| 2018-05-27 16:05:14 | ****PROVISOS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | A. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA; FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT |
| | APPLICATION 1979 FIRMS + 1' FREEBOARD; MINIMUM |
| | ELEVATION = 8.0' NGVD29, PROPOSED LOWEST FINISHED FLOOR |
| | ELEVATION = 9.0' NGVD29 |
| | A "CONSTRUCTION DRAWING" ELEVATION CERTIFICATE IS |
| | RECOMMENDED AT THIS TIME TO AVOID FUTURE DELAYS |
| | (CORRECTIONS, IF APPLICABLE, WILL NOT DELAY PERMIT |
| | ISSUANCE) |
| | A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE |
| | OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE |
| | POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW |
| | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS |
| | REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR |
| | TCO. |
| | |
| | B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| | FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| | SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| | PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| | STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| | REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| | AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| | PRESSURES SHOWN ON SHEET S0.0.5) |
| | |
| | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | D. PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A |
| | PDF VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL. |
| | |
| | E. AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED |
| | PRIOR TO C.O. |
| | |
| | F. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE |
| | SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE |
| | ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED |
| | PRIOR TO CONCRETE POUR. |
| | |
| | G. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS |
| | REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION. |
| | |
| | |