2017-11-30 09:28:251ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ALTERNATE ROLL IN TYPE SHOWER SHALL BE 36" WIDE
 48" DOES NOT COMPLY. PER FBC ACC 608.2.3 ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS.
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36
 INCHES WIDE AND 60 INCHES DEEP MINIMUM CLEAR INSIDE
 DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING SIDES.
 A 36 INCH WIDE MINIMUM ENTRY SHALL BE PROVIDED AT ONE
 END OF THE LONG SIDE OF THE COMPARTMENT.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.3
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT
 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR
 SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15
 INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE
 SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY.
  
 3. SHT. 1 NOTE #12 SHALL COMPLY WITH FBC 2509.2 BASE
 FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 O.C. FOR 1/2-INCH THICK (12.7 MM) WATER-RESISTANT
 GYPSUM BACKING BOARD AND MORE THAN 16 INCHES O.C. FOR
 5/8-INCH THICK WATER-RESISTANT GYPSUM BACKING BOARD.
  
 4. THE BRANCH DRAIN OF THE WASHING MACHINE SHALL BE A
 MIN OF 3". PER FBC PL 406.2
  
 5. A LINT TRAP IS REQUIRED ON THE WASHING MACHINE
 DRAIN. PER FBC PL 1003.6
  
 6. THE DRAIN PIPE FOR THE TEMPERATURE AND PRESSURE
 RELIEF VALVE ON THE WATER HEATER SHALL DISCHARGE A MAX
 OF 6" ABOVE S1 OR INTO THE WATER HEATER PAN IT SHALL
 NOT DISCHARGE 1/2" BELOW CEILING AS NOTED ON WATER
 HEATER DETAIL SHT 3. PER FBC PL 504.6 (6)(10)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  