Plan Review Notes
Plan Review Notes For Permit 17110860
Permit Number 17110860
Review Stop P
Sequence Number 2
Notes
Date Text
2018-03-16 14:20:17 
 2ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 COMMENT 4: THE LOCKER ROOMS SHALL BE PROVIDED WITH A
 WATER FOUNTAIN PER FBC PL TABLE 403.1 AND 410.
  
 RESPONSE: PER FBC PL 403.1, TWO DRINKING FOUNTAINS ARE
 REQUIRED, PER PBC PL 410; A HI-LOW DRINKING FOUNTAIN IS
 COUNTED AS TWO DRINKING FOUNTAINS. THERE IS A HI-LOW
 DRINKING FOUNTAIN LOCATED IN KITCHEN 2004 OUTSIDE OF
 STAFF DINING 2015. THE MEN?S AND WOMEN?S LOCKER ROOMS
 HAVE FULL-TIME ATTENDANTS (ROOMS 2081 & 2049) WHICH
 CATER TO THOSE IN THE LOCKER ROOMS. A) WILL
 THE OCCUPANTS FROM THE LOCKER ROOMS HAVE ACCESS TO THE
 WATER FOUNTAIN IN THE KITCHEN MOST COMMERCIAL KITCHENS
 DON?T ALLOW GUEST TO ENTER, IF NOT THAN A WATER
 FOUNTAIN SHALL BE PROVIDED FOR THE OCCUPANTS THE FACT
 THAT THERE IS AN ATTENDANT DOES NOT COMPLY WITH THE
 CODE. PER FBC PL TABLE 403.1 AND 410
  
  COMMENT 7: SHT. A-505, 506 ALL TRANSFER TYPE SHOWERS
 SHALL SHOW INSIDE DIMENSIONS OF 36"X36". SOME OF THE
 DIMENSIONS ON THE PLAN DO NOT COMPLY. PLEASE CLARIFY
 PER FBC ACC 608.2.1.
  
 RESPONSE: ONLY SHOWERS 2060, 2061, AND 2075 ARE
 ACCESSIBLE SHOWERS. SEE REV.1 DRAWING SHEET A-506.
 A) THE DIMENSIONS ARE STILL SHOWN AT 39-1/4? WIDE AND
 37? DEEP PLEASE CLARIFY.
  
  
 COMMENT 8: PLEASE SHOW THE DIMENSIONS OF THE HEIGHT OF
 THE RIM AND THE CLEARANCE FOR KNEE AND TOE CLEARANCE
 FOR THE LAVATORY IN BATHROOMS 2054, 2081, 2027, 2041,
 AND 2049 PER FBC ACC 213.3.4, 606.
  
 RESPONSE: SEE DETAIL 10 ON REV.1 DRAWING SHEET A-905.
 A) THE DETAIL DOES NOT SHOW THE REQUIRED KNEE AND TOE
 CLEARANCE, PLEASE SHOW CLEAR FLOOR SPACE. PER FBC ACC
 306
  
 COMMENT 10: THE PLUMBING SHEETS SHOW THE ROOM NUMBERS
 IN THE 1000'S AND THE ARCHITECTURAL SHEETS SHOW THEM IN
 THE 2000'S. PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1.
  
 RESPONSE: ROOM NUMBERS ON ALL PLUMBING SHEETS HAVE BEEN
 UPDATED TO MATCH THE ARCHITECTURAL NUMERICAL ORDER AS
 PER FBC 107.2.1.
 A) THE ROOM NUMBER ON THE PLUMBING SHEETS ARE STILL
 SHOWN AS 2000?S
  
 NEW COMMENTS:
  
 1. SHT. P7.1 DETAIL #12 AND 13 THE COLD WATER SUPPLY IS
 SHOWN CONNECTING TO INLET OF THE STORAGE TANK AND
 OUTLET OF THE BOILER THE COLD SHOULD BE CONNECTED TO
 THE INLET OF THE BOILER PROVIDE THE MANUFACTURES
 INSTILLATION GUIDE TO VERIFY. PER WBP AMEND TO FBC
 107.2.1.
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR PLEASE PLEASE NOTE ON PLAN. PER WBP AMEND
 TO FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  