| 2018-01-31 14:05:10 | PERMIT #17110874 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | 1) SHEET LS101: OCCUPANT LOADS ARE SLIGHTLY OFF IN |
| | SEVERAL AREAS. PLEASE REVIEW AND MAKE CHANGES AS |
| | NEEDED. |
| | |
| | 2) LIFE SAFETY SHEETS AND ELECTRICAL LIGHTING PLAN |
| | SHEETS DO NOT APPEAR TO MATCH WITH REGARDS TO EXIT |
| | DIRECTIONAL SIGNS. THE LIFE SAFETY SHEETS SHOW THEM, |
| | BUT THEY ARE NOT LISTED OR NOT AS OBVIOUS ON THE |
| | ELECTRICAL LIGHTING PLAN SHEETS. PLEASE REVIEW AND |
| | ENSURE THAT ALL SHEETS SHOW THE SAME DETAILS. |
| | |
| | 3) DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR, HALLWAY OR LANDING |
| | UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN 7-INCHES |
| | INTO THE REQUIRED WIDTH OF THE EGRESS PATH WHEN FULLY |
| | OPEN. PLEASE REVIEW THE DOOR SWING PROJECTION FOR THE |
| | CONFERENCE ROOM AND MAIN ELECTRICAL ROOM ON SHEET |
| | LS101. |
| | |
| | 4) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND |
| | WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL |
| | BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO |
| | CONSTRUCTION WORK. |
| | |
| | 5) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE |
| | UNDERGROUND FIRE LINE AND FIRE HYDRANTS, AS APPLICABLE |
| | TO THIS PROJECT. |
| | |
| | 6) PER NFPA 1: 16.3.5 STANDPIPES. IN ALL NEW BUILDINGS |
| | IN WHICH STANDPIPES ARE REQUIRED OR WHERE STANDPIPES |
| | EXIST IN BUILDINGS BEING ALTERED OR DEMOLISHED, SUCH |
| | STANDPIPES SHALL BE MAINTAINED IN CONFORMITY WITH THE |
| | PROGRESS OF BUILDING CONSTRUCTION IN SUCH A MANNER THAT |
| | THEY ARE ALWAYS READY FOR USE. [241:7.6] |
| | |
| | 7) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 8) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE |
| | UNDERGROUND FIRE LINE AND FIRE HYDRANTS. |
| | |
| | 9) PLEASE REVIEW AND COMPLY WITH ALL COMMENTS FROM |
| | BUILDING PLAN REVIEW. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4751 |
| | |
| | |