2018-01-12 16:09:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS PROJECT IS REQUIRED TO COMPLY WITH FBC PL
 403.1.3 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
  
 2. THE BATHROOM 2014 IN THE KITCHEN SHALL NOT OPEN
 DIRECTLY INTO THE KITCHEN PER FBC PL 403.3.2
  
 3. AT LEAST ONE TOILET COMMITMENT IN THE LOCKER-ROOM
 BATHROOMS SHALL COMPLY WITH THE REQUIREMENTS OF AN
 AMBULATORY STALL PER FBC ACC 213.3.1 AND 604.8.2
  
 4. THE LOCKER ROOMS SHALL BE PROVIDED WITH A WATER
 FOUNTAIN PER FBC PL TABLE 403.1 AND 410
  
 5. SHT. A-903 THE SHOWER STALL DETAIL (36"X36") NOTES
 THE LOWEST POINT OF MOUNTING AT 48" THE CODE STATES 38"
 MIN 48" MAX PLEASE CLARIFY. PER FBC ACC 608.5.1
  
 6. SHT. A-504, 505, 506 PLEASE SHOW THE REQUIRED CLEAR
 FLOOR SPACE FOR THE ACCESSIBLE FIXTURES PLEASE INCLUDE
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. A-505, 506 ALL TRANSFER TYPE SHOWERS SHALL SHOW
 INSIDE DIMENSIONS OF 36"X36" SOME OF THE DIMENSIONS ON
 THE PLAN DO NOT COMPLY PLEASE CLARIFY. PER FBC ACC
 608.2.1
  
 8. PLEASE SHOW THE DIMENSIONS OF THE HEIGHT OF THE RIM
 AND THE CLEARANCE FOR KNEE AND TOE CLEARANCE FOR THE
 LAVATORY,S IN BATHROOMS 2054, 2081, 2027, 2041, 2049
 PER FBC ACC 213.3.4, 606
  
 9. SHT P-2.4, 3.4, 3.6 IN ROOMS 1049 AND 1081 THE
 SANITARY AND WATER PIPING IS SHOWN IN A DIFFERENT
 LOCATION AS THE FIXTURES ARE SHOWN IN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 10. THE PLUMBING SHEETS SHOW THE ROOM NUMBERS IN THE
 1000'S AND THE ARCHITECTURAL SHEETS SHOW THEM IN THE
 2000'S PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 11. SHT. G-001 UNDER THE SHEET INDEX THE FIRE SPRINKLER
 PLANS ARE LISTED UNDER THE FUEL GAS AND THE FUEL GAS
 SHEETS ARE NOT LISTED IN THE INDEX PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 12. THE FFD-1 OUTSIDE THE KEG COOLER APPEARS TO BE ON
 THE EXTERIOR OF THE BUILDING, HOW WILL IT BE COVERED TO
 PREVENT RAIN WATER FROM DISCHARGING INTO THE SANITARY
 SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 13. PLEASE PROVIDE A KITCHEN EQUIPMENT PLAN WITH
 SCHEDULE. PER WPB AMEND TO FBC 107.2.1
  
 14. THE FLOOR SINK FOR THE ICE MACHINE SHALL DISCHARGE
 TO THE SANITARY NOT THE GREASE. PER FBC PL 1003.2
  
 15. THE HCWC AND THE HCSH ARE NOT VENTED PROPERLY THEY
 SHOULD BE VENTED AS A WET VENT OR INDIVIDUAL VENT. PER
 FBC PL 901.2.1, 910.1, 912.1
  
 16. SHT. P-5.1, 5.2 PLEASE IDENTIFY AND LABEL EACH
 RISER AND STACK WITH A NUMBER OR LETTER SYSTEM .PER WPB
 AMEND TO FBC 107.2.1
  
 17. SHT. P5.2 PROVIDE VALVES FOR ALL DROPS AND HOSE
 BIBS. PER FBC PL 606.1, 606.2
  
 18. SHT. P-5.2 PLEASE SIZE THE BRANCHES OR STUB OUTS ON
 FIXTURES. PER WPB AMEND TO FBC 107.2.1
  
 19. LAVS ARE REQUIRED TO HAVE TEMPERED WATER ONLY BUT
 THE JANITORS SINK IS REQUIRED TO HAVE HOT WATER. EACH
 LAV SHOULD BE EQUIPPED WITH A WATER TEMPERATURE
 LIMITING DEVISE PER FBC PL ,416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 607.1 IN NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE
 SUPPLIED FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR
 BUILDING MAINTENANCE PURPOSES.
  
 20. SHT. P-6.1 THE LOCATION OF THE ROOF DRAINS AND
 PIPING IS SHOWN IN A DIFFERENT LOCATION AS THE
 ARCHITECTURAL PLAN SHOWS PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 21. SHT. P6.1 IS ANY OF THE SLOPED TILE ROOF DRAINING
 ONTO THE FLAT ROOF IF SO IS THE SQFT INCLUDED IN THE
 SIZING CALCULATIONS. PER WPB AMEND TO FBC 107.2.1
  
 22. SHT. P6.2 NOTE #1 STATES THE NEW 4" STORM IS TO
 CONNECT TO EXISTING 4" STORM PLEASE PROVIDE EXISTING
 LOAD THAT THE NEW LOAD IS BEING ADDED TO. PER WPB AMEND
 TO FBC 107.2.1
  
 23. SHT.P7.1 DETAIL #9 THE SAMPLING PORT SHALL NO BE A
 DOUBLE SANITARY TEE WITH A CAP ON THE BOTTOM IT SHALL
 BE A MIN OF A 4" TWO WAT CLEAN OUT OR A PREMANUFACTURED
 SAMPLING PORT. PER WPB UTILITIES DEPT.
  
 24. SHT. P7.1 WILL BOTH WATER HEATERS HAVE THE
 THERMOSTATIC MIXING VALVE WITH 110 DEG. AND 140 DEG.
 LINES THE GWH2 APPEARS ONLY TO HAVE A SINGLE HOT LINE
 PLEASE CLARIFY AND PROVIDE SEPARATE DETAIL IF NEEDED.
 PER WPB AMEND TO FBC 107.2.1
  
 25. EXISTING GREASE INTERCEPTOR SHALL BE CERTIFIED THAT
 IT IS IN GOOD WORKING ORDER PROVIDE NOTE ON PLAN AND
 CONTACT WPB UTILITIES DEPT FOR INSPECTION DETAILS . PER
 PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER