Plan Review Notes
Plan Review Notes For Permit 17110707
Permit Number 17110707
Review Stop B
Sequence Number 1
Notes
Date Text
2017-12-27 11:15:31BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 3. SEE PLAN PAGE A-1 - PLAN SHOWS NEW FRONT DOOR
 PROPOSED. PROVIDE PRODUCT APPROVAL FOR PROPOSED DOOR.
 4. SEE PLAN PAGE A-1 - EXT. WALL, EAST ELEVATION -
 VERTICAL REINFORCING REQUIRED AT ENDS OF NEW WALL PER
 FBC R606.12.2.2.3.
 4A. PROVIDE CONNECTION DETAIL FOR NEW CMU WALL TO
 EXISTING WALL.
 5. ONLY ONE SET OF PRODUCT APPROVALS PROVIDED FOR
 WINDOWS, SGD AND MULLIONS. SUBMITTAL DOCUMENTS SHALL BE
 IN DUPLICATE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 R606.12.2.2.3 REINFORCEMENT REQUIREMENTS FOR MASONRY
 ELEMENTS.
 MASONRY ELEMENTS LISTED IN SECTION R606.12.2.2.2 SHALL
 BE REINFORCED IN EITHER THE HORIZONTAL OR VERTICAL
 DIRECTION IN ACCORDANCE WITH THE FOLLOWING:
  
 1. HORIZONTAL REINFORCEMENT. HORIZONTAL JOINT
 REINFORCEMENT SHALL CONSIST OF AT LEAST TWO
 LONGITUDINAL W1.7 WIRES SPACED NOT MORE THAN 16 INCHES
 (406 MM) FOR WALLS GREATER THAN 4 INCHES (102 MM) IN
 WIDTH AND AT LEAST ONE LONGITUDINAL W1.7 WIRE SPACED
 NOT MORE THAN 16 INCHES (406 MM) FOR WALLS NOT
 EXCEEDING 4 INCHES (102 MM) IN WIDTH; OR AT LEAST ONE
 NO. 4 BAR SPACED NOT MORE THAN 48 INCHES (1219 MM).
 WHERE TWO LONGITUDINAL WIRES OF JOINT REINFORCEMENT ARE
 USED, THE SPACE BETWEEN THESE WIRES SHALL BE THE WIDEST
 THAT THE MORTAR JOINT WILL ACCOMMODATE. HORIZONTAL
 REINFORCEMENT SHALL BE PROVIDED WITHIN 16 INCHES (406
 MM) OF THE TOP AND BOTTOM OF THESE MASONRY ELEMENTS.
  
 2. VERTICAL REINFORCEMENT. VERTICAL REINFORCEMENT SHALL
 CONSIST OF AT LEAST ONE NO. 4 BAR SPACED NOT MORE THAN
 48 INCHES (1219 MM). VERTICAL REINFORCEMENT SHALL BE
 LOCATED WITHIN 16 INCHES (406 MM) OF THE ENDS OF
 MASONRY WALLS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  