Plan Review Notes
Plan Review Notes For Permit 17110686
Permit Number 17110686
Review Stop P
Sequence Number 1
Notes
Date Text
2017-12-04 06:29:1312-04-2017 1ST PLUMBING REVIEW**DENIED**
  
 1) KITCHEN SINK SHALL NOT DISCHARGE INTO THE HORIZONTAL
 WET VENT OF THE BATHROOM GROUP. FPC 912.1
  
 2) SUPPLY MANUFACTURE SPECS AND INSTALLATION MANUAL FOR
 TANKLESS WATER HEATER. PLEASE BE ADVISED WATER HEATER
 MUST BE SIZED SO THAT ALL FIXTURES AT FULL DEMAND HAVE
 HOT WATER OF (110) FPC604.1 AND FPC 607.1
  
 3) PLEASE SEE ZONING COMMENT FROM PLAN REVIEW PERMIT#
 08090338 DATED 02/12/2008, KITCHEN SINK SHALL NOT BE
 PERMITTED
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695