Plan Review Notes
Plan Review Notes For Permit 17110812
Permit Number 17110812
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-30 07:41:511ST REVIEW FBC-2014 MECHANICAL
 REVISION #17110812
 MASTER PERMIT #16010290
 11/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 REQUIRES A SMOKE DETECTOR IN THE RETURN AIR SYSTEM OF
 AHU-2- SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION
 CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS
 INDICATE THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER
 2000 CFMS OF SUPPLY AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER