| 2018-03-16 14:20:17 | |
| | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED |
| | |
| | COMMENT 4: THE LOCKER ROOMS SHALL BE PROVIDED WITH A |
| | WATER FOUNTAIN PER FBC PL TABLE 403.1 AND 410. |
| | |
| | RESPONSE: PER FBC PL 403.1, TWO DRINKING FOUNTAINS ARE |
| | REQUIRED, PER PBC PL 410; A HI-LOW DRINKING FOUNTAIN IS |
| | COUNTED AS TWO DRINKING FOUNTAINS. THERE IS A HI-LOW |
| | DRINKING FOUNTAIN LOCATED IN KITCHEN 2004 OUTSIDE OF |
| | STAFF DINING 2015. THE MEN?S AND WOMEN?S LOCKER ROOMS |
| | HAVE FULL-TIME ATTENDANTS (ROOMS 2081 & 2049) WHICH |
| | CATER TO THOSE IN THE LOCKER ROOMS. A) WILL |
| | THE OCCUPANTS FROM THE LOCKER ROOMS HAVE ACCESS TO THE |
| | WATER FOUNTAIN IN THE KITCHEN MOST COMMERCIAL KITCHENS |
| | DON?T ALLOW GUEST TO ENTER, IF NOT THAN A WATER |
| | FOUNTAIN SHALL BE PROVIDED FOR THE OCCUPANTS THE FACT |
| | THAT THERE IS AN ATTENDANT DOES NOT COMPLY WITH THE |
| | CODE. PER FBC PL TABLE 403.1 AND 410 |
| | |
| | COMMENT 7: SHT. A-505, 506 ALL TRANSFER TYPE SHOWERS |
| | SHALL SHOW INSIDE DIMENSIONS OF 36"X36". SOME OF THE |
| | DIMENSIONS ON THE PLAN DO NOT COMPLY. PLEASE CLARIFY |
| | PER FBC ACC 608.2.1. |
| | |
| | RESPONSE: ONLY SHOWERS 2060, 2061, AND 2075 ARE |
| | ACCESSIBLE SHOWERS. SEE REV.1 DRAWING SHEET A-506. |
| | A) THE DIMENSIONS ARE STILL SHOWN AT 39-1/4? WIDE AND |
| | 37? DEEP PLEASE CLARIFY. |
| | |
| | |
| | COMMENT 8: PLEASE SHOW THE DIMENSIONS OF THE HEIGHT OF |
| | THE RIM AND THE CLEARANCE FOR KNEE AND TOE CLEARANCE |
| | FOR THE LAVATORY IN BATHROOMS 2054, 2081, 2027, 2041, |
| | AND 2049 PER FBC ACC 213.3.4, 606. |
| | |
| | RESPONSE: SEE DETAIL 10 ON REV.1 DRAWING SHEET A-905. |
| | A) THE DETAIL DOES NOT SHOW THE REQUIRED KNEE AND TOE |
| | CLEARANCE, PLEASE SHOW CLEAR FLOOR SPACE. PER FBC ACC |
| | 306 |
| | |
| | COMMENT 10: THE PLUMBING SHEETS SHOW THE ROOM NUMBERS |
| | IN THE 1000'S AND THE ARCHITECTURAL SHEETS SHOW THEM IN |
| | THE 2000'S. PLEASE CLARIFY PER WPB AMEND TO FBC |
| | 107.2.1. |
| | |
| | RESPONSE: ROOM NUMBERS ON ALL PLUMBING SHEETS HAVE BEEN |
| | UPDATED TO MATCH THE ARCHITECTURAL NUMERICAL ORDER AS |
| | PER FBC 107.2.1. |
| | A) THE ROOM NUMBER ON THE PLUMBING SHEETS ARE STILL |
| | SHOWN AS 2000?S |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. P7.1 DETAIL #12 AND 13 THE COLD WATER SUPPLY IS |
| | SHOWN CONNECTING TO INLET OF THE STORAGE TANK AND |
| | OUTLET OF THE BOILER THE COLD SHOULD BE CONNECTED TO |
| | THE INLET OF THE BOILER PROVIDE THE MANUFACTURES |
| | INSTILLATION GUIDE TO VERIFY. PER WBP AMEND TO FBC |
| | 107.2.1. |
| | |
| | 2. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| | INTERCEPTOR PLEASE PLEASE NOTE ON PLAN. PER WBP AMEND |
| | TO FBC 107.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |