| 2018-03-14 10:09:23 | PERMIT # 17110788 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 2ND REVIEW COMMENTS: |
| | |
| | REPEAT COMMENT: |
| | 1) SHEET M-5.3: GARAGE EXHAUST FANS (150 CFM) APPEAR |
| | TOO SMALL TO VENTILATE THE GARAGES IN ACCORDANCE WITH |
| | NFPA 88A. PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED |
| | PARKING STRUCTURES SHALL BE VENTILATED BY A MECHANICAL |
| | SYSTEM CAPABLE OF PROVIDING A MINIMUM OF 300 L/MIN PER |
| | M2 OF FLOOR AREA (1 FT3/MIN PER FT2 OF FLOOR AREA).... |
| | |
| | PER NFPA 1, 101, AND 88A, A PARKING STRUCTURE IS |
| | DEFINED AS A BUILDING, STRUCTURE, OR PORTION THEREOF |
| | USED FOR THE PARKING, STORAGE, OR BOTH, OF MOTOR |
| | VEHICLES. |
| | YOUR CLAIM THAT THIS DOES NOT APPLY BECAUSE PARKING IS |
| | FOR RESIDENTIAL USE, DOES NOT APPLY HERE, AS THE |
| | PRIMARY USE FOR THE BUILDING/OCCUPANCY IS APARTMENT AND |
| | THE GARAGES WILL BE USED FOR "PARKING, STORAGE, OR |
| | BOTH, OF MOTOR VEHICLES". THE CODE DOES NOT PROVIDE AN |
| | EXCEPTIONS FOR APARTMENT BUILDINGS. |
| | |
| | |
| | NEW COMMENT: |
| | 2) SHEET A-2.1: ELECTRIC GRILLS ARE SHOWN ON THE PLAN |
| | FOR USE BY TENANTS AT THE PAVILION. NFPA 1 STATES THAT |
| | COOKING DEVICES (GRILLS) MAY NOT BE UNDER ANY |
| | OVERHANGING PORTIONS OR WITHIN 10 FEET OF ANY |
| | STRUCTURE, UNLESS IT IS INSTALLED PER THE |
| | MANUFACTURER'S INSTRUCTIONS. PLEASE PROVIDE THE |
| | MANUFACTURER'S SPECIFICATIONS/DATA SHEETS FOR REVIEW. |
| | |
| | NFPA 1: 10.11.6 COOKING EQUIPMENT. |
| | 10.11.6.1 |
| | FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, NO |
| | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR |
| | COOKING, HEATING, OR ANY OTHER PURPOSE SHALL BE USED OR |
| | KINDLED ON ANY BALCONY, UNDER ANY OVERHANGING PORTION, |
| | OR WITHIN 10 FT (3 M) OF ANY STRUCTURE. |
| | 10.11.6.3 * |
| | LISTED EQUIPMENT PERMANENTLY INSTALLED IN ACCORDANCE |
| | WITH ITS LISTING, APPLICABLE CODES, AND MANUFACTURER'S |
| | INSTRUCTIONS SHALL BE PERMITTED. |
| | |
| | |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4751 |
| | |