2017-12-06 07:01:0412/6/2017 GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THE GAS METER IS SERVERLY UNDERSIZED FOR WHAT THE
 EXISTING .5 LB METER CAN FLOW PER ROB @ FPU. YOU WILL
 NEED TO RE-SUBMIT A NEW ISOMETRIC AND RESPOND TO THE
 FOLLOWING COMMENTS BELOW AND UNGRADE THE SYSTEM TO A 2
 LB SYSTEM
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2
  
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3
  
 4) THE PLANS INDICATE AN EXISTING GAS METER WHICH IS
 UNDER SIZED. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
  