2018-04-23 12:46:31****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2015 5TH EDITION
  
 AZOLA WEST PALM BEACH 17110786 TYPE "B"
  
 SECOND REVIEW:
  
 2. BASE ON THE ELEVATION CERTIFICATES PROVIDED FOR
 BUILDING 4, 5 AND 6, THESE BUILDING ARE IN FLOOD ZONE
 X. THAT IS GOOD AND WILL ELIMINATE THE NEED FOR FURTHER
 ELEVATION CERTIFICATES FOR BEING IN A FLOOD ZONE.
  
 NOTE: THE ELEVATION CERTIFICATES PROVIDED SHALL CONTAIN
 THE SEAL OF THE SURVEYOR ON PAGE 2 SECTION D.
  
 PROVIDE 3 SETS FOR BUILDINGS 4, 5 AND 6.
  
 3. NOT ADDRESSED
  
 A. THE GEOTECHNICAL REPORT RECOMMENDATIONS ON 4.2
 RECOMMENDS THE BOTTOM OF FOOTING BE AT LEAST 16 INCHES
 BELOW GRADE. SEE DETAIL A /S 3.2.2 ONLY 12 INCHES IS
 PROVIDED.
  
 B. SEE ALSO FOOTING SCHEDULE ON S 3.2.1
  
 C. PROVIDE A SOILS EXPLORATION REPORT. FBC 1803 FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 4. THRESHOLD REVIEW MOVED TO THRESHOLD STOP.
  
 17. NOT ADDRESSED.
  
 SEE PAGE A 3.1 FOR EXAMPLE. ELEVATION KEY NOTES F1 AND
 F6 HAVE NOT BEEN UPDATED.
  
 COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF EXTERIOR
 WALLS. SEE OUTLOOKERS USED AT GABLE ENDS AND DECORATIVE
 FOAM MEDALLIONS.
  
 FBC 1406.2.1 TYPE I, II, III AND IV CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, COMPLYING WITH
 THE FOLLOWING LIMITATIONS: 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 18. PARTIALLY ADDRESSED.
  
 THE KEY OUTSTANDING ITEM IS THE 2 HOUR RATING OF THE
 HORIZONTAL DUCT USED. DUCTS LOCATED OUTSIDE THE
 HOISTWAY OR MACHINE ROOM ARE ENCLOSED BY CONSTRUCTION
 HAVING NOT LESS THAN THE FIRE-RESISTANCE RATING
 REQUIRED FOR THE HOISTWAY.
 FBC 3004.2 LOCATION OF VENTS.
  
 VENTS SHALL BE LOCATED AT THE TOP OF THE HOISTWAY AND
 SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR THROUGH
 NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH THE ELEVATOR
 MACHINE ROOM, PROVIDED THAT PORTIONS OF THE DUCTS
 LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES
 IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM)
 OF CLEARANCE ON ALL SIDES.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 _______________________________________________________
 __________________________
  
 PROVISOS AND DEFERRED SUBMITTALS:
  
 5. DEFERRED SUBMITTALS LISTED ON LS 0.0
 UNDERGROUND UTILITIES
 ROOF PRODUCT APPROVALS
 DOOR AND WINDOW SHOP DRAWINGS AND PRODUCT APPROVALS
 DRAINAGE SHOP DRAWINGS
 EXTERIOR FRAMING AND SHOP DRAWINGS.
 RAILING SHOP DRAWINGS
 TRUSS DRAWINGS
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9. WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 10. SLIDING GLASS DOOR THRESHOLD. SEE A 8.3 DETAIL 1.
 THE SILL RISER WILL INTERFERE WITH THE MAXIMUM
 THRESHOLD AND ALLOWABLE 4" STEP. SEE FAIR HOUSING ACT
 DESIGN MANUAL'S DETAIL ON PAGE 4.15.
 THE OWNER AS NEEDED WILL PROVIDE ADAPTABLE PORTABLE
 RAMPS. RAMPS WILL BE AVAILABLE IN THE MANAGEMENT OFFICE
 AT ALL TIMES.
  
  