Plan Review Notes
Plan Review Notes For Permit 17110860
Permit Number 17110860
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-09 15:20:012ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17110860
 3/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.3: THE REVISED PLAN INDICATES COMPLIANCE IN
 TERMS OF EXHAUST VENTILATION CAPACITY FOR THE GOLF CART
 PARKING GARAGE, HOWEVER THE SEQUENCE OF OPERATION FOR
 THE EXHAUST FANS HAS NOT BEEN CLARIFIED. PLEASE NOTE
 THAT SECTION 502.4.2 REQUIRES CONTINUOUS VENTILATION TO
 LIMIT HYDROGEN CONCENTRATION, AND SECTION 502.4.3
 REQUIRES THE VENTILATION SYSTEM TO BE SUPERVISED BY
  
 AN APPROVED CENTRAL, PROPRIETARY OR REMOTE STATION
 SERVICE OR SHALL INITIATE AN AUDIBLE AND VISUAL SIGNAL
 AT A CONSTANTLY ATTENDED ON-SITE LOCATION. PLEASE
 PROVIDE ADDITIONAL NOTES AND DETAILS.
  
 2) M2.1: EXHAUST FANS EF-0-1 AND EF-7 ARE REQUIRED TO
 DISCHARGE TO THE OUTDOORS- SECTION 501.3. THE PLAN
 SHOWS THE FANS DISCHARGING ONTO THE GARAGE.
  
 3) M2.5 & A.105: PLEASE PROVIDE ENLARGED ARCHITECTURAL
 AND STRUCTURAL DETAILS FOR THE PROPOSED NEW ROOF LADDER
 NEEDED FOR ACCESS TO AHU-1-8A AND AHU-1-8B.
  
 4) M5.1: THE WIND LOAD ENGINEERING FOR THE RTUIS IS
 INCOMPLETE. PLEASE SHOW HOW THE UNIOTS WILL BE ATTACHED
 TO THE CURBS, AND SUBMIT THE NOA FOR THE THYBAR CURB
 WITH SHOP DRAWING APPROVAL BY THE EOR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  