| 2017-11-29 13:55:56 | 8230 OKEECHOBEE BOULEVARD - BUILDING #7 |
| | PERMIT #17110788 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET C5: PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH TO |
| | OPEN BOTH ENTRY AND EXIT GATES SIMULTANEOUSLY. |
| | |
| | SHEET A-2.1: ELECTRIC GRILLS: COOKING ON ELECTRIC |
| | GRILLS MAY RESULT IN THE PRODUCTION OF SMOKE LADEN |
| | VAPORS. PER NFPA 1 SECTION 50.2.1.1 COOKING EQUIPMENT |
| | USED IN PROCESSES PRODUCING SMOKE OR GREASE-LADEN |
| | VAPORS SHALL BE EQUIPPED WITH AN EXHAUST SYSTEM THAT |
| | COMPLIES WITH ALL THE EQUIPMENT AND PERFORMANCE |
| | REQUIREMENTS OF THIS CHAPTER. PER NFPA 1 SECTION |
| | 50.2.1.9 COOKING EQUIPMENT USED IN PAVILIONS, TENTS, OR |
| | ANY FORM OF ROOFED ENCLOSURE, SHALL COMPLY WITH NFPA 96 |
| | REQUIRING A KITCHEN EXHAUST SYSTEM AND UL300 FIRE HOOD |
| | SUPPRESSION SYSTEM. |
| | |
| | SHEET M-5.3: GARAGE EXHAUST FANS (150 CFM) APPEAR TOO |
| | SMALL TO VENTILATE THE GARAGES IN ACCORDANCE WITH NFPA |
| | 88A. PER NFPA 88 SECTION 5.3.2: ALL ENCLOSED PARKING |
| | STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM |
| | CAPABLE OF PROVIDING A MINIMUM OF 1 CFM PER 1 SF OF |
| | FLOOR AREA DURING HOURS OF NORMAL OPERATION. |
| | |
| | SHEET M-5.3: GARAGE EXHAUST FANS INDICATE A LIGHT |
| | SWITCH STARTER. THESE FANS WOULD NEED TO OPERATE |
| | CONTINUOUSLY OR BY A CO DETECTOR NOT A MANUAL SWITCH. |
| | |
| | SHEET FS-2C.2: PER NFPA 13, NO FIRE SPRINKLER |
| | PROTECTION PROVIDED IN COMBUSTIBLE CONCEALED SPACE |
| | ABOVE CEILING IN FITNESS CENTER AND COVERED PATIO. |
| | |