2017-12-22 14:33:211ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. LS-0.0 APPLICABLE CODES-AND GUIDE LINES-CHANGE
 FLORIDA ACCESSIBILITY 2012 TO FBC ACC 2014 5TH EDITION
 AND ADD FHA. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE SIZING CALCULATIONS FOR THE ROOR GUTTERS AND
 DOWN SPOUTS. PER FBC PL TABLE 1106.2(2) AND 1106.6
  
 3. SHT.A-7.2 LEGEND #27 THE ELEVATOR SUMP PIT SHALL BE
 A MIN OF 24" DEEP. PER FBC 712.3.2
  
 4. SHT. A-10.1 UNIT A2 AND B3 SHOW FHA DESIGN SPEC FOR
 BATHEOOMS. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A-10.1 UNIT B2 WHAT FHA DESIGN SPEC IS MASTER
 BATH IT IS CALLED OUT AS USABLE PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. SHT. A-10.2 THIS BUILDING IS NOT REQUIRED TO COMPLY
 WITH FBC ACC 2014 I'M CONFUSED ON WHY YOU HAVE DETAILS
 FOR THIS CODE ON THE PLAN COULD YOU PLEASE CLARIFY THIS
 FOR ME. PER WPB AMEND TO FBC 107.2.1
  
 7.SHT. A-10.1 PLEASE PLACE DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE FIXTURES. PER WPB AMEND TO FBC
 107.2.1
  
 8. SHT. A-10.3 PLEASE PROVIDE THE DIMENSION FOR THE TOP
 OF THE BACKING TO FINISH FLOOR ON THE SHOWER DETAIL
 SHALL BE 38" MIN. PER FHA DESIGN MANUAL REQ. 6 PG. 6.12
  
 9. SHTS. A-10.1 + A-10.3 THE VANITY'S IN SPEC B
 BATHROOMS SHALL BE A MAX OF 24" IN DEPTH AND 34" IN
 HEIGHT. PER FHA DESIGN MANUAL. REQ. 7 PG. 7.43 + 7.52
  
 10. SHT. A10.1 PROVIDE DIMENSION BETWEEN APPLIANCES AND
 OPPOSING ELEMENTS IN THE KITCHENS. PER FHA DES MAN REQ
 7 PG.7.7
  
 11. SHT. A-10.1 UNIT A2 PLEASE PROVIDE THE DIMENSION OF
 THE WING WALL NEXT TO THE WC IT SHALL BE 24" MAX.. PER
 FHA DESIGN MANUAL. REQ. 7 PG. 7.43
  
 12. THE DRAIN FOR THE ELEVATOR SUMP IS NOT SHOWN ON THE
 SANITARY ISOMETRICS OR THE FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 13. PLEASE INDICATE TYPE OF AIR HAMMER ARRESTOR USED
 FOR THE CLOTHES WASHING MACHINE AND DISHWASHER. PER WPB
 AMEND TO FBC 107.2.1
  
 14 PLEASE PLACE NOT ON THE PLAN A SEPARATE PERMIT IS
 REQUIRED FOR THE BACKFLOW ASSEMBLY. PER WPB UTILITIES
 DEPARTMENT
  
 15. ARE THERE ANY FLOOR DRAIN IN THIS BUILDING IT SHOWS
 A DRAIN SCHEDULE ON SHT. P6.1 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH