Plan Review Notes
Plan Review Notes For Permit 17110776
Permit Number 17110776
Review Stop E
Sequence Number 2
Notes
Date Text
2017-12-22 12:51:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS CORRECTED ARE NOTED AS CORRECTED
 REMAINING ITEMS HAVE ADDITIONAL NOTES IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED
 6. THERE ARE 2 SETS OF PLANS PROVIDED, BUT ONLY ONE OF
 THEM SHOWS THE LOCATION OF THE LIGHTS TO BE INSTALLED.
 PROVIDE CORRECTION. FBC 107.2.1 (ONLY ONE PAGE OF THE
 CORRECTED PLAN WAS PROVIDED, WE MUST HAVE 2 SETS,
 ORGANIZED AND STAPLED TOGETHER.)
 7. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1 (ALL SHEETS OF THE
 PLAN MUST BE SIGNED. ONLY ONE SHEET WAS SIGNED.)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  