2018-04-02 14:43:30****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 AZOLA TRASH COMPACTOR 17110789
  
 SECOND REVIEW:
  
 NEW COMMENTS:
  
 A) THIS APPLICATION IS FOR A TRASH ENCLOSURE AND
 COMPACTOR. A COMPLETE SET OF CIVIL PLANS HAVE BEEN
 SUBMITTED ALONG WITH THE BUS ENCLOSURE PLANS. THE
 TRANSMITTLE LETTER ATTACHED IS FOR THE BUS ENCLOSURE.
  
 B) NEW COMMENT: THE ADDRESSING ON THE RESUBMITTAL HAS
 CHANGED.
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
  
 C) PRIVATE PROVIDER:
 THERE IS A NOTE IN OUR SYSTEM REGARDING PRIVATE
 PROVIDER INSPECTIONS. IF YOU ELECT TO DO THIS WE WILL
 NEED 3 SETS OF PLANS FOR REVIEW. ADDITIONALLY WE WILL
 NEED AN APPLICATION FOR PRIVATE PROVIDER INSPECTIONS
 ALONG WITH THE SUPPORTING DOCUMENTS.
 IF YOU NEED THIS APPLICATION CONTACT ME AND I CAN EMAIL
 IT TO YOU. NOTE: IF YOU DECIDE TO GO WITH PRIVATE
 PROVIDER IT COULD TAKE SEVERAL DAYS TO PROCESS SINCE I
 REVIEW IT FIRST
 AND THEN IT NEEDS APPROVAL FROM THE BUILDING OFFICIAL.
  
 D) NEW COMMENT:
  
 REPEAT REVIEWS FOR THE SAME COMMENTS.
  
 F.S. 553.80 (2) (B)
 (B) WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 FIRST REVIEW
  
  
 1. THIS PROPERTY IS IN FLOOD ZONE A.
  
 FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016, AFTER
 OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE BOARD WILL
 BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 FBC 1612.1 GENERAL.
  
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 AFTER OCTOBER 5TH 2017 THE NGVD HAS BEEN UPDATED TO
 NAVD88. PLEASE UPDATE THE PLANS TO REFLECT THIS AS WELL
 AS THE NEW FREE BOARD.
  
 FBC 1612.4 DESIGN AND CONSTRUCTION.
  
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  
 2. STRUCTURAL CALCULATIONS:
  
 (A) CODE REFERENCES SHOWN ARE FOR IBC 2015. AT TIME OF
 SUBMITTING THE CURRENT CODE IS FBC 2014 5TH EDITION.
  
 (B) BASIC WIND SPEED SHOWN IS 165.00 MPH. SEE FBC
 FIGURE 1609C AND FBC 1609.3 BASIC WIND SPEED.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  
  
  