2018-02-14 12:08:19PERMIT # 17110860
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW - APPROVED PROVISO:
  
 FAILURE TO COMPLY WITH ALL PROVISO COMMENTS WILL RESULT
 IN A FAILED FIRE INSPECTION.
  
 REPEAT COMMENTS:
  
 SHEET G101: TABLES AND CHAIRS APPEAR TO IMPEDE THE
 DIRECT ACCESS PATH TO THE EXIT DOORS. THIS NEEDS TO BE
 REVIEWED AND VERIFIED IN THE FIELD. CHANGES MAY BE
 REQUIRED TO THE FURNITURE LAYOUT, AS DEEMED NECESSARY
 BY THE FIRE INSPECTOR.
  
 SHEETS E2.1 AND E2.2: EMERGENCY LIGHTING FIXTURES
 AND/OR EXIT SIGNAGE IS NOT CLEARLY IDENTIFIED.
 EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL BE INSTALLED
 AND MAINTAINED PER NFPA 101, CHAPTER 7. THIS IS TO BE
 VERIFIED AND INSPECTED TO ENSURE CODE COMPLIANCE, BY
 THE FIRE INSPECTOR. FAILURE TO COMPLY WITH THE FIRE
 CODE REQUIREMENTS, WILL RESULT IN A FAILED FIRE
 INSPECTION.
  