2018-01-05 08:38:391ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110860
 1/4/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT
 AS REQUIRED BY SECTION C101.4.3 FBC-14 ENERGY
 CONSERVATION.
  
 2) M1.3: PROVIDE A SCOPE OF WORK FOR THE CHILLER,
 PUMPS, AND ALL OTHER ASSOCIATED EQUIPMENT- EXISTING TO
 REMAIN? PROVIDE A SYMBOL ON THE PLAN THAT INDICATES THE
 POINT OF DEMO FOR THE EXISTING CHILLER PIPING. M4.1:
 PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLER, PUMPS ETC.
  
 3) SHEETS A-101, M1.3 & M2.1: THE GOLF CART STORAGE
 AREA IS CLASSIFIED AS A PARKING GARAGE AND REQUIRES AN
 EXHAUST VENTILATION SYSTEM IN COMPLIANCE WITH SECTION
 404.1 FBC-14 MECHANICAL. PLEASE CLARIFY IF THERE IS AN
 EXISTING SYSTEM THAT IS IN COMPLIANCE, OR REVISE THE
 PLANS TO SHOW ALL PROPOSED ALTERATIONS AND NEW
 INSTALLATIONS.
  
 4) SHEETS A-101, M1.3, & M2.1: PLEASE IDENTIFY ALL
 ROOMS AND SPACES ON THE MECHANICAL PLANS AS THEY ARE
 SHOWN ON THE ARCHITECTURAL PLANS. CLARIFY IF ANY OF THE
 ROOMS ARE USED FOR GOLF CART BATTERY STORAGE AND/OR
 BATTERY RECHARGING. PROVIDE EXHAUST VENTILATION SYSTEMS
 AND CALCULATIONS WHERE REQUIRED BY SECTION 502.
  
 5) M4.1: PLEASE INCLUDE EXHAUST VENTILATION
 CALCULATIONS IN THE VENTILATION SCHEDULE. INDICATE THE
 REQUIRED AND PROVIDED CFMS OF EXHAUST FOR EACH LOCKER
 ROOM, BATHROOM, JANITORS CLOSETS, STORAGE ROOMS ETC.
  
 6) M4.1: SECTION 403.3.2.3.3 NOTED UNDER THE
 VENTILATION SCHEDULE DOES NOT EXIST IN THE FBC-14 FIFTH
 EDITION MECHANICAL CODE- PLEASE CORRECT AND CLARIFY
 WHAT THE 0.5 DIVERSITY FACTOR IS AND HOW IT IS
 APPLICABLE TO THE PROPOSED PROJECT.
  
 7) M2.5: INDICATE HOW ACCESS TO AHU'S 1-8A & 1-8B WILL
 BE PROVIDED- SECTION 306.5.
  
 8) M2.5: THE CONDENSATE PIPING SUPPORTS SHALL BE SPACED
 MINIMUM 4' APART PER TABLE 305.4.
  
 9) M2.5 & M5.1: PROVIDE THE SITE SPECIFIC WIND LOAD
 DESIGN CRITERIA FOR INSTALLATION OF THE ROOF TOP
 SUPPORTS AND EQUIPMENT- SECTION 1609 FBC-14 BUILDING.
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE THYBAR
 CURB WITH SHOP DRAWING APPROVAL STAMP BY THE EOR.
 CLARIFY IF THE RTU ATTACHMENT DETAILS ON M2.1 ARE
 APPLICABLE TO ALL THE ROOFTOP UNITS INCLUDING THE AHU'S
 AND OAU'S, AND
  
 PROVIDE ATTACHMENT AND ANCHORING DETAILS FOR THE
 ROOFTOP DUCTWORK- SECTION 301.15.
  
 10) M2.5: THE FLORIDA PRODUCT APPROVAL #3203.1 FOR THE
 RM ENTERPRISES STAND IS NOT A VALID NUMBER. PLEASE
 PROVIDE THE CORRECT NUMBER AND SUBMIT THE PRODUCT
 APPROVAL WITH ALL APPLICABLE INSTALLATION DETAILS,
 NOTES, DESIGN PRESSURES, FASTENERS ETC. MARKED UP BY
 THE EOR.
  
 11) M7.1: SHOW IN THE CONTROL DIAGRAMS THE LOCATIONS OF
 THE DUCT SMOKE DETECTORS REQUIRED IN THE RETURN AIR
 SYSTEMS- SECTION 606.2.1.
  
 12) M2.1- 2.2, 2.3, & 2.4: SHOW THE LOCATIONS OF CO2
 SENSORS WHERE REQUIRED BY SECTION C403.2.5.1 AND IN
 ACCORDANCE WITH THE CONTROL DIAGRAMS ON M7.1.
  
 13) PROVIDE CHILLER PIPING AND PIPING INSULATION
 SPECIFICATIONS AND INSTALLATION, SUPPORT, AND HANGING
 DETAILS.
  
 14) CLEAR ACCESS TO THE ABOVE CEILING VAV BOXES AND
 EXHAUST FANS IS REQUIRED. SHOW THE LOCATIONS OF ANY
 REQUIRED ACCESS PANELS AND PROVIDE CONSTRUCTION
 DETAILS- SECTION 306.1.
  
 15) SHEET FG0.1: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 16) FG1.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED WATER HEATERS, AND PROVIDE COMBUSTION AIR
 CALCULATIONS AND VENTING PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  