| 2017-12-22 14:33:21 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. LS-0.0 APPLICABLE CODES-AND GUIDE LINES-CHANGE |
| | FLORIDA ACCESSIBILITY 2012 TO FBC ACC 2014 5TH EDITION |
| | AND ADD FHA. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. PROVIDE SIZING CALCULATIONS FOR THE ROOR GUTTERS AND |
| | DOWN SPOUTS. PER FBC PL TABLE 1106.2(2) AND 1106.6 |
| | |
| | 3. SHT.A-7.2 LEGEND #27 THE ELEVATOR SUMP PIT SHALL BE |
| | A MIN OF 24" DEEP. PER FBC 712.3.2 |
| | |
| | 4. SHT. A-10.1 UNIT A2 AND B3 SHOW FHA DESIGN SPEC FOR |
| | BATHEOOMS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. A-10.1 UNIT B2 WHAT FHA DESIGN SPEC IS MASTER |
| | BATH IT IS CALLED OUT AS USABLE PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT. A-10.2 THIS BUILDING IS NOT REQUIRED TO COMPLY |
| | WITH FBC ACC 2014 I'M CONFUSED ON WHY YOU HAVE DETAILS |
| | FOR THIS CODE ON THE PLAN COULD YOU PLEASE CLARIFY THIS |
| | FOR ME. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7.SHT. A-10.1 PLEASE PLACE DIMENSIONS ON THE CLEAR |
| | FLOOR SPACE FOR THE FIXTURES. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 8. SHT. A-10.3 PLEASE PROVIDE THE DIMENSION FOR THE TOP |
| | OF THE BACKING TO FINISH FLOOR ON THE SHOWER DETAIL |
| | SHALL BE 38" MIN. PER FHA DESIGN MANUAL REQ. 6 PG. 6.12 |
| | |
| | 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B |
| | BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN |
| | HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52 |
| | |
| | 10. SHT. A10.1 PROVIDE DIMENSION BETWEEN APPLIANCES AND |
| | OPPOSING ELEMENTS IN THE KITCHENS. PER FHA DES MAN REQ |
| | 7 PG.7.7 |
| | |
| | 11. SHT. A-10.1 UNIT A2 PLEASE PROVIDE THE DIMENSION OF |
| | THE WING WALL NEXT TO THE WC IT SHALL BE 24" MAX.. PER |
| | FHA DESIGN MANUAL. REQ. 7 PG. 7.43 |
| | |
| | 12. THE DRAIN FOR THE ELEVATOR SUMP IS NOT SHOWN ON THE |
| | SANITARY ISOMETRICS OR THE FLOOR PLAN PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED |
| | FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 14 PLEASE PLACE NOT ON THE PLAN A SEPARATE PERMIT IS |
| | REQUIRED FOR THE BACKFLOW ASSEMBLY. PER WPB UTILITIES |
| | DEPARTMENT |
| | |
| | 15. ARE THERE ANY FLOOR DRAIN IN THIS BUILDING IT SHOWS |
| | A DRAIN SCHEDULE ON SHT. P6.1 PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |