2017-11-28 16:00:018230 OKEECHOBEE BOULEVARD - BUILDING 4
 PERMIT #17110786
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET C5: PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH TO
 OPEN BOTH ENTRY AND EXIT GATES SIMULTANEOUSLY.
  
 SHEET E-4B.1: CARBON MONOXIDE ALARM IS LOCATED MORE
 THAN 10 FEET FROM THE BEDROOM DOORS.
  
 SHEET M-2B.1: GARAGE EXHAUST FANS (150 CFM) APPEAR TOO
 SMALL TO VENTILATE THE GARAGES IN ACCORDANCE WITH NFPA
 88A. PER NFPA 88 SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1 CFM PER 1 SF OF
 FLOOR AREA DURING HOURS OF NORMAL OPERATION.
  
 SHEET M-2B.1: GARAGE EXHAUST FANS INDICATE A LIGHT
 SWITCH STARTER. THESE FANS WOULD NEED TO OPERATE
 CONTINUOUSLY OR BY A CO DETECTOR NOT A MANUAL SWITCH.
  