Plan Review Notes
Plan Review Notes For Permit 17110787
Permit Number 17110787
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-19 12:54:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 2. PANEL H SHOWS A GROUNDING ELECTRODE CONDUCTOR TYING
 INTO THE GROUNDING ELECTRODE SYSTEM. THE GROUNDING
 ELECTRODE CONDUCTORS ARE INSTALLED TO THE MAIN SERVICE
 ONLY. THIS IS NOT LABELED AS A MAIN, AND IS SHOWN BEING
 FED FROM THE 1200 AMP MAIN. CLARIFY AND PROVIDE
 CORRECTION AS NEEDED. NEC 230.2(E), 250.64
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 4. PANEL SCHEDULE FOR PANEL H SHOWS A 1/0 CONDUCTOR ON
 A 175 AMP BREAKER FEEDING THE ELEVATOR. PER CODE, A 1/0
 COPPER CONDUCTOR IS NOT RATED FOR 175 AMPS. PROVIDE
 CORRECTION. PROVIDE CORRECTION. NEC 310.15(B)(16),
 408.30
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. SPECIFY FEEDER SIZES TO THE INDIVIDUAL PANELS ON
 RISER DIAGRAM TO CORRESPOND TO THE VOLTAGE DROP
 REQUIREMENTS STATED ON SHEET E-4.0. FBC 107.2.1
 7. IT APPEARS THAT ALL UNITS IN THIS BUILDING WILL BE
 "A" OR "C" TYPE, BUT THE PLAN SHOWS PANEL SCHEDULES FOR
 "B" TYPE ALSO. REMOVE ANY INFORMATION NOT RELEVANT TO
 THIS PLAN. FBC 107.2.1
 8. SHEET E-4B.1, NOTE 9 IN ELECTRICAL NOTES AND NOTE 6
 IN GENERAL NOTES STATE THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11, WHICH IS NOT THE CORRECT CODE
 SECTION. PROVIDE CORRECTION. ALSO, NOTE 2 STATES
 RECEPTACLES WEATHER PROOF PER NEC 406.8, ALSO WRONG
 CODE SECTION. PROVIDE CORRECTION. NEC 406.9, 406.12;
 FBC 107.2.1
 9. SHEET E-4B.1, NOTE 7 IN GENERAL NOTES STATES THAT
 BREAKERS FEEDING AREAS LISTED IN 250.22 SHALL BE AFCI
 TYPE BREAKERS. CLARIFY WHY 250.22 IS RELATED TO THIS
 CODE REQUIREMENT. PER CODE: "ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION."
 PROVIDE CORRECTION. NEC 210.12
 10. PANEL SCHEDULE FOR PANEL A & C SHOWS THE WATER
 HEATER BREAKER AS A 30 AMP BREAKER. BASED ON THE LOAD
 OF A STANDARD 4500 WATT ELEMENT AT 208 VOLT, THE
 BREAKER SHOULD BE SIZED AT 25 AMP. PROVIDE CORRECTION.
 NEC 422.13
 11. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED, SUCH AS ELECTRIC ROOM,
 ELEVATOR CONTROL ROOM, FIRE ROOM, ETC. FBC EC 405.2.2,
 405.2.2.2
 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. THIS INCLUDES ELECTRIC ROOM AND
 ELEVATOR ROOM CU'S, WHICH ARE NOT CURRENTLY SHOWN ON
 PLAN. SHOW LOCATION OF UNITS AND CORRESPONDING
 RECEPTACLE. NEC 210.63; FBC 107.2.1
 13. FEEDERS FROM FPL TO 1200 AMP MAIN ARE TOO SMALL.
 PLANS SHOWS 4 SETS OF 300 KCMIL AL CONDUCTORS, WHICH
 ARE RATED FOR 920 AMPS. WIRE MUST BE SIZED EQUAL TO OR
 GREATER THAN THE MAIN BREAKER. PROVIDE CORRECTION. NEC
 240.4(C)
 14. UNIT C-1 DOES NOT SHOW THE REQUIRED GFCI RECEPTACLE
 WITHIN 3 FEET OF EACH BASIN IN THE MASTER BATH. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 15. IN UNIT C-1 THERE APPEARS TO BE A KITCHEN ISLAND.
 IF SO, PROVIDE THE REQUIRED GFCI RECEPTACLE. NEC
 210.52(C)(2)
 16. UNIT A-1, THE OUTLET OUTSIDE ON CIRCUIT 16 IS
 REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8, 406.9
 17. UNIT A-2, THE OUTLET OUTSIDE ON CIRCUIT 16 IS
 REQUIRED TO BE WEATHER PROOF AND GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 210.8, 406.9
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  