| 2017-12-18 13:28:51 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED, |
| | FIRST FLOOR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE RATIO |
| | AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT SHALL BE |
| | 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1 |
| | |
| | 2. SHAT. LS.1.1 UNDER THE PLUMBING FIXTURES REQUIRED, |
| | SECOND FLOORR TERRACE A-2 YOU HAVE FOR YOUR FIXTURE |
| | RATIO AS 1 PER 125 FOR MEN AND 1 PER 65 FOR WOMEN IT |
| | SHALL BE 1 PER 75 FOR BOTH SEXES. PER FBC PL TABLE |
| | 403.1 |
| | |
| | 3. SHT. LS .1.1 WHAT WILL THE ROOF TERRACE BE USED FOR |
| | IF IT IS USED FOR THE RESTAURANT PATRONS FOR DINNING IT |
| | SHALL BE CONSIDERED AN A-2 WITH A FIXTURE RATIO OF 1 |
| | PER 75 FOR BOTH SEXES. PER FBC PL TABLE 403.1 |
| | |
| | 4. SHT LS .1.1 FOR THE A-2 RESTAURANT OCCUPANCY A WATER |
| | FOUNTAIN IS NOT REQUIRED BUT FOR THE BUSINESS OR |
| | MERCANTILE OCCUPANCY'S WITH A OCCUPANT LOAD OVER 15 A |
| | WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE 403.1 |
| | |
| | 5. PLEASE PROVIDE FIXTURE COUNT FOR THE OCCUPANTS OF |
| | THE PARK NEXT TO RESTAURANT AND THE STANDARD THAT IT |
| | WAS DESIGNED UNDER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT LS .1.2 SYSTEM NO-C-AJ-1014 PART OF THE TEXT IS |
| | CUT OFF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. PROVIDE DETAIL WITH A SYSTEM DESIGNED FOR PLASTIC |
| | PIPE LARGE THAN 2". PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. A2-2-2 DETAIL PLEASE SHOW CLEAR FLOOR SPACE FOR |
| | WATER CLOSETS. PER FBC ACC 604.3.1 |
| | |
| | 9. SHT. A2-2-2 LABEL ALL CLEAR FLOR SPACES WITH |
| | DIMENSIONS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10.SHT. A2-2-2 THE GRAB BARS SHALL BE MEASURE FROM THE |
| | GRIPPING SURFACE TI FINISHED FLOOR. PER FBC ACC 609.4 |
| | |
| | 11. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | |
| | 12. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 604.4 SEATS. |
| | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | |
| | 13. SHT. A2-2-2 PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 14. SHT. A8-2-1 DETAIL #3 PLEASE SHOW PLEASE SHOW HOW |
| | THE-ROOF DRAIN WILL BE SECURED TO STRUCTURAL SLAB. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 15. SHT. P2.1.1 PROVIDE NOTE ON PLAN OR SHOW ON RISER |
| | COMPLIANCE WITH FBC PL 416.5 TEMPERED WATER FOR PUBLIC |
| | HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THEOUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 16. HOW WILL THE FUTURE CAPPED SANITARY LINE BE |
| | LOCATED-UNDER THE SLAB. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 17. SHT. P3.2.1 PLEASE SHOW DFU LOAD ON SANITARY |
| | ISOMETRIC. PER FBC PL 710.1 AND TABLE 710.1(1) |
| | |
| | 18. SHT. P3.3.1 THE PIPE SIZE IS MISSING PLEASE CLARIFY |
| | PER WPB AMEND TO FBC 107.2.1 |
| | A) THE BRANCH FROM SECOND FLOOR TROUGH DRAIN |
| | B) THE BRANCH FROM THR RISER CONNECTING TROUGH DRAINS |
| | |
| | 19. P3.3.1 SQFT IS MISSING ON BRANCH CONNECTING THE |
| | ROOF TERRACE TRENCH DRAIN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 20. PROVIDE SIZING CALCULATIONS FROM SCHEIR |
| | MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 21. SHT. P3.3.1 THE 4" BRANCH CONNECTING THR TRENCH |
| | DRAIN-AND A + B STACKS FROM THE ROOF TERRACE IS |
| | UNDERSIZED PER FBC PL TABLE 1106.3 |
| | |
| | 22. SHT. P3.3.1 SHOW SQFT ON OVERFLOW PIPING. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 23. SHT. P3.3.1 THE 6" HORIZONTAL OVERFLOW DRAIN PIPE |
| | IS UNDERSIZED PER FBC PL TABLE 1106.3 |
| | |
| | 24. SHT. P3.3.1 THE SECOND SECTION OF 8" HORIZONTAL |
| | DRAIN PIPE WITH 12796 SQFT IS UNDERSIZED PER FBC PL |
| | TABLE 1106.3 |
| | |
| | 25. SHT. P3.3.1 WHAT LEVEL IS THE TRENCH DRAIN THAT IS |
| | LABELED WITH 350 SQFT PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 26. SHT. P4.1.1 A DOUBLE SANITARY TEE CAN NOT BE USED |
| | AS A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR |
| | A TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT. |
| | SEE STANDARD DETAIL GS 7 OR GS 7.1 |
| | |
| | 27. P4.1.1 MIAMI DADE CODES DO NOT APPLY TO THIS |
| | PROJECT PLEASE REMOVE ANY REFERENCES FROM PLAN. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 28. P4.2.1 DETAIL WITH SPACING OF PIPE HANGERS DOES NOT |
| | COMPLY WITH FBC PL TABLE 308.5 PLEASE CLARIFY |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |