Plan Review Notes
Plan Review Notes For Permit 17110779
Permit Number 17110779
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-12-04 13:16:27PERMIT # 17110779
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMENTS:
  
 1) SHEET C5: PROVIDE A FIRE DEPARTMENT KNOX KEY SWITCH
 TO OPEN BOTH THE ENTRY AND EXIT GATES, SIMULTANEOUSLY.
  
 2) SHEET M-5.3: GARAGE EXHAUST FANS (150CFM) APPEAR TO
 SMALL TO VENTILATE THE GARAGES IN ACCORDANCE WITH NFPA
 88A.
 PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1 CFM PER 1 SF OF
 FLOOR AREA DURING HOURS OF NORMAL OPERATION.
  
 3) SHEET M-5.3: GARAGE EXHAUST FANS INDICATE A LIGHT
 SWITCH STARTER. THESE FANS WOULD NEED TO OPERATE
 CONTINUOUSLY OR BY A CO DETECTOR; NOT A MANUAL SWITCH.
  
 4) FS SHEETS: SHEET FS 3.A.1. IS NOT INCLUDED. PLEASE
 ADVISE IF THE SHEET IS MSSING OR IF THE NUMBER IS
 INCORRECT. (THERE IS A FS 2.A.1 AND FS 4.A.1.)
  
 5) PLEASE SEE REVIEW AND RESPOND TO ALL OTHER PLAN
 REVIEW COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  