| 2018-03-12 10:04:29 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2015 5TH EDITION |
| | AZOLA WEST PALM BEACH 17110788 |
| | |
| | SECOND REVIEW: |
| | |
| | 1. OK ACKNOWLEDGED. |
| | ART IN PUBLIC PLACES. |
| | |
| | 2. NOT ADDRESSED. ELEVATION CERTIFICATE NOT PROVIDED |
| | FOR REVIEW. |
| | FLOOD ZONE CERTIFICATES |
| | FBC 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. |
| | AFTER OCTOBER 11, 2017 AN ADDITIONAL ONE FOOT OF FREE |
| | BOARD WILL BE REQUIRED OR (2) FREE BOARD DESIGN FLOOD |
| | ELEVATION. |
| | NOTE: EFFECTIVE OCTOBER 5, 2017 THE FLOOD ZONE MAPS |
| | HAVE BEEN REVISED. PLEASE UPDATE THE SURVEY AND CIVIL |
| | DRAWINGS TO REFLECT THE NEW FLOOD ZONE AND COMPLIANCE |
| | WITH NAV 88. |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | |
| | (A) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | |
| | 3. NOT PROVIDED. |
| | |
| | PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 4. THRESHOLD NOTES UNDER SEPARATE THRESHOLD REVIEW |
| | STOP. |
| | |
| | 5. OK DEFFERED SUBMITALS LISTED |
| | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6. OK ADDRESSED. CONSTRUCTION TRAILERS |
| | |
| | 7. OK ADDRESSED. |
| | PROVIDE AN EVALUATION REPORT FOR SPRAY INSULATION SHOWN |
| | ON PAGE A 6.1 KEY NOTE 73 AND FOR RIGID POLY ISO |
| | INSULATED BOARD SHOWN ON PAGE A 3.3 KEYNOTE 42. FBC |
| | 2603.5.4 |
| | |
| | 8. OK DEFFERED SUBMITALS LISTED |
| | TRUSS ENGINEERING APPROVED BY THE DESIGNER OF RECORD. |
| | |
| | |
| | 9. OK ADRESSED. |
| | WELDED OR BOLTED CONNECTIONS |
| | |
| | 10. OK ADRESSED. |
| | SLIDING GLASS DOOR THRESHOLD. |
| | |
| | 11. OK ADRESSED. |
| | PAGE A 9.1 DETAIL 1. FRAMING IS SHOWN AS 24 INCHES ON |
| | CENTER. CHECK MANUFACTURER'S SPECIFICATION ON |
| | CEMENTITIOUS BOARD. MANY REQUIRE FRAMING AT 16 INCHES |
| | ON CENTER. |
| | |
| | 12. OK ADRESSED. |
| | THE SCALE OF 3 INCHES EQUALS 1 FOOT IS NOT ACCURATE |
| | PLEASE SEE PAGES A 8.1, A 8.2, A 8.3 AND A 8.4. |
| | |
| | 13. OK ADRESSED. |
| | DETAIL F ON PAGE S 3.3.3 SPECIAL GIRDER TRUSS |
| | CONNECTION DETAIL 1, 2, 3 AND 4 ARE MISSING |
| | MEASUREMENTS. |
| | |
| | 14. OK ADRESSED. |
| | ON PAGE A 7.3 ELEVATOR NOTE. ELEVATOR SHALL COMPLY WITH |
| | FBC 708.14 WAS NOT FOUND. PLEASE UPDATE THIS CODE |
| | SECTION. |
| | |
| | 15. OK ADRESSED. |
| | PAGE 8.2 DETAIL 17. PLEASE UPDATE CODE SECTION TO 2014 |
| | FBC 5TH EDITION. |
| | |
| | 16. NOT PROVIDED. |
| | PLEASE PROVIDE MANUFACTURE'S SPECIFICATIONS FOR |
| | BARBECUES USED. |
| | |
| | 17. NOT PROVIDED. |
| | SEE PAGE A 3.2 DETAIL 3. CUT SECTIONS 4.1 TO 5. THE |
| | FOAM OUTLOOKERS ARE OVER 40 FT. SEE ALSO DETAIL 4 AT |
| | CUT H FOR ANOTHER EXAMPLE. |
| | COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF EXTERIOR |
| | WALLS. SEE OUTLOOKERS USED AT GABLE ENDS AND DECORATIVE |
| | FOAM MEDALLIONS. |
| | |
| | FBC 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION. |
| | ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| | EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| | CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH |
| | THE FOLLOWING LIMITATIONS: 2. COMBUSTIBLE EXTERIOR WALL |
| | COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN |
| | HEIGHT ABOVE GRADE PLANE. |
| | |
| | 18. OK. ADDRESSED. |
| | VENT ON TOP OF ELEVATOR SHAFT RATING NOT SHOWN. |
| | |
| | 19. OK. ADDRESSED. |
| | CLARIFY VAPOR BARRIER THAT IS TO BE USED. IT VARIES |
| | FROM 6 MIL TO 10 MIL. SEE S 2.1.1.1, S 4.1.1.1, S 4.1.2 |
| | AND S 4.1.3 |
| | |
| | 20. OK. ADDRESSED. |
| | EXISTING 2 STORY BUILDING TO BE DEMOLISHED REQUIRES A |
| | SEPERATE DEMO PERMIT. FBC 105.1 |
| | |
| | 21. OK. ADDRESSED. |
| | PARKING DETAILS: PARKING LOT STRIPING DETAILS VARY FROM |
| | SINGLE TO DOUBLE STRIPING THROUGHOUT THE PLANS. WEST |
| | PALM BEACH PARKING LOT STRIPING IS DOUBLE STRIPING. A |
| | DETAIL IS AVAILABLE AT THIS DEPARTMENT. NOTE: FC |
| | 553.5041(6) HAS CHANGED REGARDING SIGNAGE. THE NEW |
| | MINIMUM HEIGHT IS 60 INCHES. |
| | |
| | 22. OK. ADDRESSED. A SEPARATE REVIEW STOP HAS BEEN |
| | ENTERED FOR IMPACT FEES |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |