2018-03-16 15:01:39 
 2ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 COMMENT 1: PROVIDE ELEVATION PLAN SHOWING LOCATION OF
 CONCENTRIC VENT TERMINAL WITH DIMENSIONS TO OPENINGS.
 PER WBP AMEND TO FBC 107.2.1.
 RESPONSE: DIMENSIONS HAVE BEEN ADDED TO FUEL GAS
 ISOMETRIC PLAN ON SHEET FG3.1. DIMENSION NOT SHOWN
  
 NEW COMMENTS:
  
 1. SHOW THE LENGTH OF THE PIPE ON THE RISER FROM THE MP
 REGULATOR TO THE KITCHEN EQUIPMENT. PER FBC FG 402.4.1
 AND PER WBP AMEND TO FBC 107.2.1.
  
 2. PLEASE SIZE THE PIPE DOWN STREAM OF THE EMERGENCY
 VALVE FOR KIT EQUIPMENT. PER FBC FG 402.4.1 AND PER WBP
 AMEND TO FBC 107.2.1.
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDES FOR ALL GAS EQUIPMENT AND REGULATORS. PER WBP
 AMEND TO FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  