Plan Review Notes
Plan Review Notes For Permit 17110786
Permit Number 17110786
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-03-26 12:17:16PERMIT # 17110786
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 COMPLIANCE OF ALL ITEMS WILL BE VERIFIED IN THE FIELD.
 FAILURE TO COMPLY WITH FIRE CODE REQUIREMENTS WILL
 RESULT IN A FAILED INSPECTION.
  
 1) SHEET C5 - PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH
 TO ALLOW SIMULTANEOUS (ENTRY AND EXIT) GATE ACCESS TO
 EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
 NOTE WAS NOT FOUND ON SHEET AS INDICATED IN RESPONSE.
  
 2) COMPLIANCE OF CO DETECTOR PLACEMENT WILL BE VERIFIED
 IN THE FIELD.
  
 3) COMPLIANCE OF REQUIRED MECHANICAL VENTILATION FOR
 GARAGE UNITS, OF 1CFM PER 1SF OF FLOOR AREA, TO BE
 VERIFIED IN THE FIELD.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  