| 2017-11-28 16:00:01 | 8230 OKEECHOBEE BOULEVARD - BUILDING 4 | | | PERMIT #17110786 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET C5: PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH TO | | | OPEN BOTH ENTRY AND EXIT GATES SIMULTANEOUSLY. | | | | | | SHEET E-4B.1: CARBON MONOXIDE ALARM IS LOCATED MORE | | | THAN 10 FEET FROM THE BEDROOM DOORS. | | | | | | SHEET M-2B.1: GARAGE EXHAUST FANS (150 CFM) APPEAR TOO | | | SMALL TO VENTILATE THE GARAGES IN ACCORDANCE WITH NFPA | | | 88A. PER NFPA 88 SECTION 5.3.2: ALL ENCLOSED PARKING | | | STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM | | | CAPABLE OF PROVIDING A MINIMUM OF 1 CFM PER 1 SF OF | | | FLOOR AREA DURING HOURS OF NORMAL OPERATION. | | | | | | SHEET M-2B.1: GARAGE EXHAUST FANS INDICATE A LIGHT | | | SWITCH STARTER. THESE FANS WOULD NEED TO OPERATE | | | CONTINUOUSLY OR BY A CO DETECTOR NOT A MANUAL SWITCH. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|