2018-01-31 10:24:551ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. LABEL THE KITCHEN EQUIPMENT ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW THE LENGTH OF EACH CUT SECTION OF PIPE
 INCLUDING PIPING TO POOL EQUIPMENT. PER WPB AMEND TO
 FBC 107.2.1
  
 3. SHOW THE CFH LOAD FOR THE POOL EQUIPMENT. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE THE COMBUSTION AIR CALCULATIONS FOR
 THE KITCHENS AND POOL EQUIPMENT. PER FBC FG 304
  
 5. SHOW TABLE USED TO SIZE 2PSI SYSTEM PER FBC FG TABLE
 404.4(1) -(37)
  
 6. PLEASE SUBMIT THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND
 REGULATORS . PER NFPA 54, NFPA 58, AND FBC-2014 FUEL
 GAS SEC. 402.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  