| 2017-12-01 08:57:27 | 1ST REVIEW FBC-2014 MECHANICAL /ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17110857 |
| | 12/1/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | PLEASE ADDRESS THE FOLLOWING COMMENTS. |
| | |
| | 1) SHEETS M1.1.1 & M1.2.1: WHAT STANDARD OR APPROVED |
| | CALCULATION PROCEDURE WAS USED TO DETERMINE THE AMOUNT |
| | OF COOLING PER SQUARE FOOT, AND THE 1ST AND 2ND FLOOR |
| | AC SYSTEM SIZES? PLEASE SHOW COMPLIANCE WITH SECTION |
| | C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | C403.2.1 CALCULATION OF HEATING AND COOLING LOADS. |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND |
| | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD |
| | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY |
| | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE |
| | WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK. |
| | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN |
| | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE |
| | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| | |
| | EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A |
| | REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF |
| | SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE |
| | BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING |
| | CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE |
| | FOLLOWING (BY ZONE): |
| | |
| | 1. PROJECT NAME/OWNER |
| | |
| | 2. PROJECT ADDRESS |
| | |
| | 3. AREA IN SQUARE FEET |
| | |
| | 4. SIZING METHOD USED |
| | |
| | 5. OUTDOOR DRY BULB USE |
| | |
| | 6. INDOOR DRY BULB |
| | |
| | 7. OUTDOOR WET BULB USED |
| | |
| | 8. GRAINS WATER (DIFFERENCE) |
| | |
| | 9. TOTAL SENSIBLE GAIN |
| | |
| | 10. TOTAL LATENT GAIN |
| | |
| | 11. RELATIVE HUMIDITY |
| | |
| | 12. TOTAL COOLING REQUIRED WITH OUTSIDE AIR |
| | |
| | 13. TOTAL HEATING REQUIRED WITH OUTSIDE AIR |
| | |
| | 2) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| | IN ACCORDANCE WITH SECTION C408.2. PLEASE SUBMIT A |
| | COMMISSIONING PLAN IN COMPLIANCE WITH SECTION C408.2.1. |
| | |
| | 3) A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR |
| | SYSTEMS OF THE 5-TON RTU-1 SYSTEM PER SECTION 606.2.1. |
| | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS |
| | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 4) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE/SMOKE |
| | DAMPERS AND SUBMIT PRODUCT DATA AND SPECIFICATIONS |
| | SHEETS. |
| | |
| | 5) M5.01: NOTE 4 UNDER THE EQUIPMENT SUPPORT CURB |
| | DETAIL APPEARS TO INDICATE THAT THE CURB AND RTU |
| | INSTALLATION WILL BE DESIGNED BY A STRUCTURAL ENGINEER. |
| | IT ALSO REFERENCES DWG. S3.300 WHICH WAS NOT UPLOADED |
| | WITH THE PLANS SET. PLEASE PROVIDE SITE SPECIFIC |
| | ENGINEERING FOR INSTALLATION OF RTU-1 IN ACCORDANCE |
| | WITH SECTION 1609 FBC-14 BUILDING. |
| | |
| | 6) PROVIDE A LIST OF DEFERRED SUBMITTALS. |
| | |
| | DEFERRED SUBMITTALS |
| | |
| | 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | 2) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | FAC RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |