| 2018-04-04 11:04:10 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17110860 |
| | ADD: 1901 VILLAGE BLVD. / BEAR LAKES COUNTRY CLUB |
| | CONT: MOUW ASSOCIATES, INC. |
| | TEL: 561-276-9640 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. APRIL 4/2018 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) BUILDING PROVISO/ DEFERRED SUBMITTALS: PLEASE SUBMIT |
| | (3) COPIES OF EACH IF PAPER. 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY |
| | GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH |
| | IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 3) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOFING: FOR |
| | ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| | SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. |
| | |
| | 4) BUILDING PROVISO/ DEFERRED SUBMITTALS: W. P. B. |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | 5) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |