| 2018-01-05 08:38:39 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| | EXISTING BUILDING CODES |
| | PERMIT #17110860 |
| | 1/4/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT |
| | AS REQUIRED BY SECTION C101.4.3 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 2) M1.3: PROVIDE A SCOPE OF WORK FOR THE CHILLER, |
| | PUMPS, AND ALL OTHER ASSOCIATED EQUIPMENT- EXISTING TO |
| | REMAIN? PROVIDE A SYMBOL ON THE PLAN THAT INDICATES THE |
| | POINT OF DEMO FOR THE EXISTING CHILLER PIPING. M4.1: |
| | PROVIDE EQUIPMENT SCHEDULES FOR THE CHILLER, PUMPS ETC. |
| | |
| | 3) SHEETS A-101, M1.3 & M2.1: THE GOLF CART STORAGE |
| | AREA IS CLASSIFIED AS A PARKING GARAGE AND REQUIRES AN |
| | EXHAUST VENTILATION SYSTEM IN COMPLIANCE WITH SECTION |
| | 404.1 FBC-14 MECHANICAL. PLEASE CLARIFY IF THERE IS AN |
| | EXISTING SYSTEM THAT IS IN COMPLIANCE, OR REVISE THE |
| | PLANS TO SHOW ALL PROPOSED ALTERATIONS AND NEW |
| | INSTALLATIONS. |
| | |
| | 4) SHEETS A-101, M1.3, & M2.1: PLEASE IDENTIFY ALL |
| | ROOMS AND SPACES ON THE MECHANICAL PLANS AS THEY ARE |
| | SHOWN ON THE ARCHITECTURAL PLANS. CLARIFY IF ANY OF THE |
| | ROOMS ARE USED FOR GOLF CART BATTERY STORAGE AND/OR |
| | BATTERY RECHARGING. PROVIDE EXHAUST VENTILATION SYSTEMS |
| | AND CALCULATIONS WHERE REQUIRED BY SECTION 502. |
| | |
| | 5) M4.1: PLEASE INCLUDE EXHAUST VENTILATION |
| | CALCULATIONS IN THE VENTILATION SCHEDULE. INDICATE THE |
| | REQUIRED AND PROVIDED CFMS OF EXHAUST FOR EACH LOCKER |
| | ROOM, BATHROOM, JANITORS CLOSETS, STORAGE ROOMS ETC. |
| | |
| | 6) M4.1: SECTION 403.3.2.3.3 NOTED UNDER THE |
| | VENTILATION SCHEDULE DOES NOT EXIST IN THE FBC-14 FIFTH |
| | EDITION MECHANICAL CODE- PLEASE CORRECT AND CLARIFY |
| | WHAT THE 0.5 DIVERSITY FACTOR IS AND HOW IT IS |
| | APPLICABLE TO THE PROPOSED PROJECT. |
| | |
| | 7) M2.5: INDICATE HOW ACCESS TO AHU'S 1-8A & 1-8B WILL |
| | BE PROVIDED- SECTION 306.5. |
| | |
| | 8) M2.5: THE CONDENSATE PIPING SUPPORTS SHALL BE SPACED |
| | MINIMUM 4' APART PER TABLE 305.4. |
| | |
| | 9) M2.5 & M5.1: PROVIDE THE SITE SPECIFIC WIND LOAD |
| | DESIGN CRITERIA FOR INSTALLATION OF THE ROOF TOP |
| | SUPPORTS AND EQUIPMENT- SECTION 1609 FBC-14 BUILDING. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE THYBAR |
| | CURB WITH SHOP DRAWING APPROVAL STAMP BY THE EOR. |
| | CLARIFY IF THE RTU ATTACHMENT DETAILS ON M2.1 ARE |
| | APPLICABLE TO ALL THE ROOFTOP UNITS INCLUDING THE AHU'S |
| | AND OAU'S, AND |
| | |
| | PROVIDE ATTACHMENT AND ANCHORING DETAILS FOR THE |
| | ROOFTOP DUCTWORK- SECTION 301.15. |
| | |
| | 10) M2.5: THE FLORIDA PRODUCT APPROVAL #3203.1 FOR THE |
| | RM ENTERPRISES STAND IS NOT A VALID NUMBER. PLEASE |
| | PROVIDE THE CORRECT NUMBER AND SUBMIT THE PRODUCT |
| | APPROVAL WITH ALL APPLICABLE INSTALLATION DETAILS, |
| | NOTES, DESIGN PRESSURES, FASTENERS ETC. MARKED UP BY |
| | THE EOR. |
| | |
| | 11) M7.1: SHOW IN THE CONTROL DIAGRAMS THE LOCATIONS OF |
| | THE DUCT SMOKE DETECTORS REQUIRED IN THE RETURN AIR |
| | SYSTEMS- SECTION 606.2.1. |
| | |
| | 12) M2.1- 2.2, 2.3, & 2.4: SHOW THE LOCATIONS OF CO2 |
| | SENSORS WHERE REQUIRED BY SECTION C403.2.5.1 AND IN |
| | ACCORDANCE WITH THE CONTROL DIAGRAMS ON M7.1. |
| | |
| | 13) PROVIDE CHILLER PIPING AND PIPING INSULATION |
| | SPECIFICATIONS AND INSTALLATION, SUPPORT, AND HANGING |
| | DETAILS. |
| | |
| | 14) CLEAR ACCESS TO THE ABOVE CEILING VAV BOXES AND |
| | EXHAUST FANS IS REQUIRED. SHOW THE LOCATIONS OF ANY |
| | REQUIRED ACCESS PANELS AND PROVIDE CONSTRUCTION |
| | DETAILS- SECTION 306.1. |
| | |
| | 15) SHEET FG0.1: PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE COOKING APPLIANCES- SECTION 304 FBC-14 FUEL |
| | GAS. |
| | |
| | 16) FG1.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS-FIRED WATER HEATERS, AND PROVIDE COMBUSTION AIR |
| | CALCULATIONS AND VENTING PLANS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |