| Plan Review Notes For Permit 17110786 |
| Permit Number |
17110786 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-13 13:48:10 | MECHANICAL PROVISO: | | | | | | C402.4.5.1 FBC-14 ENERGY CONSERVATION: STAIRWAY AND | | | SHAFT VENTS. | | | STAIRWAY AND SHAFT VENTS SHALL BE PROVIDED WITH CLASS I | | | MOTORIZED DAMPERS WITH A MAXIMUM LEAKAGE RATE OF 4 | | | CFM/FT2 (20.3 L/S ? M2) AT 1.0 INCH WATER GAUGE (W.G.) | | | (249 PA) WHEN TESTED IN ACCORDANCE WITH AMCA 500D. | | | |
|