Plan Review Notes
Plan Review Notes For Permit 17110812
Permit Number 17110812
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-07 16:25:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A DISCREPANCY EXIST FOR PANEL B1. THE PANEL SCHEDULE
 STATES THAT IT IS SINGLE PHASE, BUT THE FEEDERS TO THE
 PANEL ARE FOR 3 PHASE, AS WELL AS THE BREAKER FEEDING
 THIS PANEL. CLARIFY AND/OR CORRECT. FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL B. PHASE
 B OF THE LOAD CALC SHOWS RECEPTACLE LOADS, WHICH WOULD
 NOT BE ON THE HIGH LEG OF THE SYSTEM. NEC 220; FBC
 107.2.1
 3. FIRST FLOOR POWER PLAN SHOWS A SHUNT TRIP INSTALLED
 ADJACENT TO THE METER CAN, BUT THE RISER SHOWS THIS AS
 A FUTURE INSTALLMENT. CLARIFY AND/OR CORRECT. FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  