Plan Review Notes
Plan Review Notes For Permit 17110870
Permit Number 17110870
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-29 08:01:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE PRODUCT APPROVAL DID NOT PRINT CORRECTLY; THE
 RIGHT HALF OF THE PRODUCT APPROVAL WAS NOT INCLUDED.
 PLEASE RE-PRINT AND COLLATE TWO NEW PACKAGES.
  
 2. THE ASSEMBY SELECTED HAS A DESIGN PRSSURE LIMITATION
 OF -45 WHICH DOES NOT MEET THE REQUIREMENTS FOR ZONES 2
 AND 3 SPECIFIED BY ENGINEER OF RECORD ON PAGE S3
 (Z1=-29.5, Z2=-56.28, Z3=-56.28), PROVIDE ENGINEERING
 FOR ENHANCED FASTENING (BUT ALSO SEE COMMENT #3).
  
 3. BASED ON FBC B 1609 AND ASCE 7-10, DESIGN PRESSURES
 OF -37.9, -63.6 ARE REQUIRED FOR ZONES 2, 3 FOR A
 BUILDING WITH 15MRH (SUBJECT BUILDING HAS 18.5'MRH).
 DESIGN PRESSURES APPEAR LOW. SEE ENGINEER'S
 CALCULATIONS, (OUR PAGE 200 OF 235), APPEARS TO STATE
 ZONE 1 -39.50, ZONE 2 AND 3 -66.28 PSF.
  
 (ENGINEER'S CALCS - MECAWIND PRO, PROJECT NO 1707,
 DESIGNED BY MM - THIS CAN BE PROVIDED VIA EMAIL TO THE
 ENGINEER UPON REQUEST)
  
 TO ADDRESS - REVISE SHEET S-3 TO MAKE ROOF DESIGN
 PRESSURES CONSISTENT WITH CALCULATIONS, OR HAVE
 ENGINEER SEND EXPLANATION TO ME VIA EMAIL (AM I READING
 THE CALCULATIONS INCORRECTLY?) ALSO PLEASE CHECK ALL
 OTHER DESIGN CRITERIA ON THE PLAN AT THIS TIME AND
 REVISE IF NECESSARY.
  
  