| Plan Review Notes For Permit 17110707 |
| Permit Number |
17110707 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-13 09:01:09 | PLAN DENIED | | | 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR. | | | 2014 RESIDENTIAL CODE. | | | 2) MISSING DUCT SIZE ON SUPPLY DUCT IN MASTER | | | HALL WAY. SECTION 107 FBC 2014 | | | 3) SEER ON ENERGY CALCULATIONS AND PLAN | | | DO NOT MATCH. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|