| 2017-12-07 18:32:49 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PROVIDE A STRUCTURAL REINFORCING AND FLASHING DETAIL |
| | AT WINDOW OPENING IN NEW BLOCK WALL. FBC-R611.8.1 & |
| | FBC-R703.8 |
| | |
| | 2) SPECIFY THE LINTEL FOR THE WINDOW OPENING AND |
| | PROVIDE A LINTEL TABLE. FBC-R611.8.2 |
| | |
| | 3) PROVIDE WINDOW BUCK FASTENING DETAIL ON THE PLANS. |
| | FBC-R612.7.2.1 |
| | |
| | 4) PROVIDE AN EXTERIOR WALL SECTION THAT SHOWS THE 16" |
| | OVERHANG DETAILS. FBC 107.2.1 |
| | |
| | 5) PROVIDE AN EXTERIOR WALL SECTION THAT SHOWS THE 12" |
| | OVERHANG. DETAILS. FBC 107.2.1 |
| | |
| | 6) THE AREA TABULATIONS THAT ARE PROVIDED ON SHEETS 01 |
| | AND E-1 ARE UN-CLEAR AND CONFUSING. SPECIFY THE |
| | EXISTING AREAS AND THE NEW AREAS. THE EXISTING A/C AREA |
| | SHOULD BE ON TOP, FOLLOWED BY THE EXISTING LAUNDRY AREA |
| | AND FINALLY THE EXISTING TOTAL AREA. BELOW THIS LIST |
| | THE NEW ADDITION A/C AREA, FOLLOWED BY THE NEW TOTAL |
| | A/C AREA AND THEN THE NEW TOTAL AREA. FBC 107.2.1 |
| | |
| | 7) REVISE THE EXTERIOR WALL SECTION TO SHOW THAT THE |
| | WALL INSULATION WILL BE CONTINOUS UP TO THE ROOF |
| | INSULATION. THE SECTION ON SHEET 02 DOES NOT SHOW ANY |
| | INSULATION IN THE UN-VENTED ATTIC SPACE FROM THE TOP OF |
| | THE BLOCK WALL TO THE INSULATION ON THE UNDERSIDE OF |
| | THE ROOF. FBC-R806.5 |
| | |
| | 8) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT |
| | FOR THE ICYNENE SPRAY FOAM INSULATION THAT WILL BE |
| | USED. FBC-R316 |
| | |
| | 9) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS AND THE SINGLE HUNG WINDOW. |
| | |
| | 10) ONE SET OF THE PLANS HAS NOT BE SIGNED AND SEALED |
| | BY THE FLORIDA LICENSED PROFESSIONAL ENGINEER. F.S. 471 |
| | AND FAC 61G15-23.003 REQUIRE THE ENGINEER'S HANDWRITTEN |
| | SIGNATURE AND SEAL ON THE PLANS. |
| | |
| | 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |