| 2018-01-12 16:09:44 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THIS PROJECT IS REQUIRED TO COMPLY WITH FBC PL |
| | 403.1.3 POTTY PARITY. |
| | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| | SECTION 553.86, FLORIDA STATUTES. |
| | |
| | 2. THE BATHROOM 2014 IN THE KITCHEN SHALL NOT OPEN |
| | DIRECTLY INTO THE KITCHEN PER FBC PL 403.3.2 |
| | |
| | 3. AT LEAST ONE TOILET COMMITMENT IN THE LOCKER-ROOM |
| | BATHROOMS SHALL COMPLY WITH THE REQUIREMENTS OF AN |
| | AMBULATORY STALL PER FBC ACC 213.3.1 AND 604.8.2 |
| | |
| | 4. THE LOCKER ROOMS SHALL BE PROVIDED WITH A WATER |
| | FOUNTAIN PER FBC PL TABLE 403.1 AND 410 |
| | |
| | 5. SHT. A-903 THE SHOWER STALL DETAIL (36"X36") NOTES |
| | THE LOWEST POINT OF MOUNTING AT 48" THE CODE STATES 38" |
| | MIN 48" MAX PLEASE CLARIFY. PER FBC ACC 608.5.1 |
| | |
| | 6. SHT. A-504, 505, 506 PLEASE SHOW THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE ACCESSIBLE FIXTURES PLEASE INCLUDE |
| | DIMENSIONS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHT. A-505, 506 ALL TRANSFER TYPE SHOWERS SHALL SHOW |
| | INSIDE DIMENSIONS OF 36"X36" SOME OF THE DIMENSIONS ON |
| | THE PLAN DO NOT COMPLY PLEASE CLARIFY. PER FBC ACC |
| | 608.2.1 |
| | |
| | 8. PLEASE SHOW THE DIMENSIONS OF THE HEIGHT OF THE RIM |
| | AND THE CLEARANCE FOR KNEE AND TOE CLEARANCE FOR THE |
| | LAVATORY,S IN BATHROOMS 2054, 2081, 2027, 2041, 2049 |
| | PER FBC ACC 213.3.4, 606 |
| | |
| | 9. SHT P-2.4, 3.4, 3.6 IN ROOMS 1049 AND 1081 THE |
| | SANITARY AND WATER PIPING IS SHOWN IN A DIFFERENT |
| | LOCATION AS THE FIXTURES ARE SHOWN IN PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. THE PLUMBING SHEETS SHOW THE ROOM NUMBERS IN THE |
| | 1000'S AND THE ARCHITECTURAL SHEETS SHOW THEM IN THE |
| | 2000'S PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 11. SHT. G-001 UNDER THE SHEET INDEX THE FIRE SPRINKLER |
| | PLANS ARE LISTED UNDER THE FUEL GAS AND THE FUEL GAS |
| | SHEETS ARE NOT LISTED IN THE INDEX PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. THE FFD-1 OUTSIDE THE KEG COOLER APPEARS TO BE ON |
| | THE EXTERIOR OF THE BUILDING, HOW WILL IT BE COVERED TO |
| | PREVENT RAIN WATER FROM DISCHARGING INTO THE SANITARY |
| | SYSTEM. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 13. PLEASE PROVIDE A KITCHEN EQUIPMENT PLAN WITH |
| | SCHEDULE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 14. THE FLOOR SINK FOR THE ICE MACHINE SHALL DISCHARGE |
| | TO THE SANITARY NOT THE GREASE. PER FBC PL 1003.2 |
| | |
| | 15. THE HCWC AND THE HCSH ARE NOT VENTED PROPERLY THEY |
| | SHOULD BE VENTED AS A WET VENT OR INDIVIDUAL VENT. PER |
| | FBC PL 901.2.1, 910.1, 912.1 |
| | |
| | 16. SHT. P-5.1, 5.2 PLEASE IDENTIFY AND LABEL EACH |
| | RISER AND STACK WITH A NUMBER OR LETTER SYSTEM .PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 17. SHT. P5.2 PROVIDE VALVES FOR ALL DROPS AND HOSE |
| | BIBS. PER FBC PL 606.1, 606.2 |
| | |
| | 18. SHT. P-5.2 PLEASE SIZE THE BRANCHES OR STUB OUTS ON |
| | FIXTURES. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 19. LAVS ARE REQUIRED TO HAVE TEMPERED WATER ONLY BUT |
| | THE JANITORS SINK IS REQUIRED TO HAVE HOT WATER. EACH |
| | LAV SHOULD BE EQUIPPED WITH A WATER TEMPERATURE |
| | LIMITING DEVISE PER FBC PL ,416.5 TEMPERED WATER FOR |
| | PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | 607.1 IN NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE |
| | SUPPLIED FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR |
| | BUILDING MAINTENANCE PURPOSES. |
| | |
| | 20. SHT. P-6.1 THE LOCATION OF THE ROOF DRAINS AND |
| | PIPING IS SHOWN IN A DIFFERENT LOCATION AS THE |
| | ARCHITECTURAL PLAN SHOWS PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 21. SHT. P6.1 IS ANY OF THE SLOPED TILE ROOF DRAINING |
| | ONTO THE FLAT ROOF IF SO IS THE SQFT INCLUDED IN THE |
| | SIZING CALCULATIONS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 22. SHT. P6.2 NOTE #1 STATES THE NEW 4" STORM IS TO |
| | CONNECT TO EXISTING 4" STORM PLEASE PROVIDE EXISTING |
| | LOAD THAT THE NEW LOAD IS BEING ADDED TO. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 23. SHT.P7.1 DETAIL #9 THE SAMPLING PORT SHALL NO BE A |
| | DOUBLE SANITARY TEE WITH A CAP ON THE BOTTOM IT SHALL |
| | BE A MIN OF A 4" TWO WAT CLEAN OUT OR A PREMANUFACTURED |
| | SAMPLING PORT. PER WPB UTILITIES DEPT. |
| | |
| | 24. SHT. P7.1 WILL BOTH WATER HEATERS HAVE THE |
| | THERMOSTATIC MIXING VALVE WITH 110 DEG. AND 140 DEG. |
| | LINES THE GWH2 APPEARS ONLY TO HAVE A SINGLE HOT LINE |
| | PLEASE CLARIFY AND PROVIDE SEPARATE DETAIL IF NEEDED. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 25. EXISTING GREASE INTERCEPTOR SHALL BE CERTIFIED THAT |
| | IT IS IN GOOD WORKING ORDER PROVIDE NOTE ON PLAN AND |
| | CONTACT WPB UTILITIES DEPT FOR INSPECTION DETAILS . PER |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |