| 2018-03-26 12:26:34 | PERMIT # 17110779 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED PROVISO: | | | | | | COMPLIANCE OF ALL ITEMS WILL BE VERIFIED IN THE FIELD. | | | FAILURE TO COMPLY WITH FIRE CODE REQUIREMENTS WILL | | | RESULT IN A FAILED INSPECTION. | | | | | | 1) SHEET C5 - PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH | | | TO ALLOW SIMULTANEOUS (ENTRY AND EXIT) GATE ACCESS TO | | | EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | NOTE WAS NOT FOUND ON SHEET AS INDICATED IN RESPONSE. | | | | | | 2) COMPLIANCE OF REQUIRED MECHANICAL VENTILATION FOR | | | GARAGE UNITS, OF 1CFM PER 1SF OF FLOOR AREA, TO BE | | | VERIFIED IN THE FIELD. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] |
|