| 2017-12-07 17:09:16 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE DOCUMENTS |
| | FOR THE NEW ADDITION. FBC ENERGY CONSERVATION SECTIONS |
| | R402 OR R405. |
| | |
| | 2) FBC-R 303.9 REQUIRES HABITABLE ROOMS TO BE HEATED. |
| | SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS TO |
| | SHOW THAT THE EXISTING HEATING AND COOLING EQUIPMENT IS |
| | ADEQUATE TO CONDITION THE NEW ADDITION. FBCR-M1401.3 |
| | |
| | 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND |
| | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN |
| | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT |
| | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. |
| | |
| | 4) SPECIFY THE SIZE OF THE DUCT THAT WILL BE CONNECTED |
| | TO THE EXISTING DISTRIBUTION BOX. FBC 107.2.1 |
| | |
| | 5) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT THE |
| | NEW MASTER BEDROOM. HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR PROPER BALANCED |
| | RETURN AIR EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS |
| | AND LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE |
| | MASTER SUITE SHALL BE INCLUDED. |
| | |
| | 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |