| 2017-12-22 12:51:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS CORRECTED ARE NOTED AS CORRECTED |
| | REMAINING ITEMS HAVE ADDITIONAL NOTES IN PARENTHESES. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED |
| | 6. THERE ARE 2 SETS OF PLANS PROVIDED, BUT ONLY ONE OF |
| | THEM SHOWS THE LOCATION OF THE LIGHTS TO BE INSTALLED. |
| | PROVIDE CORRECTION. FBC 107.2.1 (ONLY ONE PAGE OF THE |
| | CORRECTED PLAN WAS PROVIDED, WE MUST HAVE 2 SETS, |
| | ORGANIZED AND STAPLED TOGETHER.) |
| | 7. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN |
| | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| | 471.003(2)(H); 471.025; FBC 107.2.1 (ALL SHEETS OF THE |
| | PLAN MUST BE SIGNED. ONLY ONE SHEET WAS SIGNED.) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |