| 2018-01-17 12:17:46 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. PROVIDE ELEVATION PLAN SHOWING LOCATION OF COCENTRIC |
| | VENT TERMINAL WITH DIMENSIONS TO OPENINGS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. FG2.0 HAS GAS LOGS SHOWN ON PLAN WITH DIFFERENT |
| | BTU LOADS THESE ARE NOT SHOWN ON ANY FLOOR PLAN PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. SHT. FG0.1 THE PROPANE GAS PIPING SIZING LIST |
| | TABLES FOR NATURAL GAS PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 4. SHT. FG0.1 THE PROPANE GAS PIPE SIZING CHART IS |
| | CONFUSING THEY LIST FIRE PITS AND FIRE PLACES THAT ARE |
| | NOT SHOWN ON PLAN. UNDER AREAS SERVED IT LIST METER TO |
| | BUILDING INTERIOR, EXISTING METER AND GWH REG. THE PLAN |
| | SHOWS PROPANE WHAT ARE THESE CHARTS FOR PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. FG 3.1 TH E GAS ISOMETRIC APPEARS THAT IT DID |
| | NOT LOAD PROPERLY I CAN NOR READ IT A COMPREHENSIVE GAS |
| | REVIEW NOT NOT BE DONE AT THIS TIME. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |