| 2017-12-15 16:29:08 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17110787 |
| | 12/15/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MLC-1: A SMOKE DETECTOR IS REQUIRED IN THE |
| | RETURN AIR SYSTEM OF AC-1 PER SECTION 606.2.1. PLEASE |
| | NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS |
| | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 2) MLC-1: PROVIDE THE FLEX DUCT SIZES. |
| | |
| | 3) MLC-1 & MLC-3: IT APPEARS THAT THE EF-1 SHOWN IN THE |
| | LEASING OFFICE AND IN THE VENTILATION SCHEDULE SHOULD |
| | HAVE BEEN LOCATED IN THE RESTROOM- SEE TABLE 403.3. |
| | |
| | 4) MLC-1 & MLC-3: IT APPEARS THAT NO O/A HAS BEEN |
| | CALCULATED AND PROVIDED FOR THE E- LOUNGE ROOM. |
| | ADDITIONALLY, THE PLAN SHOWS NO AC DISTRIBUTION TO THE |
| | ROOM-PLEASE CLARIFY. |
| | |
| | 5) MLC-1 & A-2.2: ADVISORY: A NON-COMBUSTIBLE DOOR FOR |
| | THE AC CLOSET WILL BE REQUIRED IF THE RETURN IS NOT |
| | DUCTED DIRECTLY TO THE AIR HANDLER- SEE SECTION |
| | C403.2.7.2 FBC-14 ENERGY CONSERVATION CODE, AND SECTION |
| | 602.2.1 FBC-14 MECHANICAL. |
| | |
| | 6) MLC-1: PROVIDE AN AUTOMATICALLY CONTROLLED SHUTOFF |
| | DAMPERS FOR THE O/A INTAKE- SECTION C403.2.4.4 FBC-14 |
| | ENERGY CONSERVATION. |
| | |
| | 7) MLC-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE CONDENSERS AND MOUNTING PAD- SEE |
| | SECTION 1609 FBC-14 BUILDING. |
| | |
| | 8) REQUIRED SUBMITTALS: |
| | |
| | FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE AC |
| | STANDS, AND THE AIR INTAKE AND EXHAUST OUTLET LOUVERS. |
| | DUCT SMOKE DETECTOR |
| | MOTORIZED DAMPER |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |