| 2017-12-21 07:42:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO PANEL. |
| | SHOW GEC SIZE AND SYSTEM. DOES THIS HAVE ITS OWN |
| | SERVICE, OR FED FROM SOMEWHERE ELSE? PROVIDE DETAILS. |
| | FBC 107.2.1; NEC 215.5, 230, 250.50, 250.94, 408.30 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| | 3. PROVIDE AUTOMATIC LIGHTING CONTROLS REQUIRED PER |
| | ENERGY CODE. "LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN |
| | OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION |
| | OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL |
| | TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN |
| | OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME |
| | SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE |
| | CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING |
| | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 |
| | HOURS." FBC EC 405.2.4 |
| | |
| | A COMPLETE REVIEW COULD NOT BE COMPLETED AT THIS TIME |
| | DUE TO LACK OF INFORMATION. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |