Plan Review Notes
Plan Review Notes For Permit 17110787
Permit Number 17110787
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-02 10:57:551ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. LS-0.0 UNDER APPLICABLE CODES THIS BUILDING
 SHALL COMPLY WITH FBC ACCESSIBILITY 5TH EDITION 2014
 NOT 2012. PLEASE CORRECT. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE LIST OCCUPANT LOAD FOR PLUMBING FIXTURE COUNT
 CALCULATION. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. A-2.2 UNDER THE DOOR SCHEDULE , DOOR GENERAL
 NOTES #1 IT REFERENCES THE 2010 CODE EDITION THIS
 PROJECT IS UNDER 2014 5TH EDITION.
 PLEASE CORRECT. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE SHOW THE CLEAR FLOOR SPACE REQUIRED FOR THE
 LAVATORY AND BREAK ROOM SINK IT SHALL COMPLY WITH FBC
 ACC 606.2
  
 5. LABEL THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR
 THE WATER CLOSET , LAVATORY AND BREAK ROOM SINK. . PER
 WPB AMEND TO FBC 107.2.1
  
 6. THE DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE
 EXCEPTIONS: 2. WHERE THE TOILET ROOM OR BATHING ROOM IS
 FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE.
  
 7. PLEASE PROVIDE A DETAIL SHOWING THE REQUIRED KNEE
 AND TOE CLEARANCE FOR THE VANITY IN THE BATHROOM. PER
 FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 8. THE BREAK ROOM SINK SHALL BE 34" MAX OFF THE
 FINISHED FLOOR TO THE RIM OF THE SINK THE DETAIL #5
 SHT. A-2.3 SHOWS 36" PLEASE CLARIFY . PER FBC ACC 606.3
  
 9. PLEASE PROVIDE CALCULATIONS FOR THE ROOF GUTTERS PER
 FBC PL TABLE 1106.6
  
 10. SHT. A-10.1 SHOWS DETAILS FOR A WATER FOUNTAIN,
 SHOWER, AND A TOILET COMPARTMENT THAT DOES NOT MATCH
 THE PLAN PLEASE REMOVE ANY DETAILS NOT PERTAINING TO
 THIS BUILDING. PER WPB AMEND TO FBC 107.2.1
  
 11. THE COFFEE BAR SHALL COMPLY WITH FBC ACC 227, 308
  
 12 . THE MEP SHEETS SHOW A OUTSIDE DOOR TO MECHANICAL
 ROOM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 13. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 14. A TRAP PRIMER IS REQUIRED FOR ALL FLOOR DRAINS. PER
 FBC PL 1002.4
  
 15. PROVIDE THE MANUFACTURE SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 16. PLEASE PLACE NOTE ON THE PLAN A SEPARATE PERMIT
 WILL BE REQUIRED FOR THE BACK FLOW DEVICES PER WPB
 UTILITIES DEPARTMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  