
 TOILETS AND LAVATORY?S , THE CLEAR FLOOR SPACE FOR THE
 TOILET SHALL START AT THE REAR WALL AND SIDE WALL OF
 THE TOILET. ALSO IN THE MEN?S THE URINAL SHALL NOT BE
 LOCATED WITHIN THE CLEAR FLOOR SPACE OF THE TOILET. PER
 FBC PL 604.3.1 AND 604.3.2 AND 606.2
  
 8. SHT. A230 DETAIL #4 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S THE DOOR
 SHALL NOT SWING INTO THE REQUIRED CLEAR FLOOR SPACE,
 THE TOILET IN 817 IS SHOWN AT 19? THE CENTERLINE OF ALL
 ACCESSIBLE TOILETS SHALL BE 16? MIN 18? MAX OFF THE
 SIDE WALL. PER FBC ACC 604.3.1, 606.2, 604.8.1.2 AND
 604.2
  
 9. SHT. 230 DETAIL #1 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S, SHOW
 LOCATION OF THE LAVATORY LOCATED OUTSIDE OF THE
 ACCESSIBLE STALL. PER FBC ACC 604.3.1, 606.2
  
 10. SHT. A230 DETAIL #2 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S , THE CLEAR
 FLOOR SPACE FOR THE TOILET SHALL START AT THE REAR WALL
 AND SIDE WALL OF THE TOILET. PER FBC ACC 604.3.1, 606.2
  
 11. SHT. 230 DETAIL #3 SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILETS AND LAVATORY?S, ? THE
 CENTERLINE OF ALL ACCESSIBLE TOILETS SHALL BE 16? MIN
 18? MAX OFF THE SIDE WALL. PER FBC ACC 604.3.1, 606.2,
 AND 604.2
  
 12. SHT. 231 SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE
 FOR THE TOILETS AND LAVATORY?S , THE CLEAR FLOOR SPACE
 FOR THE TOILET SHALL START AT THE REAR WALL AND SIDE
 WALL OF THE TOILET, THE CENTERLINE OF ALL ACCESSIBLE
 TOILETS SHALL BE 16? MIN 18? MAX OFF THE SIDE WALL AND
 SHOW THE GRAB BARS IN THE AMBULATORY STALL. PER FBC ACC
 604.3.1, 606.2, AND 604.2
  
 13. SHT. A250 DETAIL #3 FOR K6 DOES NOT MATCH THE
 LAYOUT OF ROOM 216 ON THE FLOOR PLAN SHT A102 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 14. SHT. A243 DETAIL #7 IF THE BATHROOM IS ACCESSIBLE
 PLEASE SHOW CLEAR FLOOR SPACE FOR FIXTURES AND GRAB
 BARS. PER FBC ACC 604.3.1, 606.2, AND 604.2
  
 15. PLEASE PROVIDE DETAILS FOR THE MOUNTING HEIGHTS OF
 THE ACCESSIBLE FIXTURES, GRAB BARS, MIRRORS, TOILET
 PAPER DISPENSERS. PER FBC ACC CHAPTER 6
  
 16. PLEASE PROVIDE A SHOWER PAN DETAIL SHALL COMPLY
 WITH FBC PL 417
  
 17. PLEASE EXPAND THE ISOMETRICS FOR THE GANG BATH ON
 8TH FLOOR, POOL BATHE AND COMMON BATHROOMS ON GROUND
 FLOOR THEY ARE EXTREMELY HARD TO READ AS THEY ARE AND
 WHEN SAVED FOR OUR RECORD WILL NOT TRANSFER WELL. PER
 WPB AMEND TO FBC 107.2.1.4
  
 18. PLEASE PROVIDE A SANITARY COLLECTION ISOMETRIC
 SHOWING ALL THE RISERS LABELED TO MATCH THE FLOOR
 PLANS. WPB AMEND TO FBC 107.2.1
  
 19. PLEASE PROVIDE A COMPLETE WATER ISOMETRIC SHOWING
 THE MAIN, RISERS LABELED TO MATCH FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 20. PLEASE SHOW THE RISER NUMBERS FOR THE SANITARY,
 WATER AND STORM ON FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 21. PLEASE PROVIDE A STORM ISOMETRIC WITH THE SQFT AND
 SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  