| Plan Review Notes For Permit 17110762 |
| Permit Number |
17110762 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-02 19:08:22 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD ENGINEERING DOES NOT LIST THE | | | MODEL NUMBER OF THE GENERAC GENERATOR SPECIFICATIONS | | | THAT WERE SUBMITTED. (MODELS G007043-0 OR G007042-0) | | | PLEASE PROVIDE MATCHING DOCUMENTS. FBC 107.2.1 | | | THE MODEL NUMBERS (006551-1 OR 006552-0) FOR THE NEW | | | GENERAC GENERATOR SPECIFICATIONS THAT WERE SUBMITTED | | | ARE ALSO NOT LISTED ON THE PAD ENGINEERING. |
|