| 2017-12-15 14:23:34 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17110779 |
| | 12/15/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE AC CALCULATIONS ARE INCORRECTLY IDENTIFYING THE |
| | PROJECT NAME AS BELLA VITA CLUBHOUSE. |
| | |
| | 2) THE SUBMITTED AC CALCULATIONS DO NOT MEET THE |
| | REQUIRED PROCEDURE FOR SYSTEM SIZING AS OUTLINED IN |
| | SECTION C407.5.2.3 ENERGY CONSERVATION- MULTIFAMILY |
| | RESIDENTIAL BUILDINGS: |
| | |
| | RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL |
| | BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME |
| | ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE |
| | THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR |
| | FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING |
| | THESE FEATURES. |
| | |
| | PLEASE SUBMIT REVISED CALCULATIONS. |
| | |
| | 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| | PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A |
| | COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| | DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE |
| | THAT A COPY OF THE COMMISSIONING REPORT SHALL BE |
| | SUBMITTED FOR REVIEW AT FINAL INSPECTION. |
| | |
| | 4) PROVIDE VENTILATION CALCULATIONS FOR THE APARTMENTS- |
| | TABLE 403.3. |
| | |
| | 5) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | STORAGE ROOMS, AND THE FIRE SERVICE ROOM- TABLE 403.3 |
| | |
| | 6) SHEETS M2B.1 & M5.3, PARKING GARAGES:THE EF-2 |
| | SCHEDULE INDICATES THE EXHAUST FANS WILL BE ACTIVATED |
| | BY THE LIGHT SWITCH. PLEASE SEE SECTIONS 404.1 AND |
| | 404.2 AND REVISE THE PLAN TO SHOW THE CORRECT SEQUENCE |
| | OF FAN OPERATION AND REQUIRED EXHAUST VENTILATION |
| | RATES. |
| | |
| | 7) M2B.1: A FIRE DAMPER IS REQUIRED FOR THE ELEVATOR |
| | SHAFT RELIEF AIR OPENING- SECTION 607.5.2. |
| | |
| | 8) PLEASE PROVIDE AN ENLARGED DETAIL OF THE ELEVATOR |
| | EXHAUST VENTILATION SYSTEM THAT PROVIDES EXHAUST DUCT |
| | AND DUCT SUPPORT DETAILS, AND THE EXHAUST DUCT RUN AND |
| | TERMIANTION LOCATION INCLUDING REQUIRED CLEARANCES PER |
| | SECTIO 501.3.1. |
| | |
| | 9) M4B.1 UNIT C-1: THE PRINT IN THE DRYER VENT CHART |
| | AND AT THE GREAT ROOM DIFFUSERS IS NOT LEGIBLE. |
| | |
| | 10) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE CONDENSERS AND STANDS- SEE SECTION |
| | 1609 FBC-14 BUILDING. |
| | |
| | 11) A5.1: THE DOOR SCHEDULE INDICATES THE AC CLOSET |
| | DOORS WILL BE PROVIDED WITH INTUMESCENT PAINT ON THE |
| | INTERIOR SIDE IN ORDER TO MEET COMPLIANCE WITH SECTION |
| | C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND SECTION |
| | 602.2.1 FBC-14 MECHANICAL. PLEASE NOTE THAT THE WPB |
| | BUILDING DEPARTMENT WILL NOT PERFORM INSPECTIONS ON THE |
| | DOORS, BUT WILL REQUIRE A LETTER FROM THE ENGINEER OF |
| | RECORD TO CERTIFY THE APPLICATION OF THE PAINT AND |
| | COMPLIANCE WITH THE AFOREMENTIONED CODE SECTIONS. |
| | |
| | 12) PROVIDE REFRIGERANT PIPING RISER DRAWINGS. |
| | |
| | 13) REQUIRED SUBMITTALS: |
| | |
| | FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE AC |
| | STANDS, AND THE AIR INTAKE AND EXHAUST OUTLET LOUVERS. |
| | RANGE HOODS |
| | DRYERS |
| | MOTORIZED DAMPERS |
| | FIRE DAMPERS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |