| 2018-02-04 14:33:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 2. PLAN DOES NOT SHOW ADDRESS OF PROJECT. PROVIDE |
| | ADDRESS ON PLAN SHEETS. FBC 107.2.1 |
| | 3. PROVIDE DETAILS OF THE ADDITIONAL LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, |
| | 405.2.2.2 |
| | 4. SHEET E-104 SHOWS LIGHTING ADJACENT TO THE POOL THAT |
| | APPEARS TO BE WITHIN THE ZONE WHERE LIGHTING IS NOT |
| | PERMITTED. PROVIDE CORRECTION. NEC 680.22(B)(1) |
| | 5. SHEET E-201 SHOWS A ?GENERATOR LOAD BANK?. PROVIDE |
| | CLARIFICATION OF LOAD TEST PROCEDURE AND SPECS. WHY IS |
| | THIS FED FROM PANEL EH1? NEC 110.3, 215.5; FBC 107.2.1 |
| | 6. MOST BATHROOMS IN GUEST ROOMS DO NOT SHOW THE |
| | REQUIRED GFCI OUTLET WITHIN 3 FEET OF BASIN. ALSO, THE |
| | CIRCUIT SHOWN FOR THE BATHROOM IS SHOWN FEEDING LIGHTS |
| | OR OUTLETS OUTSIDE OF THE BATHROOM. PROVIDE |
| | CORRECTIONS. NEC 210.11, 210.60 |
| | 7. NOTE 35 OF GENERAL NOTES STATES THAT THE RECEPTACLES |
| | FOR WATER COOLERS SHALL BE DIRECTLY BEHIND THE WATER |
| | COOLER, OUT OF SIGHT. GFCI PROTECTION FOR WATER COOLERS |
| | IS REQUIRED TO BE READILY ACCESSIBLE. PROVIDE FURTHER |
| | EXPLANATION IN NOTE, OR AT LOCATION OF WATER COOLERS, |
| | THAT IF THE RECEPTACLE IS BEHIND COOLER, A GFCI BREAKER |
| | MUST BE USED. NEC 210.8, 422.52 |
| | 8. DIAGRAM FOR SERVICE DISCONNECT 2 OF 2 IS CONFUSING |
| | AND NEEDS CLARIFICATION. THIS IS LABELED AS A FIRE PUMP |
| | ATS, BUT IS SHOWS AS A DISCONNECT. THERE APPEARS TO BE |
| | A FEED FROM THE GENERATOR WHICH SHOWS TWO 600 AMP |
| | BREAKERS TIED TOGETHER, ONE FOR FIRE PUMP AND ONE FOR |
| | ATS-E. FEED FOR FIRE PUMP NEEDS TO BE INDEPENDENT OF |
| | ANY OTHER LOADS. FIRE PUMP AND JOCKEY PUMP ARE NOT |
| | SHOWN ON RISER DIAGRAM. PROVIDE CORRECTION AND |
| | CLARIFICATION. FBC 107.2.1; NEC 695.4, 695.6 |
| | 9. JOCKEY PUMP IS SHOWN AS BEING FED FROM PANEL EH1, |
| | CIRCUIT 7, 9, 11. JOCKEY PUMP FEED SHOULD NOT COME FROM |
| | A SOURCE THAT FEEDS LOADS OTHER THAN FIRE PUMP |
| | ASSOCIATED EQUIPMENT. PROVIDE CORRECTION. NEC 695.6 |
| | 10. PROVIDE SPECS OF FIRE PUMP CONTROLLER/ATS, FIRE |
| | PUMP MOTOR, AND JOCKEY PUMP. INCLUDE MOTOR SIZES AND |
| | AMPERAGE DRAW TO CONFIRM CONDUCTOR SIZING. NEC 110.3, |
| | 695.4, 695.6 |
| | 11. PROVIDE GFI PROTECTION FOR MAIN MSB. NEC 230.95 |
| | 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | ESTIMATED VALUES ARE NOT ACCEPTABLE. NEC 110.9, 110.10 |
| | 13. PROVIDE ACCURATE SIZE OF MAIN BONDING JUMPER. NEC |
| | 250.28(D) |
| | 14. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE. |
| | LOAD CALCULATION PROVIDED SHOWS DEMAND FACTORS APPLIED |
| | TWICE, ONCE FOR EACH PANEL, AND THEN AGAIN FOR NUMBER |
| | OF UNITS. DEMAND FACTORS CAN ONLY BE APPLIED ONCE FOR |
| | SERVICE. ADDITIONALLY, THE DEMAND FACTORS PERMITTED IN |
| | NEC 220.84 APPLY TO DWELLING UNITS, WHICH IS DEFINED AS |
| | A UNIT THAT HAS PERMANENT PROVISIONS FOR LIVING, |
| | SLEEPING, COOKING, AND SANITATION. MANY OF THE GUEST |
| | ROOMS DO NOT FIT THIS DEFINITION, THEREFORE, THE DEMAND |
| | FACTORS COULD NOT BE APPLIED. NO LOAD CALCULATION |
| | PROVIDED FOR SERVICE 2 OF 2, OR FOR GENERATOR. NEC 100, |
| | 220; FBC 107.2.1 |
| | 15. PROVIDE VOLTAGE DROP CALCULATIONS, SHOWING |
| | COMPLIANCE WITH FBC EC C405.7.3, PROVIDE BLOCK NOTE |
| | STATING COMPLIANCE WITH FBC EC C405.7.4 AT COMPLETION |
| | OF PROJECT. |
| | 16. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| | EC 405.7.1 |
| | 17. MANY PANEL SCHEDULES PROVIDED ARE MISSING |
| | INFORMATION INCLUDING LOAD INFORMATION, GFCI |
| | PROTECTION, AND WIRE SIZES. PROVIDE PANEL SCHEDULES FOR |
| | ALL PANELS WITH COMPLETE INFORMATION. NEC 215.2, 215.5, |
| | 408.4, 408.30; FBC 107.2.1 |
| | 18. PROVIDE DETAIL OF LABELING FOR SERVICE. NEC |
| | 230.2(E) |
| | 19. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 20. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 21. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87 |
| | 22. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 |
| | |
| | DUE TO LACK OF INFORMATION OF PLANS PROVIDED, A |
| | COMPLETE REVIEW COULD NOT BE COMPLETED AT THIS TIME. BE |
| | ADVISED THAT FURTHER REVIEW COMMENTS ARE POSSIBLE. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |