| Plan Review Notes For Permit 17110812 |
| Permit Number |
17110812 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-30 07:41:51 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #17110812 | | | MASTER PERMIT #16010290 | | | 11/30/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT | | | REQUIRES A SMOKE DETECTOR IN THE RETURN AIR SYSTEM OF | | | AHU-2- SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION | | | CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS | | | INDICATE THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER | | | 2000 CFMS OF SUPPLY AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|