Plan Review Notes
Plan Review Notes For Permit 17110860
Permit Number 17110860
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-11-29 08:10:211901 VILLAGE BOULEVARD - CLUBHOUSE
 PERMIT #17110860
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: TEMPORARY CONSTRUCTION TRAILERS OR MODULAR
 BUILDINGS WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET G-101:
 INSUFFICIENT QUANTITY OF ILLUMITED EXIT SIGNS PROVIDED
 THROUGHOUT MAIN LEVEL. FOR EXAMPLE ONLY A SINGLE EXIT
 SIGN IS PROVIDED IN ASSEMBLY ROOMS #2004, #2048, AND
 #2087 TO NAME A FEW. COORDINATE ADDITIONAL EXIT SIGNAGE
 WITH ELECTRICAL PLANS.
  
 THE SOUTH EXIT SIGN IN ASSEMBLY ROOM #2023 DIRECTS
 OCCUPANTS TO A DOUBLE EGRESS DOOR THAT IS SWINGING
 AGAINST THE PATH OF TRAVEL. PER SECTION 7.2.1.4.2, DOOR
 IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
 FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
  
 SEVERAL CHAIRS AND TABLES ARE IMPEDING A DIRECT EXIT
 ACCESS PATH TO THE EXIT DOORS.
  
 EXIT DOORS LEADING TO EXTERIOR STAIR #2065 INDICATE A
 OCCUPANT LOAD CAPACITY OF 165 AND 330 PERSONS (495
 TOTAL PERSONS); HOWEVER, THE EXIT STAIR ONLY HAS A
 WIDTH OF APPROXIMATELY 5 FEET THAT WOULD LIMIT THE
 EGRESS CAPACITY TO ROUGHLY 200 PERSONS. THE SAME
 SITUATION OCCURS AT EXTERIOR STAIR #2021.
  
 NO OCCUPANT LOAD PROVIDED FOR ASSEMBLY #2003 AND #2063.
  
 OCCUPANT LOAD FACTOR FOR KITCHEN AND SUPPORT STAFF IS
 100 SQUARE FEET PER PERSON PER NFPA 101. PLANS INDICATE
 AN OCCUPANT LOAD FACTOR OF 200 SQUARE FEET PERSON.
  
 SHEET A-801: THE DOOR SCHEDULE INFORMATION IS
 INCOMPLETE (NO DOOR NOTES, HARDWARE, ETC.)
  
 SHEET M2.1: GOLF CART STORAGE DOES NOT APPEAR TO BE
 VENTILATED. HOW WILL THE POSSIBLE HYDROGEN OFF-GASSING
 FROM THE GOLF CART BATTERIES BE MITIGATED?
  
 SHEET E2.1: NO NEW OR EXISTING EMERGENCY LIGHTING OR
 EXIT SIGNAGE SHOWN.
  
 SHEET E2.2: PLEASE CLEARLY INDICATE WHICH LIGHTING
 FIXTURES ARE EMERGENCY LIGHTS. ENSURE EMERGENCY
 LIGHTING PROVIDED FOR EXTERIOR EGRESS STAIRS.
  
 SHEET FA1.2:
 FIRE ALARM SYSTEM UTILIZING HORN-STROBE NOTIFICATION
 APPLIANCES. PER SECTION 12.3.4.3.3, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 PROVIDE FIRE ALARM NOTIFICATION APPLIANCES IN THE
 KITCHEN COLD STORAGE AREAS (FREEZERS).
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  