Plan Review Notes
Plan Review Notes For Permit 17110730
Permit Number 17110730
Review Stop M
Sequence Number 1
Notes
Date Text
2017-12-07 17:09:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE DOCUMENTS
 FOR THE NEW ADDITION. FBC ENERGY CONSERVATION SECTIONS
 R402 OR R405.
  
 2) FBC-R 303.9 REQUIRES HABITABLE ROOMS TO BE HEATED.
 SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS TO
 SHOW THAT THE EXISTING HEATING AND COOLING EQUIPMENT IS
 ADEQUATE TO CONDITION THE NEW ADDITION. FBCR-M1401.3
  
 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
  
 4) SPECIFY THE SIZE OF THE DUCT THAT WILL BE CONNECTED
 TO THE EXISTING DISTRIBUTION BOX. FBC 107.2.1
  
 5) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT THE
 NEW MASTER BEDROOM. HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR PROPER BALANCED
 RETURN AIR EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS
 AND LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE
 MASTER SUITE SHALL BE INCLUDED.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.