| 2018-01-31 11:29:56 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2015 5TH EDITION |
| | |
| | MARRIOTT HOTEL 17110874 |
| | 1ST REVIEW |
| | DATE: JANUARY 31, 2018 |
| | |
| | ACTION: DENIED |
| | |
| | ART IN PUBLIC PLACES |
| | |
| | NOTICE ONLY: THE CITY OF WEST PALM BEACH ART IN PUBLIC |
| | PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY |
| | REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE |
| | PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE |
| | TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 1. ADDRESSING |
| | |
| | PROVIDE THE ADDRESS OF 251 NARCISSUS AVE. IN THE TILE |
| | BLOCK OF ALL PAGES AND SUPPORTING DOCUMENTS. |
| | |
| | IF YOU BELIEVE THIS ADDRESS IS NOT CORRECT CONTACT |
| | MICHAEL ORIO. |
| | CITY MUNI CODE SEC.78-6 (1-7) |
| | (2) LOCATION, BUILDINGS CONTAINING MORE THAN ONE |
| | ADDRESS. ALL ADDRESSES SHALL BE POSTED ON THAT PORTION |
| | OF THE STRUCTURE FRONTING OR FACING UPON THE STREET OR |
| | PRINCIPAL VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE |
| | READILY VISIBLE TO APPROACHING VEHICLES. OWNERS OR |
| | TENANTS OF ALL HOUSES AND BUILDINGS USING A SERVICE |
| | ALLEY SHALL ALSO POST A NUMBER ON THE SIDE OF THE |
| | BUILDINGS ADJACENT TO AND FACING SUCH ALLEY. IF THE |
| | HOUSE OR BUILDING IS OBSTRUCTED BY A FENCE, THEN THE |
| | NUMBER SHALL BE POSTED ON THE FENCE. THE PLACEMENT OF |
| | NUMBERS ON BUILDINGS OR FENCES, AS THE CASE MAY BE, |
| | SHALL BE SUBJECT TO THE DIRECTION OR APPROVAL OF THE |
| | CITY'S CONSTRUCTION SERVICES DEPARTMENT. BUILDINGS |
| | WHICH CONTAIN MORE THAN ONE RESIDENTIAL, COMMERCIAL, |
| | INDUSTRIAL, OR INSTITUTIONAL ADDRESS SHALL POST A |
| | SEPARATE ADDRESS MEETING THE REQUIREMENTS OF THIS |
| | SECTION AT THE EXTERIOR ENTRANCE TO EACH INDIVIDUAL |
| | ADDRESS OR COMMON EXTERIOR ENTRANCE TO SEVERAL |
| | ADDRESSES THEREIN, AND THE UNIT NUMBER SHALL ALSO BE |
| | POSTED ON THE EXTERIOR DOOR OF EACH UNIT SERVED BY SUCH |
| | A COMMON EXTERIOR ENTRANCE. |
| | (3) MONUMENT SIGNS. ALL MONUMENT SIGNS FOR MULTIPLE |
| | RESIDENTIAL, COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL |
| | DEVELOPMENTS SHALL POST THE ADDRESS RANGE FOR THE |
| | DEVELOPMENT. THE POSTED ADDRESS RANGE SHALL MEET THE |
| | REQUIREMENTS OF THIS SECTION. |
| | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| | INFORMATION TECHNOLOGY |
| | TEL: 561-494-1040 |
| | 2. PROVIDE A SQUARE FOOTAGE BREAKDOWN BY USE AND |
| | OCCUPANCY CLASSIFICATION ON PAGE A-000. |
| | THIS IS USED TO ESTIMATE THE PROJECT COST USING ICC |
| | BUILDING VALUATION DATA. |
| | FBC 107.3 |
| | |
| | 3. WATERPROOFING |
| | |
| | ON PAGE A 711 ELEVATOR SECTIONS A AND B SHOW BLINDSIDE |
| | WATERPROOFING. PROVIDE SPECIFICATIONS FOR THIS PRODUCT. |
| | FBC 1805.3 WATERPROOFING. |
| | |
| | WHERE THE GROUND-WATER INVESTIGATION REQUIRED BY |
| | SECTION 1803.5.4 INDICATES THAT A HYDROSTATIC PRESSURE |
| | CONDITION EXISTS, AND THE DESIGN DOES NOT INCLUDE A |
| | GROUND-WATER CONTROL SYSTEM AS DESCRIBED IN SECTION |
| | 1805.1.3, WALLS AND FLOORS SHALL BE WATERPROOFED IN |
| | ACCORDANCE WITH THIS SECTION. |
| | |
| | 4. FLOOD ZONE CERTIFICATES |
| | |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | |
| | (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | |
| | (B) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | |
| | (C) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| | |
| | 5. SUBMIT SUPPORTING DOCUMENTS FROM ARDAMAN @ |
| | ASSOCIATES.THEY SHALL BE REVIEWED BY THE ARCHITECT OF |
| | RECORD AND STAMPED AS REVIEWED AND APPROVED. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 6. THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 6A. THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 6B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 6C. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 6D. A FOUNDATION PERMIT IS IN APPLICATION 17090201 AND |
| | HAS NOT BEEN APPROVED AT THIS POINT. PLEASE SUBMIT THE |
| | THRESHOLD INSPECTION PLAN, SOILS REPORTS AND THRESHOLD |
| | APPLICATION WITH THIS PERMIT AS WELL. |
| | |
| | 7. PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. 2014 |
| | FBC 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL |
| | SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO |
| | UNITS HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR |
| | PERMANENT EXCAVATIONS SHALL NOT BE STEEPER THAN ONE |
| | UNIT VERTICAL IN TWO UNITS HORIZONTAL (50-PERCENT |
| | SLOPE). DEVIATION FROM THE FOREGOING LIMITATIONS FOR |
| | CUT SLOPES SHALL BE PERMITTED ONLY UPON THE |
| | PRESENTATION OF A SOIL INVESTIGATION REPORT ACCEPTABLE |
| | TO THE BUILDING OFFICIAL. |
| | |
| | 8. SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY |
| | BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE |
| | IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED |
| | BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR |
| | FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION |
| | SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED |
| | AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER |
| | MOVEMENT. |
| | |
| | 9. PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION |
| | PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING |
| | PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM |
| | DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION |
| | WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF |
| | AND EROSION DURING CONSTRUCTION OR DEMOLITION |
| | ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION |
| | TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS |
| | OF ADJOINING BUILDINGS ADVISING THEM THAT THE |
| | EXCAVATION IS TO BE MADE AND THAT THE ADJOINING |
| | BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL |
| | BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE |
| | SCHEDULED STARTING DATE OF THE EXCAVATION. |
| | |
| | 10. IMPACT OF CONSTRUCTION 109.3.10. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ. |
| | FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 11. ADJACENT TO EXCAVATIONS FBC 3306.9. EVERY |
| | EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR LESS |
| | FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| | BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE |
| | LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| | LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE |
| | BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| | STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| | CHAPTER 16. |
| | |
| | 12. PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE |
| | PROVIDE COMPLIANCE WITH: FBC-B 3306.5 BARRIERS. |
| | BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN |
| | HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| | NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| | ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| | |
| | 13. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR |
| | BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL |
| | BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR |
| | MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT |
| | THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513, |
| | FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS |
| | WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR |
| | STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND |
| | ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR |
| | STRUCTURES. |
| | |
| | 14. STANDPIPES. FBC 3311.1 |
| | |
| | IN BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION |
| | 905.3.1, NO FEWER THAN ONE STANDPIPE SHALL BE PROVIDED |
| | FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE |
| | INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE |
| | THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST |
| | LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE |
| | SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS |
| | AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| | STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| | TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| | CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| | |
| | 15. IMPACT FEES. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 16. WALL SECTIONS 3 / A. 301 AND 4 / A.301 SHOW FAUX |
| | BEAMS. PLEASE PROVIDE ADDITIONAL INFORMATION ON THIS |
| | PRODUCT. SHOW HOW THIS IS IN COMPLIANCE WITH FBC 603.1 |
| | COMBUSTIBLE MATERIALS IN TYPE I CONSTRUCTION. |
| | |
| | 17. INSULATION IN SEVERAL LOCATIONS IS SHOWN AS R-20. |
| | THE ENERGY CALCS PROVIDED SHOW R-19 AT ROOF LOCATIONS. |
| | PLEASE CLARIFY. FBC 107.3 |
| | |
| | 18. ON PAGE A. 204A PROVIDE A ROOM DESCRIPTION FOR THE |
| | ROOM NEXT TO THE ELEVATOR SHAFT WITH DOOR 808A. FBC |
| | 107.3 |
| | |
| | 19. ACCESSIBILITY |
| | |
| | A. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR GUEST |
| | RECEPTION COUNTER. |
| | |
| | B. PROVIDE ACCESSIBLE COUNTER AT FIRST FLOOR BAR. |
| | |
| | C. PROVIDE ACCESSIBLE SEATING IN DINING ROOM 1ST FLOOR |
| | CAF? ON TERRACE, RESTAURANT. |
| | |
| | D. PROVIDE ACCESSIBLE COUNTER AT ROOF TOP MAIN POOL BAR |
| | AND SATELLITE BAR. |
| | |
| | INCLUDE ELEVATIONS OF THESE AREAS TO SHOW COMPLIANCE |
| | WITH THE FLORIDA ACCESSIBILITY CODE FOLLOWING SECTIONS. |
| | |
| | 902.1 DINING SURFACES AND WORK SURFACES SHALL COMPLY |
| | WITH 902.2 AND 902.3. |
| | |
| | 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 904.4 SALES AND SERVICE COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| | SERVICE COUNTER TOP. |
| | |
| | 902.4.1 CLEAR FLOOR OR GROUND SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR |
| | FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED, EXCEPT |
| | THAT KNEE CLEARANCE 24 INCHES (610 MM) MINIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND SHALL BE PERMITTED. |
| | |
| | 902.4.2 HEIGHT. |
| | THE TOPS OF TABLES AND COUNTERS SHALL BE 26 INCHES (660 |
| | MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 20. DOOR ARRANGEMENT |
| | |
| | THE DISTANCE BETWEEN THE DOORS IN SERIES AT THE |
| | CORRIDOR BY THE CORNER SUITES IS LESS THAN 48?. SEE |
| | SUITES 211 AND 243 FOR AN EXAMPLE. |
| | |
| | FBC 1008.1.8 SPACE BETWEEN TWO DOORS IN A SERIES SHALL |
| | BE 48 INCHES (1219 MM) MINIMUM PLUS THE WIDTH OF A DOOR |
| | SWINGING INTO THE SPACE. DOORS IN A SERIES SHALL SWING |
| | EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE |
| | BETWEEN THE DOORS. |
| | |
| | |
| | 21. RAILING SHOWN ON ID 303 1. THE HEIGHT IS OK. WHAT |
| | IS ON THE OPPOSITE SIDE. SHOW COMPLIANCE WITH FBC |
| | 1013.2 WHERE REQUIRED. |
| | |
| | GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING |
| | SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS, |
| | STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN |
| | 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR |
| | GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM) |
| | HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS SHALL |
| | BE ADEQUATE IN STRENGTH AND ATTACHMENT IN ACCORDANCE |
| | WITH SECTION 1607.8. |
| | |
| | FBC 1013.4 OPENING LIMITATIONS. |
| | REQUIRED GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW |
| | PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM |
| | THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. |
| | |
| | 22. PRODUCT APPROVALS |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND |
| | DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS |
| | AND NANA WALLS. DATA SHEET FOR ELEVATOR. |
| | |
| | ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED |
| | SUBMITTAL BY LISTING THEM ON THE COVER SHEET. |
| | |
| | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 23. CONFIRM THAT THE NANA WALL ASSEMBLY USED WILL |
| | EXCEED THE PRESSURES FOR THE AREAS THAT THEY ARE |
| | LOCATED. OFTEN THESE DOORS DO NOT MEET THE PRESSURE |
| | REQUIREMENTS FOR THIS TYPE OF BUILDING. FBC CHAPTER 16 |
| | FOR COMPONENTS AND CLADDING. |
| | |
| | 24. PROVIDE THE CALCULATIONS TO SHOW MAXIMUM AREA OF |
| | EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION |
| | DISTANCE AND DEGREE OF OPENING PROTECTION ON THE WEST |
| | SIDE OF THE HOTEL AND THE PROPOSED BUILDING ALONG THAT |
| | WEST WALL. |
| | FBC 705.8 AND TABLE 705.8. |
| | FBC 705.8.1 ALLOWABLE AREA OF OPENINGS. |
| | THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| | PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| | BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| | TABLE 705.8. |
| | |
| | 25. SEPARATE PERMITS REQUIRED FOR CONSTRUCTION |
| | TRAILERS, LANDSCAPING, SIGNS AND SWIMMING POOL. |
| | THE FOUNDATION PERMIT SUBMITTED 17090201 HAS COMPLETED |
| | THE FIRST ROUND OF PLAN REVIEWS. FBC 105.1 |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |